257/2012 Sb.
The DECREE
of 12 June. July 2012
on the prevention of emissions of substances that Deplete the ozone layer, and the
fluorinated greenhouse gases
The Ministry of the environment shall determine in accordance with section 4, paragraph 4. 3, section 10, paragraph 1.
11 and section 11 (1). 4 of Act No. 73/2012 Coll., on substances that Deplete the
the ozone layer and of the fluorinated greenhouse gases (hereinafter referred to as
the "law"):
§ 1
The subject of the edit
(1) this Ordinance in connection with the applicable provisions of the European
Union ^ 1) ^ 2) lays down the specimen records of equipment, designs for submission
messages, procedures for the activities listed in section 10, paragraph 1. 1 and 2 of the law with
the exception procedures consisting of checking the leakage of cooling or
air conditioning equipment, or fire protection systems containing
fluorinated greenhouse gases, and the extent of knowledge required to
recovery, regeneration or disposal of substances that Deplete the
the ozone layer (hereinafter referred to as "controlled substance").
(2) this Ordinance has been notified in accordance with the directive of the European
Parliament and Council Directive 98/34/EC of 22 December 2004. June 1998 on the procedure for the
the provision of information in the field of technical standards and regulations and of rules
for information society services, as amended by Directive 98/48/EC.
§ 2
Pattern the records of equipment
Pattern the records of equipment under section 4 (4). 2 of the Act is set out in
Annex No 1 to this notice.
§ 3
Patterns of messages
Patterns for reporting under section 11 (2). 1 and 2 of the Act are listed in the
Annex No 2 and 3 to this notice.
§ 4
Procedures for the management of controlled substances, the fluorinated greenhouse
gases or devices containing such substances
(1) the procedures for recovery of controlled substances and fluorinated
greenhouse gases in the recycling of the products of the domestic cooling, process and
How to check and registration of these substances are listed in annex 4 to
This Decree.
(2) the procedures for recovery of controlled substances and fluorinated
greenhouse gases in refrigeration equipment than other recycling products
domestic refrigeration, the procedure and the way to control and registration of these substances
are listed in annex 4 to this notice.
(3) the procedures for recovery of controlled substances and fluorinated
greenhouse gases when recycling products for fire protection,
the procedure and method of control and registration of these substances are listed in annex
No 5 to this Decree.
(4) the degree of modifications I and II binding technology according to annex No 4 to this
the Decree shall be carried out within a single technological unit; This total
means a fixed group of technological equipment
operating within a single campus or the various stages of mobile
přistavované technology in facilities for the collection of waste for recovery
controlled substances when recycling products.
§ 5
The procedures for checking the tightness of the cooling circuits of equipment containing
controlled substances
(1) before checking the leakage of cooling circuits of the device with the content
controlled substances certified person checks the records of equipment,
paying particular attention to the information about the recurring
the issues and problem areas.
(2) a certified person shall carry out the following parts of refrigeration
and air conditioners or heat pumps:
and joints)
b) valves, including spindles,
(c)), including on removable gasket gasket dehydrátorech and filters,
(d)) part of the system exposed by the vibration and
e) connection to the safety and operating equipment.
(3) in carrying out the checks for leakage of cooling and air conditioning
device or the heat pump containing controlled substances shall apply
the certified person direct method of measurement referred to in paragraph 4, or
indirect measuring method referred to in paragraph 7. Methods of indirect measurement
It can be used only when the parameters of the equipment referred to in paragraph 7,
to be analysed, shows what is the filling of controlled substances
referred to in the records of the device and the likelihood of their escape.
(4) to check for leaks, you can use one or more of the following methods
direct measurement:
and check the cooling circuits) and their components, for which there is
the risk of leaks, use the apparatus for the detection of gas adjusted for
the refrigerant used in the system,
(b)) the introduction of liquids for UV detection or suitable dyes into the circuit,
(c)), the special bubble, or SOAP.
(5) in the application of the direct methods, you can apply the following procedures:
and gas detection equipment) referred to in paragraph 4 (b). and) are
checked once every 12 months to ensure their proper
functioning; the sensitivity of the portable device for the detection of gases must be
at least 5 g/year
(b)) the introduction of liquids for UV detection or the appropriate colours into the cooling
the circuit is carried out only if the manufacturer of the equipment approved by such
detection methods as technically possible; This method may be used only
staff certified to carry out the activities that constitute an intervention
in the refrigeration circuit containing a controlled substance, or
(c)) If using the methods referred to in paragraph 4 does not detect the leak and
the part referred to in paragraph 2 do not show signs of a leak, but certified
the person believes that a leak occurs, you must check the other parts of the
the device, which can assume the possibility of leakage.
