483 regulation of the Federal Minister of the Interior stock for shooting and explosives (explosives storage regulation - SprLV)

On the basis of article 35, paragraph 2 and 3 of the Explosives Act 2010, Federal Law Gazette I no. 121/2009, is prescribed:

Table of contents



1 article General provisions







§ 1.





Scope







§ 2.





Definitions







§ 3.





Basic protection measures







§ 4.





Operating rules







§ 5.





Separate storage







§ 6.





Electrical equipment and lightning protection







§ 7.





Interior







§ 8.





Ventilation and heating







§ 9.





Covering layer







§ 10.





Access







§ 11.





Establishment of multiple stock







§ 12.





Eligibility exceptions







2. section above-ground storage







§ 13.





Safety distances and fire protection zone







§ 14.





Large bearings







§ 15.





Standard bearings







§ 16.





Small storage







§ 17.





Storage for small amounts







3. section underground storage







§ 18.





Basic requirements for underground storage







§ 19.





Access tunnel







§ 20.





Storage and manipulation Chamber







§ 21.





Blast shutter







section 22.





Underground storage in niche







4 section authorisation free storage







section 23.





Storage of small quantities







5. section final and transitional provisions







§ 24.





Entry into force







§ 25.





Transitional provisions







section 26.





Linguistic equal treatment





1 section

General terms and conditions

Scope

§ 1. This regulation have bearings and explosives, insofar as it is not camp, under the mineral commodity law - MinroG, Federal Law Gazette I No 38/1999, the munitions Act 2003 - MunLG 2003, Federal Law Gazette I no. 9, or under section 2 para 16 of the Gewerbeordnung 1994 - GewO 1994, BGBl. No. 194, fall.

Definitions

§ 2. Within the meaning of this regulation means:



1. storage of shooting and explosives: the storage of shooting and explosives to their consumption, excluding the short-term availability prior to use; section 8 of the regulation of blasting - SprengV, Federal Law Gazette applies this provision II No. 358/2004;

2. underground storage: storage embedded in rock or soil formations or niche;

3. transportable storage: a camp that is not associated with the underground and is built with the intention to put it locally.

Basic protection measures

Shooting and explosives are § 3 (1) to store that they are sufficiently protected against



1. influences that can cause an unintended implementation, and 2. influences that can affect their usability.

(2) all external components of a warehouse, as well as the access door including the Castle have sufficient protection against unauthorized acquisition or unauthorized use to provide targeted access. Whether sufficient protection is guaranteed, is to assess in particular by the following criteria:



1. protection from unauthorized access through violence against property, in particular one of the quantities and corresponding to the warehouse a - and burst-resistant access doors including the Castle;

2. protection against random access of lawfully present persons.

(3) in and from camps, and in the fire protection zone is prohibited:



1 smoking as well as any dealing with burning or glowing objects with fire, with an open light or spark-pulling tools, using open flames of any kind, 2 which can cause portability and use of electrical power sources, an unintended ignition, 3. the storage of flammable oxidizing, pyrophoric, or explosive materials other than shooting and explosives and 4. access by unauthorized persons.

(4) in the storage, suitable fire fighting AIDS in sufficient quantities are ready to keep.

Operating rules

§ 4 (1) on the outside of the access to the warehouse is to indicate a prohibition for unauthorized persons. On the inside of the access to the warehouse is that in section 3 para 3 prohibitions referred to in no. 1 to 3 to indicate.

(2) on every access door to a storeroom or a storage chamber, following instructions to install are:



1 upper-surface level and 2. storage classes in accordance with Appendix 1.

(3) the Chambers of warehouse or storage rooms have to serve only the storage of shooting or explosives. In these areas, no other activities may be performed.

(4) a vestibule or a manipulation Chamber may only for the opening of packaging and fiddling with shooting and explosives, as well as for the storage of the used for the storage, handling and use of required tools and equipment to the necessary extent. The storage of other items is prohibited.

Separate storage

5. (1) explosives and igniters should not be stored together in a storage room, a storage chamber or a niche.

(2) Nitrocet may not be stored in a storage room, a storage chamber or a niche with explosives.

Electrical equipment and lightning protection

6. (1) electrical equipment and electrical installations have the State of the art meet and must be particularly protected from dust.

(2) electrical equipment and electrical installations are to be examined by a qualified electrician to its proper state:



1. before the first commissioning of the warehouse, 2nd after any significant change of camp and 3 at least once every three years.

The evidence is to be kept in operation at least over a period of three years.

(3) if the camp by its natural location nor by a sufficient Earth covering adequately against the dangers of atmospheric discharge is protected, and to set up a State of the art lightning protection system is.

