Electricity (Safety) Regulations 2010

(SR 2010/36)
Anand Satyanand, Governor-General

Order in Council

At Wellington this 1st day of March 2010
Present:His Excellency the Governor-General in Council

Note

Changes authorised by subpart 2 of Part 2 of the Legislation Act 2012 have been made in this official reprint.
Note 4 at the end of this reprint provides a list of the amendments incorporated.
These regulations are administered by the Ministry of Business, Innovation, and Employment.

Pursuant to sections 169, 169A, and 169B of the Electricity Act 1992, His Excellency the Governor-General, acting on the advice and with the consent of the Executive Council, makes the following regulations.

Contents

1
Title

2
Commencement

Part 1 Preliminary provisions

Application

3
Application: things these regulations do not apply to

Definitions

4
Interpretation

5
Meanings of electrically safe and electrically unsafe

6
Prescribed electrical work

6A
Meaning of low-risk, high-risk, and general prescribed electrical work

7
Connectable installations

8
IEC shock current standards

Ambient temperature

9
New Zealand ambient temperature

Penalty levels

10
Level 1 and level 2 penalties defined

11
Strict liability offences

12
Infringement offences

Part 2 General safety requirements

Requirements for electrical safety

13
Doing work on works, installations, fittings, and appliances

14
Designing works, installations, fittings, and appliances

14A
Manufacturer’s instructions

15
Using works, installations, fittings, appliances, and associated equipment

15A
Fittings and appliances at rented residential premises

16
Minimising risk of contact with live conductive parts

17
Maintaining safe distances

18
Notices where high voltages used, generated, or transmitted

18A
Signs when carrying out prescribed electrical work

19
Notifying WorkSafe of danger

Things deemed electrically safe or electrically unsafe

20
Electrically unsafe works and installations

21

Electrically safe single-wire earth return systems [Revoked]

22
Electrically unsafe low voltage fittings

23
Electrically unsafe appliances

24
Electrically unsafe RCDs

24A
Electrically unsafe safety-critical equipment

24B
Electrically unsafe electrical work in relation to certain mining electrical equipment

25
Specific installations, fittings, and appliances deemed to be electrically safe

26
When fittings and appliances in use deemed to be electrically safe

Part 3 Systems of supply

27
Systems in general

28
Voltage supply to installations

29
Frequency of electricity supplied

30
Requirements relating to safety of electricity supplied

31
Requirements relating to quality of supply

32
Protection against fault currents

33
Requirements relating to construction of, or work in vicinity of, telecommunications equipment

33A
Limits of operation of SWER systems in relation to telecommunications

Part 4 Safety of works

Rules applying in relation to all works

34
Protective fittings for works

35
Interference with, or movement of, works

36
Generating facilities and substations

37
Works constructed as low voltage installations

37A
Trolley bus supply systems must be treated as works

38
Testing works before connecting to supply

Works not covered by audited safety management systems

39
Regulations 40 to 46 do not apply to works covered by audited safety management systems

40
Safety checks of works

41
Structural loading on works

42
Requirements for earthing systems in works

43
Isolation fittings for works

44
High voltage conductors of overhead electric lines

45
Permanent notices on works

46
Keeping records and plans

Works covered by audited safety management systems

47
Overview

48
What safety management systems must do

49
Substantive requirements of safety management systems

50
Documentation of safety management systems

51
Audit of safety management systems

52
Audit certificate for safety management systems

53
Statutory declaration by safety management system operator

54
Cancellation of audit certificate

55
Certification and declaration deemed to be compliance with section 61A of Act

56
Offences by accredited auditors

Part 5 Safety of installations

Domestic wiring exemption

57
Exemption for domestic electrical wiring work

Certified designs for installations

58
Certified designs

Rules for low and extra-low voltage installations

59
Low and extra-low voltage installations to comply with AS/NZS 3000

60
Certain installations must comply with Part 2 of AS/NZS 3000

61
Specific rules for installations under Part 1 of AS/NZS 3000

61AA
Installations in excavated areas must comply with AS/NZS 3007

61A
Rule about 3-pin flat-pin socket-outlets in low voltage installations

Rules for high voltage installations

62
High voltage installations treated as if works

Testing prescribed electrical work

63
Testing prescribed electrical work on low and extra-low voltage installations

64
Testing prescribed electrical work on high voltage installations

Certifying prescribed electrical work

65
Requirement for certificate of compliance

66
Content of certificate of compliance

67
Information recorded on certificate of compliance

68
Who may issue certificate of compliance

69
Offences relating to certificates of compliance

Inspecting prescribed electrical work

70
High-risk prescribed electrical work to be inspected

71
Who may carry out inspection

72
Record of inspection

72A
What happens to records of inspection

73
Offences relating to inspection

Connection to power supply after prescribed electrical work

73A
Before connecting installations to power supply

73B
Offence relating to connection

Reconnection when no general or high-risk prescribed electrical work done

74
Reconnecting or restoring power supply to certain low voltage installations

Certifying installations

74A
Electrical safety certification

74B
Exception for operators with maintenance management systems

74C
Time when electrical safety certificate to be issued

74D
Offences relating to electrical safety certificates

Record-keeping

74E
What happens to certificates of compliance

74F
Details of high-risk work to be lodged on database

74G
What happens to electrical safety certificates

74H
Offences relating to record-keeping

Miscellaneous

74I
Location of installations

Periodic assessments

75
Periodic assessments of certain installations

Connectable installations

76
No supply without warrant of electrical fitness

77
Restrictions on use of connectable installations

78
Issue of warrants of electrical fitness for connectable installations

Part 5A Mining electrical equipment and conductors

78A
Interpretation

Alluvial mining operations and quarrying operations

78B
Obligations in relation to alluvial mining operations and quarrying operations

