257/2012 Sb.



The DECREE



of 12 June. July 2012



on the prevention of emissions of substances that Deplete the ozone layer, and the

fluorinated greenhouse gases



The Ministry of the environment shall determine in accordance with section 4, paragraph 4. 3, section 10, paragraph 1.

11 and section 11 (1). 4 of Act No. 73/2012 Coll., on substances that Deplete the

the ozone layer and of the fluorinated greenhouse gases (hereinafter referred to as

the "law"):



§ 1



The subject of the edit



(1) this Ordinance in connection with the applicable provisions of the European

Union ^ 1) ^ 2) lays down the specimen records of equipment, designs for submission

messages, procedures for the activities listed in section 10, paragraph 1. 1 and 2 of the law with

the exception procedures consisting of checking the leakage of cooling or

air conditioning equipment, or fire protection systems containing

fluorinated greenhouse gases, and the extent of knowledge required to

recovery, regeneration or disposal of substances that Deplete the

the ozone layer (hereinafter referred to as "controlled substance").



(2) this Ordinance has been notified in accordance with the directive of the European

Parliament and Council Directive 98/34/EC of 22 December 2004. June 1998 on the procedure for the

the provision of information in the field of technical standards and regulations and of rules

for information society services, as amended by Directive 98/48/EC.



§ 2



Pattern the records of equipment



Pattern the records of equipment under section 4 (4). 2 of the Act is set out in

Annex No 1 to this notice.



§ 3



Patterns of messages



Patterns for reporting under section 11 (2). 1 and 2 of the Act are listed in the

Annex No 2 and 3 to this notice.



§ 4



Procedures for the management of controlled substances, the fluorinated greenhouse

gases or devices containing such substances



(1) the procedures for recovery of controlled substances and fluorinated

greenhouse gases in the recycling of the products of the domestic cooling, process and

How to check and registration of these substances are listed in annex 4 to

This Decree.



(2) the procedures for recovery of controlled substances and fluorinated

greenhouse gases in refrigeration equipment than other recycling products

domestic refrigeration, the procedure and the way to control and registration of these substances

are listed in annex 4 to this notice.



(3) the procedures for recovery of controlled substances and fluorinated

greenhouse gases when recycling products for fire protection,

the procedure and method of control and registration of these substances are listed in annex

No 5 to this Decree.



(4) the degree of modifications I and II binding technology according to annex No 4 to this

the Decree shall be carried out within a single technological unit; This total

means a fixed group of technological equipment

operating within a single campus or the various stages of mobile

přistavované technology in facilities for the collection of waste for recovery

controlled substances when recycling products.



§ 5



The procedures for checking the tightness of the cooling circuits of equipment containing

controlled substances



(1) before checking the leakage of cooling circuits of the device with the content

controlled substances certified person checks the records of equipment,

paying particular attention to the information about the recurring

the issues and problem areas.



(2) a certified person shall carry out the following parts of refrigeration

and air conditioners or heat pumps:



and joints)



b) valves, including spindles,



(c)), including on removable gasket gasket dehydrátorech and filters,



(d)) part of the system exposed by the vibration and



e) connection to the safety and operating equipment.



(3) in carrying out the checks for leakage of cooling and air conditioning

device or the heat pump containing controlled substances shall apply

the certified person direct method of measurement referred to in paragraph 4, or

indirect measuring method referred to in paragraph 7. Methods of indirect measurement

It can be used only when the parameters of the equipment referred to in paragraph 7,

to be analysed, shows what is the filling of controlled substances

referred to in the records of the device and the likelihood of their escape.



(4) to check for leaks, you can use one or more of the following methods

direct measurement:



and check the cooling circuits) and their components, for which there is

the risk of leaks, use the apparatus for the detection of gas adjusted for

the refrigerant used in the system,



(b)) the introduction of liquids for UV detection or suitable dyes into the circuit,



(c)), the special bubble, or SOAP.



(5) in the application of the direct methods, you can apply the following procedures:



and gas detection equipment) referred to in paragraph 4 (b). and) are

checked once every 12 months to ensure their proper

functioning; the sensitivity of the portable device for the detection of gases must be

at least 5 g/year



(b)) the introduction of liquids for UV detection or the appropriate colours into the cooling

the circuit is carried out only if the manufacturer of the equipment approved by such

detection methods as technically possible; This method may be used only

staff certified to carry out the activities that constitute an intervention

in the refrigeration circuit containing a controlled substance, or



(c)) If using the methods referred to in paragraph 4 does not detect the leak and

the part referred to in paragraph 2 do not show signs of a leak, but certified

the person believes that a leak occurs, you must check the other parts of the

the device, which can assume the possibility of leakage.