Interior

Section 7 (1) in each room and each storage chamber must be present for an orderly warehouse management:



1. adequate facilities such as shelving, shelves, storage racks or pallets, and 2. a suitable thermometer.

(2) be stored igniters not in their original packaging, separate shelves are for the various stages of the ignition time to set up. The ground of the shelves is to prevent mechanical stress of the igniters with an appropriate material, Revet such as felt or wood.

(3) it is an equipotential bonding must be provided which connects all touchable conductive parts in stock.

(4) in an entryway or in a manipulation Chamber at least a table manipulation works and appropriate deletion support in sufficient numbers must exist.

(5) if the camp is accessible, the floor may have no bumps, joints or grooves. A possible flooring must be non-combustible and must have a surface that is easy to clean. He must be securely fastened, electrostatically conductive sufficiently viable, in particular for the storage of electric detonators.

Ventilation and heating

8. (1) has the ventilation to ensure that any occurring gases or vapours that can not accumulate in a lot of dangerous for human health, and condensation is avoided whenever possible.

(2) air vents are so run that from the outside no objects or liquids are introduced or penetrate.

(3) only heating equipment must be used for a heating function which the goods can ignite nor decompose.

Covering layer

9. (1) a covering must be made on all sides, with the exception of access. An erosion is through appropriate measures to counteract such as by justification.

(2) in bulk, a shock-absorbing material is to use, how about medium detachable bottom (loose soil or stitch floor) with a grain size of up to 16 mm.

Access

§ 10 (1) of the access area and the entrances to the camp must suitably designed and safely usable according to the circumstances be.

(2) before the access to the camp, a firewall is to build, which is suitable to derive the shock wave in a direction in which no protecting persons or objects to reside. The peak height of the wall to tower over access to at least one metre. The construction of a protective wall is not necessary with small bearings or, where the terrain or-bewachsung equivalent protection.

(3) doors of a warehouse must open outwards. Doors inside a bearing must be fire retardant.

Establishment of multiple stock


§ 11 (1) several camps are built, is by maintaining a minimum distance to make sure that there is any transfer of implementation in the other stock in the case of the implementation of the stored goods in a warehouse.

(2) to observe a minimum distance which is stock with each other according to the formula Z = to calculate 0.8 L1/3. Where Z is the distance in meters and L the maximum quantities in kilograms. The fire protection zones of ten metres between the camps is to comply with anyway.

(3) storage with opposite approaches (exhaust directions) are not permitted.

(4) between camps, which are in a row and have the same direction, the safety distances in accordance with the table in the Appendix A apply 2 column.

Eligibility exceptions

§ 12 (1) at the request can grant, if necessary, the authority exceptions to the provisions of this regulation, under the terms, limitations and conditions, if safe storage in accordance with the principles of this regulation is ensured by other, equivalent arrangements, such as structural measures.

(2) a request for exemptions referred to in paragraph 1 are all descriptions and AIDS, which are relevant to the assessment of the coveted exception (such as description of the explosives warehouse in performing and planlicher type, map in a suitable scale, in which are all buildings within the safety distance), to connect.

2. section

Above-ground storage

Safety distances and fire protection zone

The safety distances indicated in Appendix 2 are section 13 (1) in above-ground warehouses to comply.

(2) without prejudice to the safety distance referred to in paragraph 1 an at least ten metres wide fire protection zone is the above-ground camp to build, that free is bearings, parking of vehicles, other than charging function, and arid vegetation. No other building may be located in the fire protection zone.

Large bearings

Section 14 (1) in a large camp more than 1000 kg of shooting and explosives may be stored; It may not be achieved but a capacity of 10 000 kg shooting and explosives.

(2) warehouses must have an anteroom and a ventilation and carry storey.

(3) the warehouse may have no more opening except the entrance door and the air vents. The covering layer must be at least one metre.

(4) walls, ceilings and floors are made of reinforced concrete with a minimum thickness of 200 mm to build.

Standard bearings

Section 15 (1) in a standard warehouse up to 1000 kg of shooting and explosives may be stored.

(2) standard bearings have a vestibule or from the storage access an area protected from the weather (forecourt) and a ventilation system. The establishment of a ventilation system may be waived if an effective ventilation by opening the door of the warehouse. The covering layer must be at least one metre.

(3) walls, ceilings and floors are made of reinforced concrete with a minimum thickness of 150 mm to build.

(4) standard bearings can be built as transportable storage. In this case is to call the prospect area in the application.

Small storage

Section 16 (1) in a small warehouse up to 150 kg of shooting and explosives may be stored.

(2) walls, ceilings and floors are made of reinforced concrete with a minimum thickness of 100 mm to build.

(3) the covering layer must be at least half a meter.

(4) by way of derogation by article 3, par. 4 suitable extinguishing AIDS in sufficient quantities in the immediate vicinity of a small warehouse are ready, if not because of the location and of the purpose of the small camp can be waived.