78C
Standards for equipment at alluvial mining operations and quarrying operations

78D
Periodic assessment of equipment and conductors at alluvial mining operations and quarrying operations

Opencast mining operations

78E
Obligations in relation to opencast mining operations

78F
Standards for equipment at opencast mining operations

78G
Safety assessment programmes at opencast mining operations

Tunnelling operations and underground mining operations

78H
Obligations in relation to tunnelling operations

78I
Obligations in relation to underground mining operations

78J
Certified designs for mining electrical equipment and conductors at tunnelling operations and underground mining operations

78K
Safety assessment programmes at tunnelling operations and underground mining operations

78L
General offences

Tourist mining operations

78M
Obligations in relation to tourist mining operations

Part 6 Safety of fittings and appliances

79
Maintenance of domestic appliances

80
New and used fittings and appliances to be electrically safe

81
Evidence of compliance with standards

82
Offences relating to false or incorrect marking

83
Supplier declaration of conformity required before sale of declared medium risk articles

83A
Deemed approval by WorkSafe for sale of medium risk EESS products

84
Declared high risk articles not to be sold unless approved

85
Approval by WorkSafe for sale of declared high risk articles

86
Deemed approval by WorkSafe for sale of declared high risk articles

86A
Deemed approval by WorkSafe for sale of high risk EESS products

87
Prohibitions relating to fittings and appliances

88
Supply of electricity to hand-held appliances

89
Use of hand-held appliances in certain high-risk situations

89A
Use of hand-held appliances in cramped spaces

Testing appliances

90
Testing appliances after certain work done on them

Periodic assessment of electrical medical devices

91
Periodic assessment of electrical medical devices

Part 7 Registration, employer licences, and Board provisions

What supervised persons and trainees may do

92
Limits of work that supervised persons may do

93
Limits of work that trainees may do

Employer licences

94
Requirements for system of operation of holders of employer licences

95
Certification of system of operation

96
Approved persons

Board provisions

97
Search criteria for register of electrical workers

98
Form of complaints

99
Fees payable to Board

Part 8 Working practices

100
Safety responsibilities of person who carries out work

101
Responsibility of employers for safety of employees

102
Work on live high voltage overhead electric lines

103
Work on live conductors of low voltage overhead electric lines in installations

103A
Work on or near bare live conductors in alluvial mining operations, mining operations, and quarrying operations

104
Work on isolated high voltage fittings

105
Work stringing additional conductors between poles or other supports

106
Notices when working on works and installations

107
Offences relating to Part 8

Part 9 Miscellaneous

WorkSafe’s powers and obligations

108
WorkSafe’s power to prescribe forms, etc

109
WorkSafe’s power to exempt from requirements

110
Issuing urgent instructions, orders, or requirements

Miscellaneous

111
Gazette notices to be published on Internet site

111A
Consolidation of certificates

111B
Authentication mark

111C
Offences relating to application of authentication mark

112
Details that must be provided in reports of accidents

Recording certificate details

112A
Database for recording certificate details on Internet site

112B
Access to database

Transitional provisions

113
Existing and in-process works, installations, fittings, and appliances

114
Declared articles under previous regulations

115
Specified fittings and appliances under previous regulations

116
Secretary’s exemptions

117
Warrants of electrical fitness

118
Certificates of compliance

Transitional provision relating to 2011 amendments

118A
Transitional provision relating to Electricity (Safety) Amendment Regulations 2011

Transitional provision relating to 2012 amendments

118B
Transitional provision relating to Electricity (Safety) Amendment Regulations 2012

Transitional and savings provisions relating to 2013 amendments

118C
Savings provision for existing mining electrical equipment in relation to Electricity (Safety) Amendment Regulations 2013

118D
Transitional provision relating to Electricity (Safety) Amendment Regulations 2013

Arbitrators

119
Arbitrators

Revocation and amendments

120
Revocation of Electricity Regulations 1997

121
Amendment to Electricity (Hazards from Trees) Regulations 2003

122
Amendments to Electricity (China Free Trade Agreement) Regulations 2008

Schedule 1 Prescribed electrical work

Schedule 2 Electrical codes of practice and official standards cited in these regulations

Schedule 3 Infringement notice and reminder notice

Schedule 4 Standards applicable to fittings and appliances

Schedule 5 Prescribed fees payable to WorkSafe

Schedule 6 Prescribed fees payable to Board

Schedule 7 Authentication mark

Schedule 8 Rules for mining electrical equipment and conductors

Gazette Information

Electricity (Safety) Amendment Regulations 2012

Reprint notes

Regulations

1 Title


These regulations are the Electricity (Safety) Regulations 2010.

2 Commencement


These regulations come into force on 1 April 2010.

Part 1 Preliminary provisions

Application

3 Application: things these regulations do not apply to



Nothing in these regulations applies to any of the following, or to work done on any of the following:

(a)

fittings and electrical appliances manufactured solely for export or imported solely for re-export:

(b)

road vehicles other than road vehicles used in a mining operation:

(ba)

the fittings of such road vehicles other than fittings that operate at standard low voltage:

(c)

trains, locomotives, trams, and trolley buses, and the fittings of trains, locomotives, trams, and trolley buses:

(d)

ships other than—

(i)

pleasure vessels containing connectable installations; and

(ii)

barges and dredges used in connection with a mining operation:

(da)

the fittings of such ships:

(e)

aircraft (as defined in section 2(1) of the Civil Aviation Act 1990) and the fittings of aircraft:

(f)

restricted weapons (as defined in section 2 of the Arms Act 1983).