(6) before the pressure test using a direct measurement of nitrogen content

oxygen gas or other suitable for pressure tightness test

It is necessary that the person certified to the recovery of controlled substances from

the type of equipment carried out the recovery of controlled substances from all over the

the system.



(7) to check the tightness of the indirect method uses the certified person

Visual and manual control device and the analysis of one or more

the following parameters:



and pressure)



(b)), the temperature



(c)) the current compressor,



(d)) the level of liquids



(e) the quantity of the refrigerant) supplemented.



(8) Any suspected leakage of controlled substances must be verified by checking the

leakage measurement using the direct method, in accordance with paragraph 4.



(9) the method used for the checks for leakage shall be recorded in the accounting books

the device.



§ 6



The procedures for checking the tightness of the fire protection system that contains

controlled substances



(1) before checking the tightness of the fire protection system certified person

checks the records of equipment, with particular attention to the

information on recurring issues and problem areas.



(2) in determining the damage and signs of leakage performs certified

person a Visual check of the controls, receptacles, couplings, which are

exposed to pressure, and other components.



(3) the suspected leak in these situations:



and) firmly installed leakage detection system reports a leak,



(b) shows the pressure tank) by more than 10% after deducting the impact of

temperature, or



(c) shows loss of stack) of the quantity of extinguishing agent of more than 5%.



(4) the proper functioning of the tyre-pressure monitoring and equipment weight

checks the certified person once every 12 months.



(5) the procedure used checks for leakage shall be recorded in the accounting books

the device.



section 7 of the



The extent of knowledge required for recovery, regeneration or

disposal of controlled substances



(1) the scope of the required knowledge in the framework of the training of natural persons

perform recovery of controlled substances and otherwise manipulate

controlled substances within the recycling of products:



and basic knowledge about the protection) of the ozone layer and the legislation in

the area of the protection of the ozone layer,



b) basic knowledge of the concept of the potential damage to the ozone layer and the

on the use of controlled substances,



(c) the method of filling and emptying) cylinders with controlled substances in liquid

and gaseous form,



(d) the method of determining the quantity) of the controlled substance in the bottle,



(e)) the requirements for the correct procedures for handling, storage and transport

controlled substances,



(f)) method of operation apparatus for extraction of controlled substances,



(g)) the way the correct handling of discarded products



(h)) way to keeping and



I) basic knowledge of the physical and chemical properties

controlled substances including their recycling and regeneration.



(2) the scope of the required knowledge in the framework of the training of natural persons

handling controlled substances within their regeneration:



and basic knowledge about the protection) of the ozone layer and the legislation in

the area of the protection of the ozone layer,



b) basic knowledge of the concept of the potential damage to the ozone layer and the

on the use of controlled substances,



(c) the method of filling and emptying) cylinders with controlled substances in liquid

and gaseous form,



(d) the method of determining the quantity) of the controlled substance in the bottle,



(e)) the requirements for the correct procedures for handling, storage and transport

controlled substances,



(f)) method of operation apparatus for the regeneration of controlled substances,



(g) the method of registration and management)



h) basic knowledge of the physical and chemical properties

controlled substances including their recycling and regeneration.



(3) the scope of the required knowledge in the framework of the training of natural persons

handling controlled substances within the framework of their destruction:



and basic knowledge about the protection) of the ozone layer and the legislation in

the area of the protection of the ozone layer,



b) basic knowledge of the concept of the potential damage to the ozone layer and the

on the use of controlled substances,



(c) on the proper procedures) the requirements in the handling, storage and transport

controlled substances,



(d)) way to keeping



e) basic knowledge of the physical and chemical properties

controlled substances, including the procedures for their disposal and



(f) the method of filling and emptying) cylinders with controlled substances in liquid

and gaseous form and the method of determining the quantity of the controlled substance in

the bottle.



(4) the provisions of paragraph 3 (f)) does not apply, if the

training of individuals, that handle regulated substances

they are transported by pipeline from the point of origination to the point of disposal.



(5) the Training referred to in paragraphs 1, 2 and 3 provides the operator that

performs recovery, regeneration and destruction of controlled substances.



§ 8



The transitional provisions of the



The registration book of the device in accordance with the model set out in Decree No.