(5) section 15 paragraph 4 shall apply mutatis mutandis.

Storage for small amounts

Shooting or explosives may § 17 (1) Notwithstanding the provisions of the first section up to a volume of 26 kg in its original packaging or in solid, dense containers (boxes, shooting, safety cabinets) in a room the following prerequisites are met, the:



1. the room has to be on the ground and locked.

2. the walls and ceiling of this room must be fire retardant.

3. the floor must have a surface to be cleaned easily and may exhibit no joints, cracks, or comparable wells.

4. the door to this room has to consist of non-combustible materials.

5. window or other openings must be protected against unauthorized access through appropriate grid.

6 next to or immediately above or below the room no living quarters and other rooms to the stay of persons may be located.

7 only equipment must be used for heating, which the goods can ignite nor decompose.

8. in the or a suitable deletion help is willing to keep in front of the room.

(2) in this room may not smoked, still open flame or fire are used and no work involving risk of sparks may be carried. Voltage carrier, which can inadvertently cause an ignition like mobile phones or radios, are not permitted. Manipulation works may not be made to the explosives in this room.

3. section

Underground storage

Basic requirements for underground storage

Section 18 (1) underground storage sites must be sufficiently



1 mountain mechanical influences (such as cave-in or dangerous rock movements), 2. to ride water and 3 mine gas be protected.

(2) underground storage sites must at least



1. an access tunnel, 2. a storage chamber and 3 a manipulation Chamber consisting.

(3) access tunnel, bearing Chambers and chambers of manipulation must be sufficiently dimensioned in accordance with transport and storage conditions and safely accessible.

(4) the minimum distance by which each storage chamber of the areas to be protected above and below ground is according to the formula: D = to measure 2 L 1/3. Where L is the distance in metres the highest quantities in kilograms and D. The distance D with a discount of 10% is to setup a closure of the explosion.

(5) if the construction of walls or ceilings is required, these are in reinforced concrete with a minimum thickness of 200 mm.

(6) every storage chamber and every manipulation is to complete the access tunnel through a lockable door.

(7) the storage has to be that a minimum of ceiling and walls of the Commons Chamber distance of at least 30 cm.

Access tunnel

Section 19 (1) of the access tunnel is to run, that in the case of a detonativen implementation as little impact of the blast shock wave takes place on the surface.

(2) the total length of the access tunnel has to be at least 1.6 times the distance D (§ 18 par. 4).

(3) in the access tunnel, at least two rectangular kinks must be provided. Only those breaks, which are arranged by the first Chamber of the camp at a distance of at least the 0.8-fold operate the distance D (§ 18 para 4) count as buckling. On the kinks, according to deep bouncing bags are to install. The depth of the bouncing bags has to meet at least the width of the studs.

Storage and manipulation Chamber

Section 20 (1) which has minimum distance between the bearing Chambers to be the 0.8-fold operate distance D (§ 18 para 4) with each other and to the Chamber of manipulation.

(2) the storage chambers may, have no further connections with the exception of the access adit.

Blast shutter

§ 21 (1) is there a connection at a camp with protective areas underground or the construction of a protective wall is not sufficient to provide is to minimise the explosion pressure push a closure of the explosion.

(2) the length of (AE in meters) of the access adit of the Commons Chamber of the explosion sealing is calculated depending on the number of breaks from the formula x L0 5 AE = 16.8/3n. In this formula, L means the maximum capacity per storage chamber in kilograms and n the number of rectangular refractions of the open connection between storage chamber and explosion closure. Other facilities reducing the pressure shock wave (such as expansion Chambers) can reduce the length AE.

(3) the size of the explosion catches is so that the formula p = this 65 L / v calculated explosion pressure reliably resist. In this formula, L means the maximum capacity per storage chamber in kilograms, v the contents of the room closed off due to the explosion of seal in litres and p the explosion pressure in kilonewtons per square centimeter.

(4) the doors (cover, fold-out) of explosion shutters are fitted with devices to which prevent a restart ripping through the setback following on the explosion shock.

Underground storage in niche

Shooting or explosives may § 22 (1) Notwithstanding the provisions of the first section and the sections 19 to 21 to be stored to a volume of 150 kg under the following conditions in niches:



1. the distance of the respective niche to the areas to be protected above and below ground has to be at least 10 m.

2. in the presence of multiple niches, these have so arranged to be that they are secured by intervening pillar or barriers against a detonation transmission. The pillar or barriers must have a thickness of at least two meters.

3. niche may be built only in page lines or blind places and the like, where they are unaffected by business operations.

4.

Niches are in compliance with fire protection technical and weather-technical issues to build and operate.