(6) before the pressure test using a direct measurement of nitrogen content
oxygen gas or other suitable for pressure tightness test
It is necessary that the person certified to the recovery of controlled substances from
the type of equipment carried out the recovery of controlled substances from all over the
the system.
(7) to check the tightness of the indirect method uses the certified person
Visual and manual control device and the analysis of one or more
the following parameters:
and pressure)
(b)), the temperature
(c)) the current compressor,
(d)) the level of liquids
(e) the quantity of the refrigerant) supplemented.
(8) Any suspected leakage of controlled substances must be verified by checking the
leakage measurement using the direct method, in accordance with paragraph 4.
(9) the method used for the checks for leakage shall be recorded in the accounting books
the device.
§ 6
The procedures for checking the tightness of the fire protection system that contains
controlled substances
(1) before checking the tightness of the fire protection system certified person
checks the records of equipment, with particular attention to the
information on recurring issues and problem areas.
(2) in determining the damage and signs of leakage performs certified
person a Visual check of the controls, receptacles, couplings, which are
exposed to pressure, and other components.
(3) the suspected leak in these situations:
and) firmly installed leakage detection system reports a leak,
(b) shows the pressure tank) by more than 10% after deducting the impact of
temperature, or
(c) shows loss of stack) of the quantity of extinguishing agent of more than 5%.
(4) the proper functioning of the tyre-pressure monitoring and equipment weight
checks the certified person once every 12 months.
(5) the procedure used checks for leakage shall be recorded in the accounting books
the device.
section 7 of the
The extent of knowledge required for recovery, regeneration or
disposal of controlled substances
(1) the scope of the required knowledge in the framework of the training of natural persons
perform recovery of controlled substances and otherwise manipulate
controlled substances within the recycling of products:
and basic knowledge about the protection) of the ozone layer and the legislation in
the area of the protection of the ozone layer,
b) basic knowledge of the concept of the potential damage to the ozone layer and the
on the use of controlled substances,
(c) the method of filling and emptying) cylinders with controlled substances in liquid
and gaseous form,
(d) the method of determining the quantity) of the controlled substance in the bottle,
(e)) the requirements for the correct procedures for handling, storage and transport
controlled substances,
(f)) method of operation apparatus for extraction of controlled substances,
(g)) the way the correct handling of discarded products
(h)) way to keeping and
I) basic knowledge of the physical and chemical properties
controlled substances including their recycling and regeneration.
(2) the scope of the required knowledge in the framework of the training of natural persons
handling controlled substances within their regeneration:
and basic knowledge about the protection) of the ozone layer and the legislation in
the area of the protection of the ozone layer,
b) basic knowledge of the concept of the potential damage to the ozone layer and the
on the use of controlled substances,
(c) the method of filling and emptying) cylinders with controlled substances in liquid
and gaseous form,
(d) the method of determining the quantity) of the controlled substance in the bottle,
(e)) the requirements for the correct procedures for handling, storage and transport
controlled substances,
(f)) method of operation apparatus for the regeneration of controlled substances,
(g) the method of registration and management)
h) basic knowledge of the physical and chemical properties
controlled substances including their recycling and regeneration.
(3) the scope of the required knowledge in the framework of the training of natural persons
handling controlled substances within the framework of their destruction:
and basic knowledge about the protection) of the ozone layer and the legislation in
the area of the protection of the ozone layer,
b) basic knowledge of the concept of the potential damage to the ozone layer and the
on the use of controlled substances,
(c) on the proper procedures) the requirements in the handling, storage and transport
controlled substances,
(d)) way to keeping
e) basic knowledge of the physical and chemical properties
controlled substances, including the procedures for their disposal and
(f) the method of filling and emptying) cylinders with controlled substances in liquid
and gaseous form and the method of determining the quantity of the controlled substance in
the bottle.
(4) the provisions of paragraph 3 (f)) does not apply, if the
training of individuals, that handle regulated substances
they are transported by pipeline from the point of origination to the point of disposal.
(5) the Training referred to in paragraphs 1, 2 and 3 provides the operator that
performs recovery, regeneration and destruction of controlled substances.
§ 8
The transitional provisions of the
The registration book of the device in accordance with the model set out in Decree No.