Compare: SR 1997/60 r 3

Regulation 3(b): replaced, on 31 December 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 3(ba): inserted, on 31 December 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 3(d): replaced, on 31 December 2013, by regulation 4(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 3(da): inserted, on 31 December 2013, by regulation 4(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Definitions

4 Interpretation

(1)

In these regulations, unless the context otherwise requires,—
AC means alternating current

accredited auditor means any of the following bodies:

(a)

a body accredited by either of the following to assess an organisation’s compliance with these regulations and safety management systems generally:

(i)

the Joint Accreditation System of Australia and New Zealand:

(ii)

a signatory to the International Accreditation Forum multilateral recognition arrangement for management systems:

(b)

a body approved, by or under an international agreement between New Zealand and another country that does not have a national accreditation body that is a signatory to the International Accreditation Forum multilateral recognition arrangement for management systems, to assess an organisation’s compliance with these regulations and safety management systems generally

Act means the Electricity Act 1992
alluvial mine operator has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
alluvial mining operation has the meaning given to it in section 19L of the Health and Safety in Employment Act 1992
appliance means an electrical appliance as defined in section 2(1) of the Act
audited safety management system means a safety management system for which an audit certificate has been issued under regulation 52 and not cancelled under regulation 54

caravan park means an area of land—

(a)

that is used, or intended to be used, to site 2 or more vehicles or relocatable buildings that contain connectable installations; and

(b)

on which are installed fittings to supply electricity to those installations

CCC marks means marks required by the Conformity Cooperation Agreement to be put on fittings and appliances
certificate of compliance means a certificate, issued under regulation 65, regarding the lawfulness and safety of prescribed electrical work done on an installation or part installation
certified design means a design for an installation that has been certified in accordance with regulation 58
conductor means a wire, cable, bar, or tube, used or placed in position for the conveyance of electricity; but does not include the wire of an electric fence

Conformity Cooperation Agreement means the Agreement between the Government of New Zealand and the Government of the People’s Republic of China on Cooperation in the Field of Conformity Assessment in Relation to Electrical and Electronic Equipment and Components (which is Annex 14 of the Free Trade Agreement between the Government of New Zealand and the Government of the People’s Republic of China done at Beijing on 7 April 2008), and includes—

(a)

any amendments made to, and in accordance with, the Agreement; and

(b)

any rules or standards that are applied by or to the Agreement, in accordance with the Agreement

dangers includes dangers such as, or associated with, electric shock, fire, burns, mechanical injury, toxicity, and radiation
DC means direct current
earthed means effectively connected to the general mass of earth
EESS means the harmonised Australian/New Zealand Electrical Equipment Safety System

EESS law means,—

(a)

in relation to Queensland, Part 2A of the Electrical Safety Act 2002 (Qld):

(b)

in relation to Tasmania, the Electricity Industry Safety and Administration Act 1997 (Tas):

(c)

in relation to any other Australian state, any legislation that gives effect to the EESS

electric line means all conductors (including fittings supporting, or connected to, those conductors), whether above or below ground, that are used or intended to be used in, or in connection with, the supply of electricity from the outgoing terminals of a generating station, a building, enclosure, or other structure to—

(a)

the incoming terminals of another building, enclosure, or other structure; or

(b)

an appliance, in any case where the appliance is supplied with electricity other than from a terminal in a building, enclosure, or other structure

electrical medical device means a medical device (as defined in section 3A of the Medicines Act 1981), other than an implant, that is supplied with electricity
electrical safety certificate means a certificate, issued under regulation 74A, regarding the electrical safety of an installation or part installation that is connected to a power supply
electrically safe and electrically unsafe have the meanings set out in regulation 5
ERZ0 has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
ERZ1 has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
extra-low voltage means any voltage normally not exceeding 50 volts AC or 120 volts ripple-free DC
general body concentration, in relation to methane, means the concentration of methane in the relevant area expressed as a percentage of volume
general prescribed electrical work has the meaning set out in regulation 6A(3)
generating station means those parts of works that are used principally for the generation of electricity
hazardous area means an area in which an explosive atmosphere is present, in quantities that require special precautions for the construction, installation, and use of electrical equipment
high-risk prescribed electrical work has the meaning set out in regulation 6A(2)
high voltage means voltage exceeding 1 000 volts AC or 1 500 volts ripple-free DC
IEC shock current standard means the shock current standards set out in regulation 8
install, in relation to an installation, includes to construct, alter, relocate, or add to the whole or any part of the installation
installation means an electrical installation as defined in section 2(1) of the Act, and part installation means any part of an installation
insulated, in relation to conductors and other fittings, means that the conductors or fittings are covered with insulation in such a manner that a person may safely handle them when they are live

integral plug device means—

(a)

an appliance that incorporates pins that can be inserted into a socket-outlet for the purpose of connecting that appliance to a supply of electricity; and

(b)

includes a power pack

level 1 penalty has the meaning set out in regulation 10(1)
level 2 penalty has the meaning set out in regulation 10(2)
live means charged with electricity so that a difference in voltage exists to earth or between conductors

live conductor means a conductor that is—

(a)

charged with electricity so that a difference in voltage exists to earth or between conductors; or

(b)

a neutral conductor

location, for the purpose of identifying on a certified design, certificate of compliance, or electrical safety certificate the location of an installation or part installation, has the meaning set out in regulation 74I
low-risk prescribed electrical work has the meaning set out in regulation 6A(1)

low voltage,—

(a)

in relation to mining electrical equipment, means any voltage exceeding 50 volts AC or 120 volts ripple-free DC but not exceeding 1 200 volts AC or 1 500 volts ripple-free DC; and