279/2009 Coll. on the prevention of emissions of controlled substances and fluorinated

greenhouse gases, as an effective until the date of entry into force of this

the Decree, is considered a registration book of the device in accordance with section 2 of this

the Ordinance, with the exception of the newly introduced accounting books after 1. January 2014,

You can only use the model set out in annex 1 to this notice.



§ 9



The effectiveness of the



This Decree shall take effect on 1 January 2005. September 2012, with the exception of the provisions

§ 7 (2). 2, which shall take effect on 1 January 2005. January 2013.



Minister:



Mgr. Cottage in r.



Annex 1



Pattern the records of equipment



Annex 2



Pattern halonech report, fire protection systems and fire extinguishers

devices with halons pursuant to section 11 (1). 2 of the Act



Annex 3



Model report on fluorinated greenhouse gases obtained or

transmitted from or to another Member State of the European Union, about the disposal of the

fluorinated greenhouse gases, placing on the market, the recovery,

recycling, recovery and disposal of controlled substances pursuant to section 11 (1).

1 of the law



Annex 4



The procedure for recovery of controlled substances and fluorinated greenhouse

gases from refrigeration equipment



This quality and control provisions apply to processing, in particular

recycling discarded refrigeration equipment containing controlled substances and

fluorinated greenhouse gases. Conditions for the collection, in order to

their recycling and reclamation for reuse or disposal.



1. the terms Used for the purposes of this annex.



1. Nadouvadlem means a controlled substance or a fluorinated greenhouse

the gas, which have been used in the manufacture of thermally insulating rigid foam

materials to their foaming and are contained in them.



2. Recycling of refrigeration equipment "means all the measures on the

recording, storage and adjustment of the refrigeration equipment containing

controlled substances and fluorinated greenhouse gases, with the goal of

These measures, in particular the capture of controlled substances and

fluorinated greenhouse gases and their transfer for disposal, as well as

the acquisition of valuable secondary raw materials and ecological manner in order to

further use.



3. The cooling device for a household means a household refrigerator

the typical structure for use in the home and other similar use to

in the commercial content of 270 litres; the device can be equipped with a separate

freezer and the freezer section or be without them (= device type 1).



4. Combined refrigerator and freezer box for household means

cooling equipment in the typical for the household and for other similar

use a commercial content from 270 gallons to 350 litres, which are usually

equipped with a separate freezer box and partition (= device type 2).



5. The freezer cabinets and containers for household refrigerators in

the design for the household and for other similar use to the

the size of 500 liters of commercial content (= device type 3).



6. Collection and storage are all measures designed to ensure

the collection of refrigeration equipment in the place of occurrence to the point of their edits; to

This fall as measures for temporary storage of refrigeration equipment

from the producer of the waste, so measures in the úpravářském business.



7. Adjusting means



Open the cooling circuit) and suction, controlled substances, the fluorinated

greenhouse gases and oils from the circulation of the cooling circuit (grade I),



(b)) the release of foam heat insulating materials with content

controlled substances and fluorinated greenhouse gases, other materials

parts of the equipment, parts and components, respectively. the cooling elements

the device, always with the help of appropriate technical equipment with the aim of the Department

controlled substances so as to prevent their release into the air (the degree of

(II)),



(c)) sift and classification of substances acquired in grade I and grade

(II), as well as their preparation for further use and disposal.



2. Collection and recycling of refrigeration equipment



2.1.1 General requirements



It is necessary to carry out such protective measures, which effectively prevents the

theft or loss of collected refrigeration equipment or their

unauthorized sales.



2.1.2. Specific requirements for the collection and storage of



2.1.2.1 Subscription refrigeration equipment



A subscription is necessary to make the refrigeration appliances in a way as to avoid the

damage to the equipment, which would cause the leakage of substances affecting the

environment or that would complicate or make it impossible to edit. In particular, it is

should be appropriate measures to exclude damage to the cooling circuit. Is

must still have appropriate equipment ready to capture flowing

liquids (oils) and sorption materials for disposal and binding

flowing liquids in sufficient quantity. The owners of refrigeration

device transmitting them to the persons carrying out the collection and providing

Storage notifies the provable way on measures necessary for the protection of

These devices against the release of controlled substances and fluorinated

greenhouse gases.