279/2009 Coll. on the prevention of emissions of controlled substances and fluorinated
greenhouse gases, as an effective until the date of entry into force of this
the Decree, is considered a registration book of the device in accordance with section 2 of this
the Ordinance, with the exception of the newly introduced accounting books after 1. January 2014,
You can only use the model set out in annex 1 to this notice.
§ 9
The effectiveness of the
This Decree shall take effect on 1 January 2005. September 2012, with the exception of the provisions
§ 7 (2). 2, which shall take effect on 1 January 2005. January 2013.
Minister:
Mgr. Cottage in r.
Annex 1
Pattern the records of equipment
Annex 2
Pattern halonech report, fire protection systems and fire extinguishers
devices with halons pursuant to section 11 (1). 2 of the Act
Annex 3
Model report on fluorinated greenhouse gases obtained or
transmitted from or to another Member State of the European Union, about the disposal of the
fluorinated greenhouse gases, placing on the market, the recovery,
recycling, recovery and disposal of controlled substances pursuant to section 11 (1).
1 of the law
Annex 4
The procedure for recovery of controlled substances and fluorinated greenhouse
gases from refrigeration equipment
This quality and control provisions apply to processing, in particular
recycling discarded refrigeration equipment containing controlled substances and
fluorinated greenhouse gases. Conditions for the collection, in order to
their recycling and reclamation for reuse or disposal.
1. the terms Used for the purposes of this annex.
1. Nadouvadlem means a controlled substance or a fluorinated greenhouse
the gas, which have been used in the manufacture of thermally insulating rigid foam
materials to their foaming and are contained in them.
2. Recycling of refrigeration equipment "means all the measures on the
recording, storage and adjustment of the refrigeration equipment containing
controlled substances and fluorinated greenhouse gases, with the goal of
These measures, in particular the capture of controlled substances and
fluorinated greenhouse gases and their transfer for disposal, as well as
the acquisition of valuable secondary raw materials and ecological manner in order to
further use.
3. The cooling device for a household means a household refrigerator
the typical structure for use in the home and other similar use to
in the commercial content of 270 litres; the device can be equipped with a separate
freezer and the freezer section or be without them (= device type 1).
4. Combined refrigerator and freezer box for household means
cooling equipment in the typical for the household and for other similar
use a commercial content from 270 gallons to 350 litres, which are usually
equipped with a separate freezer box and partition (= device type 2).
5. The freezer cabinets and containers for household refrigerators in
the design for the household and for other similar use to the
the size of 500 liters of commercial content (= device type 3).
6. Collection and storage are all measures designed to ensure
the collection of refrigeration equipment in the place of occurrence to the point of their edits; to
This fall as measures for temporary storage of refrigeration equipment
from the producer of the waste, so measures in the úpravářském business.
7. Adjusting means
Open the cooling circuit) and suction, controlled substances, the fluorinated
greenhouse gases and oils from the circulation of the cooling circuit (grade I),
(b)) the release of foam heat insulating materials with content
controlled substances and fluorinated greenhouse gases, other materials
parts of the equipment, parts and components, respectively. the cooling elements
the device, always with the help of appropriate technical equipment with the aim of the Department
controlled substances so as to prevent their release into the air (the degree of
(II)),
(c)) sift and classification of substances acquired in grade I and grade
(II), as well as their preparation for further use and disposal.
2. Collection and recycling of refrigeration equipment
2.1.1 General requirements
It is necessary to carry out such protective measures, which effectively prevents the
theft or loss of collected refrigeration equipment or their
unauthorized sales.
2.1.2. Specific requirements for the collection and storage of
2.1.2.1 Subscription refrigeration equipment
A subscription is necessary to make the refrigeration appliances in a way as to avoid the
damage to the equipment, which would cause the leakage of substances affecting the
environment or that would complicate or make it impossible to edit. In particular, it is
should be appropriate measures to exclude damage to the cooling circuit. Is
must still have appropriate equipment ready to capture flowing
liquids (oils) and sorption materials for disposal and binding
flowing liquids in sufficient quantity. The owners of refrigeration
device transmitting them to the persons carrying out the collection and providing
Storage notifies the provable way on measures necessary for the protection of
These devices against the release of controlled substances and fluorinated
greenhouse gases.