(b)

in all other cases, means any voltage exceeding 50 volts AC or 120 volts ripple-free DC but not exceeding 1 000 volts AC or 1 500 volts ripple-free DC

low voltage works means works that are supplied or operate, or are intended to operate, at low voltage

main earthing system means an earthing system of an installation that—

(a)

operates at standard low voltage; and

(b)

comprises an earth electrode, an earthing conductor that is connected between that earth electrode and a MEN switchboard, and a removable link between the neutral and earth conductors within that MEN switchboard

main switchboard, in relation to an installation, means the switchboard that is used by the consumer to provide the greatest degree of control of the supply of electricity to that installation
mains means those fittings forming part of an installation that are used for the supply of electricity to the MEN switchboard of the installation that is closest to the point of supply

mains parallel generation system means fittings that—

(a)

are used or intended for use by any person in, or in connection with, the generation of electricity for that person’s use; and

(b)

are capable of supplying electricity to fittings that, at the same time, are supplied with electricity from other systems of electrical supply

mains work—

(a)

means any of the following:

(i)

work on mains (including connecting the conductors of mains at a MEN switchboard):

(ii)

work on main earthing systems (including connecting the conductors of main earthing systems at a MEN switchboard):

(iii)

work on the connection between earth and neutral made by the removable link within the MEN switchboard closest to the point of supply; but

(b)

does not include—

(i)

work on fittings that are used or intended for use by any person in, or in connection with, the generation of electricity for that person’s use and not for supply to any other person; or

(ii)

work that is limited to removing or replacing the removable link within a MEN switchboard for the purposes of testing; or

(iii)

the installation of a revenue meter, but only if the work cannot affect the integrity of the neutral or result in the transposition of the neutral and any active conductor

maintenance includes repair
medical location means a patient treatment area or other place labelled or specifically set aside to be used to undertake patient treatment
MEN switchboard means a switchboard that has a connection to an earth electrode via an earthing conductor, and a connection between earth and neutral made by a removable link, for the purposes of creating a MEN system

MEN system means the Multiple Earthed Neutral system, which is a New Zealand variant of the internationally defined TNC system of supply of electricity in which the neutral is connected to earth—

(a)

at the source of supply (being either the generating station or the substation from which electricity, at the voltage at which it is delivered to the consumer, is derived); and

(b)

at points on the supply system; and

(c)

at every installation connected to that system

mine operator has the meaning given to it in section 19L of the Health and Safety in Employment Act 1992

mining electrical equipment means fittings and appliances (including cables) used or installed at an alluvial mining operation, a mining operation, or a quarrying operation in connection with—

(a)

any activity described in section 19M(a) or (b), 19N(1)(a), or 19O(a) of the Health and Safety in Employment Act 1992:

(b)

the extraction of gold or ironsand

mining operation has the meaning given to it in section 19M of the Health and Safety in Employment Act 1992
mobile medical facility means a vehicle or relocatable building containing 1 or more connectable installations that are used for patient treatment

mobile mining electrical equipment—

(a)

means mining electrical equipment that is designed to be moved while it is connected to or powered by an electricity supply (whether or not the equipment needs or uses electricity in order to move); and

(b)

may include hand-held equipment

opencast mining operation means an opencast coal mining operation or an opencast metalliferous mining operation as those terms are defined in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
patient treatment means the diagnosis, treatment, prevention, monitoring, or alleviation of a medical or dental condition, or of a disability, in humans
personal protective equipment means items of apparel and equipment worn by a person that are intended either to prevent the occurrence of harm to the person or to minimise any dangers that may occur from hazards that are present in the workplace or hazards that may arise in the course of work
plug means any device, other than a bolted coupler or a restrained coupler, that is or can be plugged directly into a socket-outlet for the purpose of connecting an appliance or a fitting to a supply of electricity
prescribed electrical work has the meaning given in regulation 6 (which refers to the detailed description in Schedule 1)
quarry operator has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
quarrying operation has the meaning given to it in section 19N of the Health and Safety in Employment Act 1992
RCD, or residual current device, means a device for isolating supply to protected circuits, socket-outlets, or appliances in the event of a current flow to earth that exceeds a predetermined level

reduced low-voltage system means—

(a)

a single-phase system in which—

(i)

the nominal line-to-line voltage does not exceed 110 volts AC; and

(ii)

the nominal line-to-earth voltage does not exceed 55 volts AC; and

(iii)

all exposed conductive parts are connected to the protective conductor; or

(b)

a three-phase system in which—

(i)

the nominal line-to-line voltage does not exceed 110 volts AC; and

(ii)

the nominal line-to-earth voltage does not exceed 63.5 volts AC; and

(iii)

all exposed conductive parts are connected to the protective conductor

registered EESS product means a fitting or an appliance that is—

(a)

classified as level 2 or 3 equipment under any EESS law; and

(b)

registered in respect of the relevant registered EESS supplier on a database established under any EESS law

registered EESS supplier means a person registered under any EESS law as a responsible supplier
relocatable mining electrical equipment means mining electrical equipment that is capable of being moved, but not while it is connected to an electricity supply
revenue meter includes all associated fittings, such as load control fittings

safety-critical equipment, in relation to mining electrical equipment, means any or all of the following:

(a)

signalling and communication systems:

(b)

environmental monitoring systems:

(c)

gas monitors:

(d)

equipment designed or used for rescue and emergency purposes

safety management system means a system that is implemented by a safety management system operator for the purpose of ensuring that all practicable steps are taken to prevent an electricity supply system (as defined in section 61A(2) of the Act) or other works from presenting a significant risk of—

(a)

serious harm to any member of the public; or

(b)

significant damage to property owned by a person other than the safety management system operator

safety management system operator means—

(a)

an electricity generator or electricity distributor that is required, by section 61A(1) of the Act, to implement and maintain a safety management system; or

(b)

an owner of any other works who chooses to implement and maintain a safety management system

shock current means an electrical current that passes through the body of a person or animal, and that has characteristics that are likely to cause disorders of physiological processes of the body

standard low voltage means,—

(a)

in respect of electricity supplied by either a single-phase MEN system or a multiple-phase MEN system, a nominal voltage of 230 volts AC between phase and neutral; or