2.1.2.2 Transport refrigeration equipment



In the transport refrigeration equipment it is necessary to take measures against leakage

liquids. Refrigeration equipment carried on means of transport is

need to consolidate so as to avoid damage to the device and to escape

controlled substances and fluorinated greenhouse gases. Cooling device

It is necessary for loading and unloading to protect from impact, reversing them or

the fall. Cooling equipment must be transported in the position prescribed by the

the manufacturer of the device type for the transport of new products.



2.1.2.3 Storage refrigeration equipment



Taken by the cooling device must be registered in accordance with the quantity of each

types of controlled substances and fluorinated greenhouse gases and the type of

isolation. The device is necessary to check whether they are not mechanically damaged

and the extent of the damage in writing. It is necessary to compile a list of

serious damage to the model provided in this annex, while it is possible to choose

the form's. The storage of the received refrigeration equipment must be performed with the

taking into account the water protection legislation, in particular the requirements on

gripper bathtub. Storage it is necessary to ensure that it was out of the question

damage to the refrigeration equipment, which would complicate or prevent further

editing or would cause the leakage of substances affecting the environment.



2.2 Modify refrigeration equipment



2.2.1 General requirements



It is necessary to draw up a description of technological processes and their progress

adjustment of the refrigeration equipment containing controlled substances and fluorinated

greenhouse gases. Furthermore, it is necessary to lay down the appropriate assignment

the individual operating segments of the processes and their course (operating

order). It is necessary to adopt protective measures against theft or loss

obtained in any other way or refrigeration equipment their unauthorized

the sale. It is not permissible to rebuild the putting into circulation of complete to

the recycling of the equipment transmitted, which contain controlled substances (in the

the cooling system and/or in the foam insulation). All taken cooling

the device is necessary to undergo treatment.



2.2.2 special requirements for adjustment of the refrigeration equipment containing

controlled substances and fluorinated greenhouse gases



The adjustment includes these basic activities



and aspirate) controlled substances and fluorinated greenhouse gases and oils

from the cooling circuit (grade I),



(b)) the release of thermal insulating foam materials with content

controlled substances, and other materials, parts, equipment, respectively.

parts and elements of the refrigeration equipment, using appropriate

technical equipment with the aim of Department of controlled substances without their

escape into the environment, the components containing hazardous substances and

the use of valuable materials (level II),



(c)) sift and classification of the substances and materials gained within the degree and

and (II), including the preparation for future use or disposal.



Modification of refrigeration equipment containing controlled substances and fluorinated

greenhouse gases should be carried out in accordance with other legal

Regulation ^ 3).



Individually, it is necessary to fulfill the following requirements:



Treatment-stage I



1. To aspirate the controlled substances and fluorinated greenhouse gases and

oils from the cooling circuit, use suitable handling equipment, which

allows movement with refrigeration equipment to the optimum working position for the

Extractor.



2. controlled substances and fluorinated greenhouse gases extracted together with the

oil cooling circuit with minimum leakage of controlled substances and

fluorinated greenhouse gases into the atmosphere.



3. When taking technical liquids (controlled substances and fluorinated

greenhouse gas and oil), a special tool to open the cooling circuit

and the contents extracted in podtlakovém mode, automatically controlled multiple-

safety system (pressure sensing devices and a safety pressure valves,

switch off the device, depending on the time and weight).



4. the quantity of controlled substances of expressed and fluorinated greenhouse gases

and cooling oil a day to detect and record in writing.



5. the residual content of controlled substances and fluorinated greenhouse gases

in the oil from the refrigerant circuit must be less than 0.1% by mass

the percentage determined by submitted together with the application for a certificate.



6. the equipment must include an appropriate measuring device to indicate the

collected quantities of controlled substances and fluorinated greenhouse

gases and the appropriate number of refrigeration equipment. The procedure used must

include the appropriate device, which prevents the manipulation with the subsequent

the release of controlled substances and fluorinated greenhouse gases.



7. Expressed controlled substances and fluorinated greenhouse gases sort out and

classify according to the procedure referred to in point 2.2.2, the numbers 3 and kept by species

in separate containers.



8. The workplace equipped with suitable bathtubs to capture fluids and their

the accidental release into the environment.



Treatment-stage II



1. Thermal insulation foams containing controlled substances or fluorinated

greenhouse gas cooling device separate from the cabinets be analysed(1)(2),

which is carried out in a closed environment in podtlakovém technology

the device. Controlled substance while capturing from the appropriate

separation processes (for example, freeze drying or adsorption).