2.1.2.2 Transport refrigeration equipment
In the transport refrigeration equipment it is necessary to take measures against leakage
liquids. Refrigeration equipment carried on means of transport is
need to consolidate so as to avoid damage to the device and to escape
controlled substances and fluorinated greenhouse gases. Cooling device
It is necessary for loading and unloading to protect from impact, reversing them or
the fall. Cooling equipment must be transported in the position prescribed by the
the manufacturer of the device type for the transport of new products.
2.1.2.3 Storage refrigeration equipment
Taken by the cooling device must be registered in accordance with the quantity of each
types of controlled substances and fluorinated greenhouse gases and the type of
isolation. The device is necessary to check whether they are not mechanically damaged
and the extent of the damage in writing. It is necessary to compile a list of
serious damage to the model provided in this annex, while it is possible to choose
the form's. The storage of the received refrigeration equipment must be performed with the
taking into account the water protection legislation, in particular the requirements on
gripper bathtub. Storage it is necessary to ensure that it was out of the question
damage to the refrigeration equipment, which would complicate or prevent further
editing or would cause the leakage of substances affecting the environment.
2.2 Modify refrigeration equipment
2.2.1 General requirements
It is necessary to draw up a description of technological processes and their progress
adjustment of the refrigeration equipment containing controlled substances and fluorinated
greenhouse gases. Furthermore, it is necessary to lay down the appropriate assignment
the individual operating segments of the processes and their course (operating
order). It is necessary to adopt protective measures against theft or loss
obtained in any other way or refrigeration equipment their unauthorized
the sale. It is not permissible to rebuild the putting into circulation of complete to
the recycling of the equipment transmitted, which contain controlled substances (in the
the cooling system and/or in the foam insulation). All taken cooling
the device is necessary to undergo treatment.
2.2.2 special requirements for adjustment of the refrigeration equipment containing
controlled substances and fluorinated greenhouse gases
The adjustment includes these basic activities
and aspirate) controlled substances and fluorinated greenhouse gases and oils
from the cooling circuit (grade I),
(b)) the release of thermal insulating foam materials with content
controlled substances, and other materials, parts, equipment, respectively.
parts and elements of the refrigeration equipment, using appropriate
technical equipment with the aim of Department of controlled substances without their
escape into the environment, the components containing hazardous substances and
the use of valuable materials (level II),
(c)) sift and classification of the substances and materials gained within the degree and
and (II), including the preparation for future use or disposal.
Modification of refrigeration equipment containing controlled substances and fluorinated
greenhouse gases should be carried out in accordance with other legal
Regulation ^ 3).
Individually, it is necessary to fulfill the following requirements:
Treatment-stage I
1. To aspirate the controlled substances and fluorinated greenhouse gases and
oils from the cooling circuit, use suitable handling equipment, which
allows movement with refrigeration equipment to the optimum working position for the
Extractor.
2. controlled substances and fluorinated greenhouse gases extracted together with the
oil cooling circuit with minimum leakage of controlled substances and
fluorinated greenhouse gases into the atmosphere.
3. When taking technical liquids (controlled substances and fluorinated
greenhouse gas and oil), a special tool to open the cooling circuit
and the contents extracted in podtlakovém mode, automatically controlled multiple-
safety system (pressure sensing devices and a safety pressure valves,
switch off the device, depending on the time and weight).
4. the quantity of controlled substances of expressed and fluorinated greenhouse gases
and cooling oil a day to detect and record in writing.
5. the residual content of controlled substances and fluorinated greenhouse gases
in the oil from the refrigerant circuit must be less than 0.1% by mass
the percentage determined by submitted together with the application for a certificate.
6. the equipment must include an appropriate measuring device to indicate the
collected quantities of controlled substances and fluorinated greenhouse
gases and the appropriate number of refrigeration equipment. The procedure used must
include the appropriate device, which prevents the manipulation with the subsequent
the release of controlled substances and fluorinated greenhouse gases.
7. Expressed controlled substances and fluorinated greenhouse gases sort out and
classify according to the procedure referred to in point 2.2.2, the numbers 3 and kept by species
in separate containers.
8. The workplace equipped with suitable bathtubs to capture fluids and their
the accidental release into the environment.
Treatment-stage II
1. Thermal insulation foams containing controlled substances or fluorinated
greenhouse gas cooling device separate from the cabinets be analysed(1)(2),
which is carried out in a closed environment in podtlakovém technology
the device. Controlled substance while capturing from the appropriate
separation processes (for example, freeze drying or adsorption).