(b)

in respect of electricity supplied by any other system, a nominal voltage,—

(i)

in relation to single-phase supplies, of 230 volts AC between conductors; or

(ii)

in relation to 2-phase supplies, of 400 volts AC or 460 volts AC between conductors; or

(iii)

in relation to multiple-phase supplies, of 400 volts AC between conductors

substation means all or part of a building, structure, or enclosure that incorporates fittings that are used principally for the purposes of the control of the distribution of electricity
supplier declaration of conformity means a declaration, relating to a low voltage or extra-low voltage fitting or appliance, that complies with regulation 83(3)
SWER system means a single wire earth return system
telecommunications network voltage, in relation to telecommunications lines or equipment, means a voltage that is not greater than the limits specified in AS/NZS 60950
tourist mining operation has the meaning given to it in section 19L of the Health and Safety in Employment Act 1992
tunnelling operation has the meaning given to it in section 19O of the Health and Safety in Employment Act 1992
underground mining operation has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013.

(2)
A term used in connection with a particular standard has the meaning used in that standard, unless the term is defined in the Act or these regulations, in which case it has that meaning.

(3)

A term used in these regulations and not defined in the Act or these regulations, and to which subclause (2) does not apply, has the meaning given (if any),—

(a)

in the case of installations, in AS/NZS 3000; and

(b)

in all other cases, in IEC 60050.

(4)
In these regulations, electrical codes of practice and official standards (such as AS/NZS and IEC) are referred to by the abbreviations listed in Schedule 2.

Compare: SR 1997/60 r 2

Regulation 4(1) accredited auditor: substituted, on 10 November 2011, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 4(1) alluvial mine operator: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) alluvial mining operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) certificate of compliance: replaced, on 1 July 2013, by regulation 4(3) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) certified design: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) declaration of conformity: revoked, on 1 July 2013, by regulation 4(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) EESS: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) EESS law: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) electrical medical device: amended, on 1 July 2014, by section 48 of the Medicines Amendment Act 2013 (2013 No 141).
Regulation 4(1) electrical safety certificate: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) ERZ0: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) ERZ1: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) general body concentration: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) general prescribed electrical work: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) grade A offence: revoked, on 1 July 2013, by regulation 4(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) grade B offence: revoked, on 1 July 2013, by regulation 4(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) high-risk prescribed electrical work: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) install: amended, on 1 July 2013, by regulation 4(4) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) installation: amended, on 1 July 2013, by regulation 4(5) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) integral plug device: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) level 1 penalty: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) level 2 penalty: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) location: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) low-risk prescribed electrical work: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) low voltage: replaced, on 31 December 2013, by regulation 5(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) low voltage works: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) main earthing system paragraph (b): replaced, on 1 July 2013, by regulation 4(6) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) mains work: substituted, on 10 November 2011, by regulation 4(4) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 4(1) mains work paragraph (b)(ii): amended, on 1 July 2013, by regulation 4(7) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) mains work paragraph (b)(iii): inserted, on 1 July 2013, by regulation 4(8) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) maintenance: inserted, on 1 July 2013, by regulation 4(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 4(1) mine operator: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) mining electrical equipment: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) mining operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) mobile mining electrical equipment: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) opencast mining operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) plug: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) quarry operator: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) quarrying operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) reduced low-voltage system: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) registered EESS product: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) registered EESS supplier: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) relocatable mining electrical equipment: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) safety-critical equipment: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) supplier declaration of conformity: amended, on 10 November 2011, by regulation 4(5) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 4(1) SWER system: inserted, on 10 November 2011, by regulation 4(6) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 4(1) tourist mining operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) tunnelling operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 4(1) underground mining operation: inserted, on 31 December 2013, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

5 Meanings of electrically safe and electrically unsafe



In these regulations, unless the context otherwise requires—
electrically safe means, in relation to works, installations, fittings, appliances, and associated equipment, that there is no significant risk that a person or property will be injured or damaged by dangers arising, directly or indirectly, from the use of, or passage of electricity through, the works, installations, fittings, appliances, or associated equipment
electrically unsafe means, in relation to works, installations, fittings, appliances, and associated equipment, that there is a significant risk that a person may suffer serious harm, or that property may suffer significant damage, as a result of dangers arising, directly or indirectly, from the use of, or passage of electricity through, the works, installations, fittings, appliances, or associated equipment.

Compare: SR 1997/60 r 69(2)

Regulation 5 electrically safe: amended, on 10 November 2011, by regulation 5(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 5 electrically unsafe: amended, on 10 November 2011, by regulation 5(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

6 Prescribed electrical work


For the purpose of the definition of prescribed electrical work in section 2(1) of the Act, prescribed electrical work is electrical work of a type described in clause 1 of Schedule 1 that is not work of a type described in clause 2 of that schedule.

6A Meaning of low-risk, high-risk, and general prescribed electrical work

(1)

In these regulations, low-risk prescribed electrical work—

(a)

means prescribed electrical work that comprises the maintenance or replacement of a fitting in an existing installation; and

(b)

includes relocation or extension of a conductor to facilitate replacement of a fitting; but

(c)

excludes maintenance that involves the adjustment of protection or gas monitor settings of mining electrical equipment.