2. When adjusting the heat insulating foam containing controlled substances or


fluorinated greenhouse gases destroy the pores of the grinding, as well as

degassed matrix minced material (at elevated temperature) obtained from

degassing of pore.



3. the quantity of controlled substances or of fluorinated greenhouse

gases from thermal insulating foam daily record.



4. the residual content of controlled substances or of fluorinated greenhouse

gases from thermal insulating foam in the odplyněném foam material must not

must not exceed 0.2% by mass and must be determined by the method

submitted together with the application for a certificate.



5. The water contained in the insulation foam capture and edit as

waste water.



6. clean the exhaust air from the device with the appropriate reference systems. As

to comply with the limit value through less than 5 g of controlled

substances in an hour. Compliance with the limit values to control the suitable analytical

in the continuous measurement method, submitted together with the application for

certificate.



2.2.3 when you make adjustments according to the level II on the site of mobile technology

the operator shall inform the Czech environmental inspection within 14

days before the start of the activity. The notification contains the address of the place of performance

the activity, the date of commencement and the date of its termination.



2.2.4 Preparation to recovery and disposal



1. Disassembled or by editing the components and materials obtained

separated into fractions for use as secondary raw materials. To

disposal are intended primarily to chlorofluorocarbons CFC-11 and CFC-12

(they are the only substances having effect on the ozone layer). Used

treatment technology of materials must ensure that individual materials

they were dirt or other materials.



2. Removed from editing equipment obtained parts and the

materials stored in compliance with the relevant legislation.



3. Warehousing provide way more use or purchasing

disposal and to prevent damage to the environment.



4. Liquid threatening water or parts containing liquids

threatening water save in separate, clearly marked and

the design allowed containers in accordance with the relevant laws

provisions.



5. The electrolytic capacitors to store in a dry, separate and if

may be a separate room in plastic containers or steel barrels.

These containers to keep tightly closed and have saved over a sufficiently large

gripper bathtub.



6. Components of the mercury store in sealed plastic

containers secure against impact, which are always during the whole storage

hermetically sealed.



7. Absorption materials for leaking fluids and absorbent materials on the

the mercury have always available and ready to use. Used the absorption

disposing of materials as hazardous waste.



3. Documentation requirements, registration and operating rules



3.1 Documentation



3.1.1 Documentation permits issued



All permits, approvals, consents and the official decision

document, the lead in the current state, and have freely accessible to the competent

the inspection authorities.



3.1.2 rules of operation



Prepare corporate operating procedure, which contains rules and guidelines for the

the operating safety and order. Operating procedure also applies to customers and

visitors to the company and therefore must be posted in a conspicuous place

in the place of activity, at least in its main parts. The order also contains a

rules for behavior in case of danger.



3.1.3 Operating Manual



Develop an operations manual, which lists the measures necessary for the

proper recycling of refrigeration equipment containing controlled substances,

as well as for operational safety in normal operation, repairs and

operational malfunctions. Also included here are the tasks and areas

the liability of employees and a description of the process of recycling of refrigeration equipment

containing controlled substances.



3.1.4 the Operation journal



As the document is properly carried out by the recycling of refrigeration equipment containing

controlled substances and fluorinated greenhouse gases lead to operating

journal in electronic form. The journal contains



and documentation of all taken) refrigeration equipment to adjust according to the

product type and quantity; a copy of the slips issued for

equipment suppliers,



(b) type and quantity of documentation) all removed the cooling

the device, a recovered controlled substances and fluorinated greenhouse

gas intended for further use and disposal, together with the relevant

documents under other legislation ^ 2)



c) records of events, in particular of malfunction

including the list of possible causes and subsequent corrective measures,



d) protocols on functional checks and maintenance work carried out;

the Protocol for the functional check means a record of inspections

the device, which runs the recycling of refrigeration equipment, which

contains the controlled substance or the fluorinated greenhouse gas.



3.1.5 other documentation



All persons, which are forwarded to the controlled substances, materials, parts

device, or parts and components for further use or

disposal, lead the documentation with proof that they own

the necessary permits, approvals, certificates, etc. In addition to document what

procedures for adjustments, use or disposal and that are used for more

methods are chosen for the resulting output material.



3.2 Special control provisions for the monitoring of the productivity of traffic



3.2.1 Detecting the quantity of controlled substances and fluorinated greenhouse

gases obtained from Grade I and grade II edit



The survey obtained quantities of controlled substances from section 2.2.2

to carry out the method of measurement and the method of comparing the annual numbers.