5 niches have to be locked. Section 3 subsection 2 applies to the access door or the door of the niche.

6. in the area of niche suitable extinguishing AIDS are ready to keep.

(2) in the area of niche may not smoked, still open flame or fire are used and no work involving risk of sparks may be carried. Devices in explosion-proof execution, which can trigger an unintended implementation may not be carried to the niches. In terms of niche manipulation work may not be made on the explosives.

4 section

Permit free storage

Storage of small quantities

Section 23 (1) up to a maximum limit of 10 kilograms shooting or explosives (small quantities) outside of approved warehouses in a suitable area and versperrtem container must be stored.

(2) a suitable room exists if



1. This is not the permanent stay of people around a storage room or basement, 2. it is not generally accessible part of a house or no attic, 3. it is no fire hazard rooms, boiler rooms or fuel storage areas and 4 he is dry and Frost as well as the room temperature does not exceed 50 degrees Celsius.

(3) Furthermore is on the suitability in accordance with paragraph 2 required that appropriate deletion AIDS available are as well as the necessary precautions are taken to prevent unauthorized access. Packaging units broken on are measures to ensure that the use of is not impaired.

(4) in the storage room, smoking as well as any dealing with burning or glowing objects with fire, with an open light or spark-pulling tools and the use of naked flames of any kind are prohibited. A corresponding billboard is to attach easily visible at the entrance of the area.

(5) igniters may be stored only in the manufacturer's original packaging.

(6) on the occasion of shooting competitions or similar events do not visibly store Nitrocet in an amount of up to ten kilograms in a closed vehicle, in a closed container from the outside. This type of storage is permitted only for the time strictly required.

5. section

Final and transitional provisions

Entry into force

§ 24. This Regulation shall enter into force January 1, 2011.

Transitional provisions

Existing section 25 (1) explosives warehouse, that any approval after the shooting and explosives law, BGBl. No. 196/1935, in connection with the shooting and explosives monopoly regulation, Federal Law Gazette No. 204/1935, needed, are to adapt to the provisions of article 23 of this regulation until 1 July 2011.

(2) on the day before the entry into force of this regulation, pending for approval of a bearing are after the shooting and explosives monopoly regulation, Federal Law Gazette to lead No. 204/1935, to end.

Linguistic equal treatment

section 26. As far as this regulation to natural persons are related names only in the male form, these relate to women and men in the same way. In applying the term to certain natural persons, the respective gender-specific form is to use.

Fekter

 

Appendix 1 to § 4 paragraph 2

Storage class 1.1

Shooting and explosives, which have a mass explosion hazard. (A mass explosion is an explosion which affects virtually instantaneously all quantities in stock.)

Stock class 1.2

Shooting and explosives, which have the risk of formation of splinters, explosives and pieces of litter, but are not a mass explosion hazard.

Stock class 1.3

Shooting and explosives, which have a fire hazard and either by pressure or a low risk of splinters, explosives and pieces of litter or both have a low risk, but are not a mass explosion hazard

(a) whose combustion produces considerable radiant heat or

(b) one at a time to burn, that result in a low air pressure effect or splitter - and blast - litter piece effect or both effects.

Stock class 1.4

Shooting and explosives which pose only a low risk of explosion in the event of ignition or ignition. The effects are essentially limited to the packaging. Acting outside fire may result in almost all of the contents of the packaging not virtually instantaneous explosion.

Stock class 1.5

Very insensitive explosive mass shooting and explosives, which are so insensitive that the probability of initiation or of transition of fire to a detonation under normal conditions is very low.

Stock class 1.6

Extremely insensitive shooting and explosives that are not bulk explosive and contain only insensitive detonating substances and have a negligible probability of accidental initiation or propagation.

Annex 2 to § 11 par. 4 and 13

Safety distances

Safety distances to



A: are roads and other routes (such as slopes, water routes, tracks, Seilbahntrassen), B: buildings, which inhabits or in which people regularly reside, as well as facilities that serve the general public (such as houses, office buildings, power lines) and C: buildings and facilities with high density (such as hospitals, homes, schools, stadiums, train stations, airports, shopping, leisure and event centers): to be complied for free and flat terrain safety distances of bearings , in which explosives of storage class 1.1, 1.2, 1.3, 1.5 and 1.6 in accordance with Appendix 1, are calculated from the specified formulas in the table.



(L) capacity in kg





Minimum distance (S) in metres (rounded) to







 







A









B









C









 





S 7 L = 1/3





S = 18 L 1/3





S 35 L = 1/3







100





30





85





160







200





40





105





205







500





55





145





280







1000





70





180





350







2000





90





225





440







5000





120





305





600







10,000





150





390





755





The safety distance of fire protection zones is for shooting and explosives of the stock class 1.4 in accordance with Appendix 1.