(2)

In these regulations, high-risk prescribed electrical work means the prescribed electrical work (not being low-risk prescribed electrical work) that—

(a)

comprises or includes the installation, or adjustment of the settings, of any of the following:

(i)

an extra-low or low voltage installation that does not, or will not, comply with Part 2 of AS/NZS 3000:

(ii)

an installation that operates, or will operate, at high voltage (other than high voltage discharge lighting, high voltage mobile mining electrical equipment, and high voltage relocatable mining electrical equipment):

(iii)

a mains parallel generation system in an installation:

(iv)

a photovoltaic system in an installation:

(v)

an installation that is, or will be, located in a hazardous area other than an ERZ0 or ERZ1:

(vi)

an installation that is, or is intended, for use with electrical medical devices:

(vii)

any fittings (including any neutral earth resistors and earth leakage circuit breakers) that—

(A)

control earth potential rise; and

(B)

are not part of any relocatable mining electrical equipment:

(viii)

any fittings or appliances that are not part of any relocatable mining electrical equipment and are used or installed, or to be used or installed, in an ERZ0 or ERZ1:

(b)

is mains work on an installation:

(c)

is work on an installation’s animal stunning appliances or meat conditioning appliances:

(d)

is work on low voltage AC railway signalling equipment except where the equipment has been tested in accordance with ECP 60 and the work has been carried out in accordance with AS/NZS 3000:

(e)

comprises or includes the construction of any relocatable mining electrical equipment, including fittings that control earth potential rise (such as neutral earth resistors, neutral earth reactors, and earth leakage circuit breakers):

(f)

comprises the connection of a supply of electricity from an above-ground supply to mining electrical equipment, or conductors supplying mining electrical equipment, that are located in the underground parts of an underground mining operation:

(g)

includes the adjustment of the settings of—

(i)

any isolation fittings of mining electrical equipment:

(ii)

gas monitors used in a mining operation.

(3)
In these regulations, general prescribed electrical work means any prescribed electrical work on an installation, or on mining electrical equipment, that is not low-risk prescribed electrical work or high-risk prescribed electrical work.

(4)
To avoid doubt, work done on an installation by a person acting under the exemption in section 79 of the Act (an exemption for domestic electrical wiring work) is not categorised as low-risk, high-risk, or general prescribed electrical work, unless, in order to comply with regulation 57, the work is required to be certified, in which case the work is to be categorised in accordance with subclauses (1) to (3) of this regulation.

Regulation 6A: replaced, on 31 December 2013, by regulation 6 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

7 Connectable installations


For the purpose of the definition of connectable installation in section 2(1) of the Act in relation to a vehicle, a relocatable building, or a pleasure vessel, a connectable installation is one that is designed or intended for, or is capable of, connection to an external power supply that operates at a nominal voltage between 90 and 250 volts AC at standard low voltage.

8 IEC shock current standards

(1)
Works not covered by audited safety management systems are deemed to be electrically unsafe if the magnitude and duration of electric shock currents resulting from the step, touch, and transferred voltages created by an earth fault exceed curve c2 of Fig 20 of IEC/TS 60479-1.

(2)

A low voltage installation and any fittings and appliances supplied at low voltage are deemed to be electrically unsafe if the magnitude and duration of electric shock currents resulting from direct or indirect contact with the live parts of the installation, fitting, or appliance exceed—

(a)

curve b of Fig 20 of IEC/TS 60479-1; or

(b)

curve b of Fig 22 of IEC/TS 60479-1.

(3)
A high voltage installation, and any fittings and appliances supplied at high voltage, that are not provided with protection from supplying works are deemed to be electrically unsafe if the magnitude and duration of electric shock currents resulting from step, touch, and transferred voltages created by an earth fault exceed curve c1 of Fig 20 of IEC/TS 60479-1.

(4)
A high voltage installation and any fittings and appliances supplied by that installation that are provided with protection from supplying works are deemed to be electrically unsafe if the magnitude and duration of electric shock currents resulting from step, touch, and transferred voltages created by an earth fault exceed curve c2 of Fig 20 of IEC/TS 60479-1.

Regulation 8: substituted, on 10 November 2011, by regulation 6 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 8(2): amended, on 31 December 2013, by regulation 7(1)(a) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 8(2): amended, on 31 December 2013, by regulation 7(1)(b) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 8(3): amended, on 31 December 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 8(4): amended, on 31 December 2013, by regulation 7(3) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Ambient temperature

9 New Zealand ambient temperature



In New Zealand, the ambient temperature is deemed to be—

(a)

30° Celsius for the purpose of designing, constructing, testing, and inspecting works and installations; and

(b)

25° Celsius for the purpose of manufacturing and testing fittings and appliances for compliance with AS/NZS 3820.

Penalty levels

Heading: replaced, on 1 July 2013, by regulation 6 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

10 Level 1 and level 2 penalties defined

(1)

A level 1 penalty is,—

(a)

in the case of an individual, a fine not exceeding $2,000; and

(b)

in any other case, a fine not exceeding $10,000.

(2)

A level 2 penalty is,—

(a)

in the case of an individual, a fine not exceeding $10,000; and

(b)

in any other case, a fine not exceeding $50,000.

Regulation 10: replaced, on 1 July 2013, by regulation 6 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

11 Strict liability offences

(1)
Subclauses (2) and (3) apply to every offence in these regulations except those that specifically refer to a defendant’s state of knowledge or intention regarding the facts constituting the offence.

(2)
In a prosecution for an offence to which this subclause applies, it is not necessary for the prosecution to prove that the defendant knew or intended the facts that constitute the offence.

(3)

It is a defence to a prosecution for an offence to which this subclause applies if the defendant proves—

(a)

that—

(i)

the action or event to which the prosecution relates was necessary for the purpose of avoiding serious harm to any person, or preventing significant damage to property; and

(ii)

the defendant’s conduct was reasonable in the circumstances; and

(iii)

the effects of the action or event were adequately mitigated or remedied by the defendant after it occurred; or

(b)

that the action or event to which the prosecution relates was due to an event beyond the control of the defendant (such as natural disaster, mechanical failure, or sabotage) and—

(i)

the action or event could not reasonably have been foreseen or been provided against by the defendant; and

(ii)

the effects of the action or event were adequately mitigated or remedied.