3.2.1.1. Method of measurement



3.2.1.1.1 degree of editing and



When measuring the edit at least 1000 refrigeration equipment, which are completely

flushes the cooling circuits. Znovuzískaná controlled refrigerant by type of

collect and consider. From the data collected to calculate the average amount of

regulated refrigerant znovuzískaného from one cooling device

(g). Uses the form provided at the end of this annex.



3.2.1.1.2. The degree of editing II



When you edit at least 1000 measurements of refrigeration equipment. When determining the

the average quantity of CFC-11 chlorfluoruhlovodíku znovuzískaného from

one of the cooling device to follow the type of device (type 1 =

household refrigerators, type 2 = combination refrigerators and freezers, type

3 = display cabinets and showcases for the home). The vessels prepared for collecting

chlorfluoruhlovodíku CFC-11 to consider the empty before the start of the edit and the

What more could a filling after. The result of the weighing in kg divided

the number of customized refrigeration equipment (all equipment including defective

pieces). As a result of calculated the average amount of chlorfluoruhlovodíku

CFC-11 on one cooling device in grams. Apply form

referred to at the end of this annex.



3.2.1.2 Method annual numbers



The quantity of the controlled substances and fluorinated greenhouse gases from the degree

Also, the grade II respectively, that was obtained when editing refrigeration equipment

and proven to be passed to the disposal, divide by the number of pieces prepared in

the period of one calendar year.



3.2.1.3. Other methods



For the determination of the average quantities of controlled substances and fluorinated

greenhouse gases in refrigeration equipment, you can also use other methods

referred to in the certificate request.



3.2.2 Detecting residual quantity of controlled substances and fluorinated

greenhouse gases in the oil from the refrigerant circuit Measurement of residual content

controlled substances and fluorinated greenhouse gases in the oil cooling

circuit to perform the analytical method submitted together with the application for

certificate. The result is determined by the ratio of the controlled substances and

fluorinated greenhouse gas in grams per kilogram of

oil and as a percentage by mass of controlled substances and fluorinated

greenhouse gases in the oil.



3.2.3 Survey of residual content of chlorfluoruhlovodíku in the degassed

powder fraction of the thermal insulation foams to determine the residual

the content of chlorfluoruhlovodíku (CFC-11) in samples of degassed, powder

fraction of the thermal insulation foams from refrigeration equipment to carry out

the method of analysis presented together with the application for a certificate.

The result is the determination of weight percent in chlorfluoruhlovodíku

degassed, powder fraction of thermal insulation foams from cooling

the device.



4. Custom control



The operator to continuously ensure compliance with binding technology and continuously

performs the custom control including control measures arising from the

section 4. On the examinations carried out a written record indicating the

the shortcomings identified and the measures taken and their fulfilment.



Annex 5



The procedure for recovery of controlled substances and fluorinated greenhouse

When recycling products for fire protection



This quality and control provisions apply for recycling of fire

equipment and systems, fire protection, regeneration and recovery

controlled substances contained in them. Governing the conditions for their

collection, recycling, reprocessing and the storage of controlled substances for the purpose of

their extraordinary use to ensure the basic needs of the State

(critical uses, process agents, special use for

the health and life of humans, use in science and research, etc.) or

their destruction.



1. the objective of recycling of products and equipment



The aim of recycling of products and equipment is primarily controlled capture

substances and fluorinated greenhouse gases and their regeneration and

storage for critical use or their transmission to the proper

disposal, as well as obtaining secondary raw materials an environmentally suitable way.

Thus obtained raw materials to be reused.



2. Collection and recycling of fire extinguishers and fire protection systems



2.1 Provisions for the collection and storage of



2.1.1 General requirements for storage



Carry out protective measures to prevent the leakage of controlled substances and

fluorinated greenhouse gases into the atmosphere, theft or loss

collected by fire-extinguishers, fire protection systems and

controlled substances and fluorinated greenhouse gases or unauthorized

the sale of controlled substances and fluorinated greenhouse gases and products,


that contain them.



2.1.2. Specific requirements for the collection and storage of



2.1.2.1 collection of fire extinguishers and fire protection systems



The collection of fire extinguishers and fire protection systems to be carried out,

to avoid the damage that would cause the leak

controlled substances or fluorinated greenhouse gases or which would

complicate or even prevent their recovery. In particular, it should be appropriate

measures to exclude damage to the valve of the pressure vessel. If the fire extinguisher

device or system fire protection comes in a special warehouse

halon certified person notifies that person during their transmission on

the measures necessary for the protection against the release of the contained controlled substances and

fluorinated greenhouse gas, if necessary.