2. When adjusting the heat insulating foam containing controlled substances or
fluorinated greenhouse gases destroy the pores of the grinding, as well as
degassed matrix minced material (at elevated temperature) obtained from
degassing of pore.
3. the quantity of controlled substances or of fluorinated greenhouse
gases from thermal insulating foam daily record.
4. the residual content of controlled substances or of fluorinated greenhouse
gases from thermal insulating foam in the odplyněném foam material must not
must not exceed 0.2% by mass and must be determined by the method
submitted together with the application for a certificate.
5. The water contained in the insulation foam capture and edit as
waste water.
6. clean the exhaust air from the device with the appropriate reference systems. As
to comply with the limit value through less than 5 g of controlled
substances in an hour. Compliance with the limit values to control the suitable analytical
in the continuous measurement method, submitted together with the application for
certificate.
2.2.3 when you make adjustments according to the level II on the site of mobile technology
the operator shall inform the Czech environmental inspection within 14
days before the start of the activity. The notification contains the address of the place of performance
the activity, the date of commencement and the date of its termination.
2.2.4 Preparation to recovery and disposal
1. Disassembled or by editing the components and materials obtained
separated into fractions for use as secondary raw materials. To
disposal are intended primarily to chlorofluorocarbons CFC-11 and CFC-12
(they are the only substances having effect on the ozone layer). Used
treatment technology of materials must ensure that individual materials
they were dirt or other materials.
2. Removed from editing equipment obtained parts and the
materials stored in compliance with the relevant legislation.
3. Warehousing provide way more use or purchasing
disposal and to prevent damage to the environment.
4. Liquid threatening water or parts containing liquids
threatening water save in separate, clearly marked and
the design allowed containers in accordance with the relevant laws
provisions.
5. The electrolytic capacitors to store in a dry, separate and if
may be a separate room in plastic containers or steel barrels.
These containers to keep tightly closed and have saved over a sufficiently large
gripper bathtub.
6. Components of the mercury store in sealed plastic
containers secure against impact, which are always during the whole storage
hermetically sealed.
7. Absorption materials for leaking fluids and absorbent materials on the
the mercury have always available and ready to use. Used the absorption
disposing of materials as hazardous waste.
3. Documentation requirements, registration and operating rules
3.1 Documentation
3.1.1 Documentation permits issued
All permits, approvals, consents and the official decision
document, the lead in the current state, and have freely accessible to the competent
the inspection authorities.
3.1.2 rules of operation
Prepare corporate operating procedure, which contains rules and guidelines for the
the operating safety and order. Operating procedure also applies to customers and
visitors to the company and therefore must be posted in a conspicuous place
in the place of activity, at least in its main parts. The order also contains a
rules for behavior in case of danger.
3.1.3 Operating Manual
Develop an operations manual, which lists the measures necessary for the
proper recycling of refrigeration equipment containing controlled substances,
as well as for operational safety in normal operation, repairs and
operational malfunctions. Also included here are the tasks and areas
the liability of employees and a description of the process of recycling of refrigeration equipment
containing controlled substances.
3.1.4 the Operation journal
As the document is properly carried out by the recycling of refrigeration equipment containing
controlled substances and fluorinated greenhouse gases lead to operating
journal in electronic form. The journal contains
and documentation of all taken) refrigeration equipment to adjust according to the
product type and quantity; a copy of the slips issued for
equipment suppliers,
(b) type and quantity of documentation) all removed the cooling
the device, a recovered controlled substances and fluorinated greenhouse
gas intended for further use and disposal, together with the relevant
documents under other legislation ^ 2)
c) records of events, in particular of malfunction
including the list of possible causes and subsequent corrective measures,
d) protocols on functional checks and maintenance work carried out;
the Protocol for the functional check means a record of inspections
the device, which runs the recycling of refrigeration equipment, which
contains the controlled substance or the fluorinated greenhouse gas.
3.1.5 other documentation
All persons, which are forwarded to the controlled substances, materials, parts
device, or parts and components for further use or
disposal, lead the documentation with proof that they own
the necessary permits, approvals, certificates, etc. In addition to document what
procedures for adjustments, use or disposal and that are used for more
methods are chosen for the resulting output material.
3.2 Special control provisions for the monitoring of the productivity of traffic
3.2.1 Detecting the quantity of controlled substances and fluorinated greenhouse
gases obtained from Grade I and grade II edit
The survey obtained quantities of controlled substances from section 2.2.2
to carry out the method of measurement and the method of comparing the annual numbers.