Compare: 2004 No 72 s 388

12 Infringement offences

(1)

Offences against the following are infringement offences:

(a)

any regulation in Parts 2 to 6 of these regulations:

(b)

section 20(d) of the Act (failure to report accidents, etc):

(c)

section 162 of the Act (doing prescribed electrical work in breach of section 74 of the Act):

(d)

section 163 of the Act (employing someone to do prescribed electrical work in breach of section 74 of the Act).

(2)

The infringement fee for an offence punishable by a level 2 penalty is,—

(a)

for an individual, $1,000; and

(b)

for a body corporate, $3,000.

(3)

The infringement fee for an offence punishable by a level 1 penalty is,—

(a)

for an individual, $500; and

(b)

for a body corporate, $1,000.

(4)
The infringement fee for an offence against any of sections 20(d), 162, and 163 of the Act is the infringement fee set for an offence punishable by a level 2 penalty.

(5)
The prescribed form for infringement notices is form 1 as set out in Schedule 3.

(6)
Reminder notices for infringement offences must be as set out in form 2 of Schedule 3.

Regulation 12(2): amended, on 1 July 2013, by regulation 8(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 12(3): amended, on 1 July 2013, by regulation 8(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 12(4): amended, on 1 July 2013, by regulation 8(3) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Part 2 General safety requirements

Requirements for electrical safety

13 Doing work on works, installations, fittings, and appliances

(1)

A person who does work on any works or installation, or on any part of any works or installation, must ensure—

(a)

that the resulting works or installation, or part of the works or installation, is electrically safe; and

(b)

if the work is on only part of any works or installation, that the work has not adversely affected the electrical safety of the rest of the works or installation.

(2)

A person who does work on any fittings or appliances must ensure that—

(a)

the resulting fittings or appliances are electrically safe; and

(b)

in the case of mining electrical equipment or conductors supplying that equipment, the resulting equipment and conductors comply with the applicable requirements of Part 5A and Schedule 8.

(3)
A person who does work on any works, installations, fittings, or appliances must, while doing the work, take all practicable steps to ensure that people and property are protected from dangers arising from the work.

(4)

In this regulation, work includes doing, or supervising the doing of, any of the following:

(a)

constructing, manufacturing, or assembling:

(b)

installing or connecting:

(c)

maintaining:

(d)

testing, certifying, or inspecting.

(5)

A person commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

does work on any works or installation and fails to comply with subclause (1); or

(b)

does work on any fittings or appliances and fails to comply with subclause (2); or

(c)

while doing work on any works, installations, fittings, or appliances, fails to take all practicable steps to ensure that people and property are protected from dangers arising from the work, where the person doing the work knows, or can reasonably be expected to know, of the dangers that may arise from the work.

Compare: SR 1997/60 r 69(1)

Regulation 13(2): replaced, on 31 December 2013, by regulation 8 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 13(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 13(5): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

14 Designing works, installations, fittings, and appliances

(1)
A person who designs, or supervises the design of, works, installations, fittings, or appliances must ensure that, if the finished design were constructed, installed, or manufactured as designed, the finished works, installations, fittings, or appliances would be electrically safe.

(2)
A person who designs, or supervises the design of, works, installations, fittings, or appliances commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (1).

Compare: SR 1997/60 r 69(1)

Regulation 14(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 14(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

14A Manufacturer’s instructions

(1)

This regulation applies if a manufacturer or importer supplies a fitting or appliance with manufacturer’s instructions that—

(a)

expressly apply in New Zealand; or

(b)

are silent as to where they apply.

(2)

The manufacturer’s instructions must be such that, if the fitting or appliance to which they apply is installed, tested, maintained, or connected in accordance with those instructions, the resulting fitting or appliance will—

(a)

comply with these regulations; and

(b)

be electrically safe.

(3)
A person who does any prescribed electrical work involving a fitting or appliance to which manufacturer’s instructions apply is entitled (if acting in good faith) to rely on the manufacturer’s instructions as complying with subclause (2).

(4)
A manufacturer or importer who supplies a fitting or appliance to which manufacturer’s instructions apply commits an offence and is liable on conviction to a level 2 penalty if the manufacturer’s instructions do not comply with subclause (2).

Regulation 14A: inserted, on 1 July 2013, by regulation 9 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 14A(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

15 Using works, installations, fittings, appliances, and associated equipment

(1)
A person who owns or operates works, installations, fittings, or appliances must not use, and must not allow any other person to use, the works, installations, fittings, or appliances if the works, installations, fittings, or appliances are electrically unsafe.

(1A)
A person must not rent, hire out, or lease out fittings or appliances to any other person if the fittings or appliances are electrically unsafe at the start of the rental, hire, or lease period.

(1B)
A person who is the direct renter, hirer, or lessee of fittings or appliances must not use, and must not allow any other person to use, the fittings or appliances if the fittings or appliances are electrically unsafe.

(2)
A person who uses, or supervises the use of, associated equipment must ensure that the associated equipment is not used in a manner that renders the associated equipment a danger to persons or property.

(3)
A person who owns, rents, hires, leases, or operates works, installations, fittings, or appliances commits an offence and is liable on conviction to a level 2 penalty if he or she uses, or allows another person to use, the works, installations, fittings, or appliances, knowing that, or being reckless as to whether, the works, installations, fittings, or appliances are electrically unsafe.

(3A)
A person who is the direct renter, hirer, or lessee of fittings or appliances commits an offence and is liable on conviction to a level 2 penalty if he or she uses, or allows another person to use, the fittings or appliances knowing that, or being reckless as to whether, the fittings or appliances are electrically unsafe.

(4)
A person who uses, or supervises the use of, associated equipment commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (2).