2.1.2.2. The carriage of fire extinguishers and fire protection systems



In the carriage of fire extinguishers, take measures against leakage of regulated

substances and fluorinated greenhouse gases. Fastening of transported

fire extinguishers on vehicles to ensure that there are no

damage to the fire extinguishers. Fire extinguishers for loading and

landing to protect from impact or fall.



2.1.2.3. The storage of controlled substances and fluorinated greenhouse

gases, fire extinguishers and fire protection systems



Adopted by the fire extinguishers and fire protection systems pursuant to

the different types of controlled substances and fluorinated greenhouse gases.

Control devices and systems, whether they are not mechanically damaged.

Compile a list of serious damage, taking the form of a chosen

the certified person. Storage ensure that was out of the question

the damage of fire extinguishers, which would complicate or prevent aspiration

controlled substances and fluorinated greenhouse gases or caused

his escape. Containers for the storage of controlled substances and fluorinated

greenhouse gases before being sucked and regeneration have properly identified

and divided according to the type of the contained controlled substances and fluorinated

greenhouse gases.



2.2 the Recycling of fire extinguishers and fire protection systems

recovery of controlled substances and fluorinated greenhouse gases



Elaborate description of technological processes and during extraction

controlled substances and fluorinated greenhouse gases from the fire

equipment or of fire protection systems and their subsequent

recycling, recovery and storage for the purposes of critical uses. These

processes must take place in a hermetically sealed circuit, which avoids leakage

controlled substances and fluorinated greenhouse gases into the atmosphere. U

reclaimed controlled substances and fluorinated greenhouse gases

must be restored to the original properties of the controlled substances and fluorinated

greenhouse gases in their 100% value. Furthermore, it must be established

the assignment of the individual operating segments of the processes and

their course (operating procedures). It is not permissible to reuse the extinguishing

the appliance into circulation without recycling or reclamation of the contained

controlled substances and fluorinated greenhouse gases. After recycling, or

regeneration of controlled substances and fluorinated greenhouse gases

possible its reuse on the basis of the certificate. Recovery

controlled substances and fluorinated greenhouse gases and their

storage until their critical use or disposal must be

implemented within a single technological unit. Technological

in total, for the purposes of this provision, means a group of technological

devices installed in one area.



2.3. Specific requirements for the recycling of fire extinguishers and systems

fire protection



1. the technology must include suitable measuring equipment to

determine the actual quantities of controlled substances and fluorinated

greenhouse gas emissions, the procedure used must include appropriate facilities which

prevents leakage of controlled substances and fluorinated greenhouse gases in

the surrounding environment.



2. Aspirate the controlled substances and fluorinated greenhouse gases from

the original containers must take place in a hermetically sealed circuit without

the possibility of their escaping into the surrounding environment.



3. Recycling and reclamation of controlled substances and fluorinated

greenhouse gases must be carried out on the device, which ensures the renewal of

their original characteristics without the possibility of their escaping into the surrounding

environment.



4. Using a controlled substance or fluorinated greenhouse gases in containers

for their storage in hermetically closed circuit without options

their escape into the surrounding environment.



5. The disassembled or by editing the components and materials obtained

separate and save for use as secondary raw materials.



6. the premises in which the extraction takes place, recycling and recharging

controlled substances and fluorinated greenhouse gases to equip

Automatic detector leakage of controlled substances and fluorinated

greenhouse gases.



2.4 preparing for use and disposal



2.4.1 General provisions



1. Reclaimed controlled substances and fluorinated greenhouse gases after

their overdrafts to their storage containers to sort out and

Save in a special warehouse for halon.



2. Store separately recovered regulated substances and fluorinated

greenhouse gases intended for disposal and reclaimed controlled substances

and fluorinated greenhouse gases intended for critical use.



3. the premises of the special warehouse have fitted with an automatic detector

leakage of controlled substances and fluorinated greenhouse gases.



2.4.2 Analysis of controlled substances and fluorinated greenhouse gases



After recycling or regeneration and before using the controlled

substances and fluorinated greenhouse gases shall ensure that the operator of a special

the inventory of its chemical analysis to determine whether recycled or

reclaimed controlled substances and fluorinated greenhouse gases meet the

the requirements of the quality standards. The analysis of controlled substances and fluorinated

greenhouse gas emissions must be done even before its recycling in the event that the

There are doubts about the declared content delivered containers in controlled

substances and fluorinated greenhouse gases.