3.2.1.1. Method of measurement
3.2.1.1.1 degree of editing and
When measuring the edit at least 1000 refrigeration equipment, which are completely
flushes the cooling circuits. Znovuzískaná controlled refrigerant by type of
collect and consider. From the data collected to calculate the average amount of
regulated refrigerant znovuzískaného from one cooling device
(g). Uses the form provided at the end of this annex.
3.2.1.1.2. The degree of editing II
When you edit at least 1000 measurements of refrigeration equipment. When determining the
the average quantity of CFC-11 chlorfluoruhlovodíku znovuzískaného from
one of the cooling device to follow the type of device (type 1 =
household refrigerators, type 2 = combination refrigerators and freezers, type
3 = display cabinets and showcases for the home). The vessels prepared for collecting
chlorfluoruhlovodíku CFC-11 to consider the empty before the start of the edit and the
What more could a filling after. The result of the weighing in kg divided
the number of customized refrigeration equipment (all equipment including defective
pieces). As a result of calculated the average amount of chlorfluoruhlovodíku
CFC-11 on one cooling device in grams. Apply form
referred to at the end of this annex.
3.2.1.2 Method annual numbers
The quantity of the controlled substances and fluorinated greenhouse gases from the degree
Also, the grade II respectively, that was obtained when editing refrigeration equipment
and proven to be passed to the disposal, divide by the number of pieces prepared in
the period of one calendar year.
3.2.1.3. Other methods
For the determination of the average quantities of controlled substances and fluorinated
greenhouse gases in refrigeration equipment, you can also use other methods
referred to in the certificate request.
3.2.2 Detecting residual quantity of controlled substances and fluorinated
greenhouse gases in the oil from the refrigerant circuit Measurement of residual content
controlled substances and fluorinated greenhouse gases in the oil cooling
circuit to perform the analytical method submitted together with the application for
certificate. The result is determined by the ratio of the controlled substances and
fluorinated greenhouse gas in grams per kilogram of
oil and as a percentage by mass of controlled substances and fluorinated
greenhouse gases in the oil.
3.2.3 Survey of residual content of chlorfluoruhlovodíku in the degassed
powder fraction of the thermal insulation foams to determine the residual
the content of chlorfluoruhlovodíku (CFC-11) in samples of degassed, powder
fraction of the thermal insulation foams from refrigeration equipment to carry out
the method of analysis presented together with the application for a certificate.
The result is the determination of weight percent in chlorfluoruhlovodíku
degassed, powder fraction of thermal insulation foams from cooling
the device.
4. Custom control
The operator to continuously ensure compliance with binding technology and continuously
performs the custom control including control measures arising from the
section 4. On the examinations carried out a written record indicating the
the shortcomings identified and the measures taken and their fulfilment.
Annex 5
The procedure for recovery of controlled substances and fluorinated greenhouse
When recycling products for fire protection
This quality and control provisions apply for recycling of fire
equipment and systems, fire protection, regeneration and recovery
controlled substances contained in them. Governing the conditions for their
collection, recycling, reprocessing and the storage of controlled substances for the purpose of
their extraordinary use to ensure the basic needs of the State
(critical uses, process agents, special use for
the health and life of humans, use in science and research, etc.) or
their destruction.
1. the objective of recycling of products and equipment
The aim of recycling of products and equipment is primarily controlled capture
substances and fluorinated greenhouse gases and their regeneration and
storage for critical use or their transmission to the proper
disposal, as well as obtaining secondary raw materials an environmentally suitable way.
Thus obtained raw materials to be reused.
2. Collection and recycling of fire extinguishers and fire protection systems
2.1 Provisions for the collection and storage of
2.1.1 General requirements for storage
Carry out protective measures to prevent the leakage of controlled substances and
fluorinated greenhouse gases into the atmosphere, theft or loss
collected by fire-extinguishers, fire protection systems and
controlled substances and fluorinated greenhouse gases or unauthorized
the sale of controlled substances and fluorinated greenhouse gases and products,
that contain them.
2.1.2. Specific requirements for the collection and storage of
2.1.2.1 collection of fire extinguishers and fire protection systems
The collection of fire extinguishers and fire protection systems to be carried out,
to avoid the damage that would cause the leak
controlled substances or fluorinated greenhouse gases or which would
complicate or even prevent their recovery. In particular, it should be appropriate
measures to exclude damage to the valve of the pressure vessel. If the fire extinguisher
device or system fire protection comes in a special warehouse
halon certified person notifies that person during their transmission on
the measures necessary for the protection against the release of the contained controlled substances and
fluorinated greenhouse gas, if necessary.
2.1.2.2. The carriage of fire extinguishers and fire protection systems
In the carriage of fire extinguishers, take measures against leakage of regulated
substances and fluorinated greenhouse gases. Fastening of transported
fire extinguishers on vehicles to ensure that there are no
damage to the fire extinguishers. Fire extinguishers for loading and
landing to protect from impact or fall.
2.1.2.3. The storage of controlled substances and fluorinated greenhouse
gases, fire extinguishers and fire protection systems
Adopted by the fire extinguishers and fire protection systems pursuant to
the different types of controlled substances and fluorinated greenhouse gases.
Control devices and systems, whether they are not mechanically damaged.
Compile a list of serious damage, taking the form of a chosen
the certified person. Storage ensure that was out of the question
the damage of fire extinguishers, which would complicate or prevent aspiration
controlled substances and fluorinated greenhouse gases or caused
his escape. Containers for the storage of controlled substances and fluorinated
greenhouse gases before being sucked and regeneration have properly identified
and divided according to the type of the contained controlled substances and fluorinated
greenhouse gases.
2.2 the Recycling of fire extinguishers and fire protection systems
recovery of controlled substances and fluorinated greenhouse gases
Elaborate description of technological processes and during extraction
controlled substances and fluorinated greenhouse gases from the fire
equipment or of fire protection systems and their subsequent
recycling, recovery and storage for the purposes of critical uses. These
processes must take place in a hermetically sealed circuit, which avoids leakage
controlled substances and fluorinated greenhouse gases into the atmosphere. U
reclaimed controlled substances and fluorinated greenhouse gases
must be restored to the original properties of the controlled substances and fluorinated
greenhouse gases in their 100% value. Furthermore, it must be established
the assignment of the individual operating segments of the processes and
their course (operating procedures). It is not permissible to reuse the extinguishing
the appliance into circulation without recycling or reclamation of the contained
controlled substances and fluorinated greenhouse gases. After recycling, or
regeneration of controlled substances and fluorinated greenhouse gases
possible its reuse on the basis of the certificate. Recovery
controlled substances and fluorinated greenhouse gases and their
storage until their critical use or disposal must be
implemented within a single technological unit. Technological
in total, for the purposes of this provision, means a group of technological
devices installed in one area.
2.3. Specific requirements for the recycling of fire extinguishers and systems
fire protection
1. the technology must include suitable measuring equipment to
determine the actual quantities of controlled substances and fluorinated
greenhouse gas emissions, the procedure used must include appropriate facilities which
prevents leakage of controlled substances and fluorinated greenhouse gases in
the surrounding environment.
2. Aspirate the controlled substances and fluorinated greenhouse gases from
the original containers must take place in a hermetically sealed circuit without
the possibility of their escaping into the surrounding environment.
3. Recycling and reclamation of controlled substances and fluorinated
greenhouse gases must be carried out on the device, which ensures the renewal of
their original characteristics without the possibility of their escaping into the surrounding
environment.
4. Using a controlled substance or fluorinated greenhouse gases in containers
for their storage in hermetically closed circuit without options
their escape into the surrounding environment.
5. The disassembled or by editing the components and materials obtained
separate and save for use as secondary raw materials.
6. the premises in which the extraction takes place, recycling and recharging
controlled substances and fluorinated greenhouse gases to equip
Automatic detector leakage of controlled substances and fluorinated
greenhouse gases.
2.4 preparing for use and disposal
2.4.1 General provisions
1. Reclaimed controlled substances and fluorinated greenhouse gases after
their overdrafts to their storage containers to sort out and
Save in a special warehouse for halon.
2. Store separately recovered regulated substances and fluorinated
greenhouse gases intended for disposal and reclaimed controlled substances
and fluorinated greenhouse gases intended for critical use.
3. the premises of the special warehouse have fitted with an automatic detector
leakage of controlled substances and fluorinated greenhouse gases.
2.4.2 Analysis of controlled substances and fluorinated greenhouse gases
After recycling or regeneration and before using the controlled
substances and fluorinated greenhouse gases shall ensure that the operator of a special
the inventory of its chemical analysis to determine whether recycled or
reclaimed controlled substances and fluorinated greenhouse gases meet the
the requirements of the quality standards. The analysis of controlled substances and fluorinated
greenhouse gas emissions must be done even before its recycling in the event that the
There are doubts about the declared content delivered containers in controlled
substances and fluorinated greenhouse gases.