3. Documentation requirements, registration, operating rules and the qualifications of the

persons



3.1 Documentation



3.1.1 Documentation permits issued



All permits, approvals, consents and the official decision document

and the lead in the current state, and have freely accessible to the control

to the authorities.



3.1.2 rules of operation



Prepare corporate operating procedure, which contains standard provisions and

instructions for operating safety and order. Also applies to customers and

visitors to the special store halon and therefore is posted on the well

conspicuous place at the entrance to the establishment, at least in its main

parts. The order also contains rules for behavior in case of danger.



3.1.3 Operating Manual



Develop an operations manual, which lists the measures necessary for the

proper recycling of fire extinguishers and fire protection systems,

as well as for operational safety in normal operation, repairs and

operational malfunctions. Also included here are the tasks and areas

the responsibilities of staff and the description of the course work in the recycling.



3.1.4 the working instructions



For activities of importance for the security and protection of the environment

the environment to draw up a work instruction that is

accessible.



3.1.5 the Operation journal



As the document duly carried out by fire extinguishers and recycling systems

fire protection lead the operating journal in electronic form if

It can be. The journal contains



and documentation of all taken) fire extinguishers and systems

fire protection for recovery contained in them regulated

substances and fluorinated greenhouse gases, their quantity and quantity

contained halon; a copy of the certificate for the vendor on the surrender of the fire fighting

the device or controlled substances and fluorinated greenhouse gases in

Special warehouse for halon,



(b) documentation of all stored) fire extinguishers and systems

fire protection and a recovered regulated substances and fluorinated

greenhouse gas emissions (type and quantity) intended for further use and

disposal, an overview of the type and quantity of recycled and

reclaimed controlled substances and fluorinated greenhouse gases



(c)), special events, primarily operating disorders including possible causes

and subsequent corrective measures,



(d) a copy of the protocols of inspections).



3.1.6 other documentation



Keep the documentation of all persons, which are forwarded to the regulated

substances and fluorinated greenhouse gases, fire extinguishers or systems

fire protection for critical use or disposal. At the same time

keep copies of certificates in the documentation of persons, which will be regulated

substances and fluorinated greenhouse gases, fire extinguishers or stable

fire-extinguishing equipment containing controlled substances and fluorinated

greenhouse gases released, which will perform the addition or

installation for critical uses.



3.1.7 the requirements for physical persons



Staff carrying out recycling fire extinguishers, systems

fire protection and recovery of controlled substances and fluorinated

greenhouse gases must have a valid certificate as regards stationary

fire protection systems and fire extinguishers containing certain

fluorinated greenhouse gases.



4. the provisions on the control of



4.1 Custom control



The operator to continuously ensure compliance with quality provisions and

continuously performs its own control. In the framework of the own-checks are

all the control measures required by binding technology. About

the visit is conducted by written record indicating the detected

deficiencies, measures taken and their fulfilment.



4.2 checking the registration of substances



The operator shall send in quarterly intervals, regular reports on the

the quantity and condition of the stored, controlled substances and fluorinated

greenhouse gases, the Ministry of the environment.



4.3 Check for leaks-the methods used



Check tightness of containers with uskladněnými controlled substances and

fluorinated greenhouse gases shall be carried out in particular by the detector


halogenated derivatives of hydrocarbons and on their regular weighing. Spaces,

in which the handling of controlled substances and fluorinated

greenhouse gases and the premises where they are stored must be

secured by the automatic alarm, which detects the leak

controlled substances and fluorinated greenhouse gases.



This quality and control provisions apply for recycling of fire

equipment and systems, fire protection and recovery of the regulated

substances and fluorinated greenhouse gases contained in them. Governing the

the conditions for their collection for recycling, reprocessing and storage of

because of their extraordinary use to ensure basic

the needs of the State (the critical uses, process agents, special

use to ensure the health and life of humans, use in science and research

etc.) or their destruction.



1) European Parliament and Council Regulation (EC) No 1005/2009 of 16 January.

September 2009 on substances that Deplete the ozone layer, as amended.



2) European Parliament and Council Regulation (EC) No 842/2006 of 17 May 2006.

May 2006 on certain fluorinated greenhouse gases, as

the text of the.



3) Law No 185/2001 Coll., on waste and amending certain other

laws, as amended.