3. Documentation requirements, registration, operating rules and the qualifications of the
persons
3.1 Documentation
3.1.1 Documentation permits issued
All permits, approvals, consents and the official decision document
and the lead in the current state, and have freely accessible to the control
to the authorities.
3.1.2 rules of operation
Prepare corporate operating procedure, which contains standard provisions and
instructions for operating safety and order. Also applies to customers and
visitors to the special store halon and therefore is posted on the well
conspicuous place at the entrance to the establishment, at least in its main
parts. The order also contains rules for behavior in case of danger.
3.1.3 Operating Manual
Develop an operations manual, which lists the measures necessary for the
proper recycling of fire extinguishers and fire protection systems,
as well as for operational safety in normal operation, repairs and
operational malfunctions. Also included here are the tasks and areas
the responsibilities of staff and the description of the course work in the recycling.
3.1.4 the working instructions
For activities of importance for the security and protection of the environment
the environment to draw up a work instruction that is
accessible.
3.1.5 the Operation journal
As the document duly carried out by fire extinguishers and recycling systems
fire protection lead the operating journal in electronic form if
It can be. The journal contains
and documentation of all taken) fire extinguishers and systems
fire protection for recovery contained in them regulated
substances and fluorinated greenhouse gases, their quantity and quantity
contained halon; a copy of the certificate for the vendor on the surrender of the fire fighting
the device or controlled substances and fluorinated greenhouse gases in
Special warehouse for halon,
(b) documentation of all stored) fire extinguishers and systems
fire protection and a recovered regulated substances and fluorinated
greenhouse gas emissions (type and quantity) intended for further use and
disposal, an overview of the type and quantity of recycled and
reclaimed controlled substances and fluorinated greenhouse gases
(c)), special events, primarily operating disorders including possible causes
and subsequent corrective measures,
(d) a copy of the protocols of inspections).
3.1.6 other documentation
Keep the documentation of all persons, which are forwarded to the regulated
substances and fluorinated greenhouse gases, fire extinguishers or systems
fire protection for critical use or disposal. At the same time
keep copies of certificates in the documentation of persons, which will be regulated
substances and fluorinated greenhouse gases, fire extinguishers or stable
fire-extinguishing equipment containing controlled substances and fluorinated
greenhouse gases released, which will perform the addition or
installation for critical uses.
3.1.7 the requirements for physical persons
Staff carrying out recycling fire extinguishers, systems
fire protection and recovery of controlled substances and fluorinated
greenhouse gases must have a valid certificate as regards stationary
fire protection systems and fire extinguishers containing certain
fluorinated greenhouse gases.
4. the provisions on the control of
4.1 Custom control
The operator to continuously ensure compliance with quality provisions and
continuously performs its own control. In the framework of the own-checks are
all the control measures required by binding technology. About
the visit is conducted by written record indicating the detected
deficiencies, measures taken and their fulfilment.
4.2 checking the registration of substances
The operator shall send in quarterly intervals, regular reports on the
the quantity and condition of the stored, controlled substances and fluorinated
greenhouse gases, the Ministry of the environment.
4.3 Check for leaks-the methods used
Check tightness of containers with uskladněnými controlled substances and
fluorinated greenhouse gases shall be carried out in particular by the detector
halogenated derivatives of hydrocarbons and on their regular weighing. Spaces,
in which the handling of controlled substances and fluorinated
greenhouse gases and the premises where they are stored must be
secured by the automatic alarm, which detects the leak
controlled substances and fluorinated greenhouse gases.
This quality and control provisions apply for recycling of fire
equipment and systems, fire protection and recovery of the regulated
substances and fluorinated greenhouse gases contained in them. Governing the
the conditions for their collection for recycling, reprocessing and storage of
because of their extraordinary use to ensure basic
the needs of the State (the critical uses, process agents, special
use to ensure the health and life of humans, use in science and research
etc.) or their destruction.
1) European Parliament and Council Regulation (EC) No 1005/2009 of 16 January.
September 2009 on substances that Deplete the ozone layer, as amended.
2) European Parliament and Council Regulation (EC) No 842/2006 of 17 May 2006.
May 2006 on certain fluorinated greenhouse gases, as
the text of the.
3) Law No 185/2001 Coll., on waste and amending certain other
laws, as amended.