Compare: SR 1997/60 rr 69(1), 100(b)

Regulation 15(1A): inserted, on 1 February 2014, by clause 1(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 15(1B): inserted, on 1 February 2014, by clause 1(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 15(3): amended, on 1 February 2014, by clause 1(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 15(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 15(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 15(3A): inserted, on 1 February 2014, by clause 1(3) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 15(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 15(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

15A Fittings and appliances at rented residential premises

(1)
A landlord of residential premises must not provide any fittings or appliances under or in connection with a residential tenancy if the fittings or appliances are electrically unsafe.

(2)
A landlord of residential premises must not allow any person to use any fittings or appliances provided by the landlord under or in connection with a residential tenancy if the fittings or appliances are electrically unsafe.

(3)
A landlord of residential premises must provide the occupier with adequate instructions for the safe use of any fittings or appliances provided under or in connection with a residential tenancy.

(4)
A landlord commits an offence and is liable on conviction to a level 2 penalty if he or she provides fittings or appliances, or allows another person to use fittings or appliances that are provided, under or in connection with a residential tenancy, knowing that, or being reckless as to whether, the fittings or appliances are electrically unsafe.

(5)
In this regulation, landlord has the meaning given to it in section 2(1) of the Residential Tenancies Act 1986.

Regulation 15A: inserted, on 1 February 2014, by clause 2 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

16 Minimising risk of contact with live conductive parts

(1)

A person who has control of works, installations, fittings, appliances, or associated equipment must take all practicable steps to minimise the risk of injury to persons or damage to property from dangers arising from direct or indirect contact between—

(a)

any live exposed conductive parts of the works, installations, fittings, appliances, or associated equipment; and

(b)

any person or animal, or any thing being worn or carried by a person or animal.

(2)
A person to whom subclause (1) applies commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with that subclause.

Compare: SR 1997/60 r 94(1)

Regulation 16(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 16(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

17 Maintaining safe distances

(1)

A person who carries out any construction, building, excavation, or other work on or near an electric line must maintain safe distances—

(a)

in accordance with ECP 34; or

(b)

in relation to work on or near overhead rail, trolley bus, tramway, or road vehicle electrification systems (including the use of machinery, equipment, or plant), in accordance with—

(i)

ECP 34; or

(ii)

for railway electrification systems, IEC 62128-1, BS EN 50122-1, BS EN 50119, and sections 5 and 9 of ECP 34; or

(iii)

for tramway and trolley bus systems, IEC 60913; or

(c)

in relation to work done at alluvial mining operations, opencast mining operations, and quarrying operations, in accordance with AS/NZS 3007.

(2)

However,—

(a)

the minimum distances required by table 7 and clause 6.4 of ECP 34, to the extent that they apply to a telecommunication line near electricity conductors, do not apply if—

(i)

the telecommunication line is an all-dielectric self-supporting fibre optic cable (a fibre optic cable); and

(ii)

the fibre optic cable is designed, manufactured, and tested to IEEE 1222; and

(iii)

the fibre optic cable and the electricity conductors have shared supports or shared spans; and

(iv)

in the case of a fibre optic cable erected on poles or other supports, the design and installation of the fibre optic cable is in accordance with AS/NZS 7000; and

(b)

a person who carries out work upgrading or altering an electric line that was in existence immediately before 1 April 2010 must comply with ECP 34 only in relation to those parts of the line that are being upgraded or altered.

(3)

Each of the following persons commits an offence and is liable on conviction to a level 2 penalty if safe distances are not maintained as required by subclause (1):

(a)

a person who carries out the work described in subclause (1):

(b)

a person who controls the work described in subclause (1):

(c)

a person who owns or controls any line, works, fittings, building, structures, equipment, or machinery that is the subject of, or involved in, the work described in subclause (1).

(4)
A person commits an offence and is liable on conviction to a level 2 penalty if the person places thermal insulating material on or around fittings in an installation in such a way that the safety of the installation is compromised.

Compare: SR 1997/60 r 93

Regulation 17: substituted, on 10 November 2011, by regulation 7 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 17(1)(b): replaced, on 31 December 2013, by regulation 9 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 17(1)(c): inserted, on 31 December 2013, by regulation 9 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 17(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 17(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 17(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 17(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

18 Notices where high voltages used, generated, or transmitted

(1)

Notices providing instructions on the treatment of electric shock must be installed in a conspicuous position, and be maintained, on the following:

(a)

all premises where electricity is, or is to be, used at high voltage; and

(b)

all premises where electricity is generated, or from which it is transmitted, at high voltage.

(2)
A person who owns premises referred to in subclause (1) commits an offence and is liable on conviction to a level 1 penalty if he or she fails to ensure that the notices required by that subclause are installed and maintained as required.

Compare: SR 1997/60 r 34(3)

Regulation 18(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 18(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

18A Signs when carrying out prescribed electrical work

(1)
While a person is carrying out prescribed electrical work on an installation, the person must, if there is a reasonable risk associated with the work of injury to any person from electric shock, erect or affix the sign referred to in subclause (2) at each access point to the area in which the work is carried out.

(2)
WorkSafe must give notice in the Gazette of the sign that is required for the purposes of subclause (1).

(3)
A person who carries out prescribed electrical work on an installation commits an offence and is liable on conviction to a level 1 penalty if he or she fails to comply with subclause (1).

Regulation 18A: inserted, on 1 July 2013, by regulation 10 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 18A(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 18A(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

19 Notifying WorkSafe of danger

(1)

This regulation applies to a person while engaged in any of the following:

(a)

carrying out prescribed electrical work, including while acting under an exemption:

(b)

carrying out a periodic assessment under regulations 75, 78D, 78G, and 78K:

(c)

examining a connectable installation with a view to issuing a warrant of electrical fitness under regulation 78.

(2)

If a person to whom this regulation applies has reasonable grounds to believe that the works, installation, fitting, or appliance presents an immediate danger to life or property, the person must, as soon as practicable, advise both of the following people of the danger:

(a)

the owner or occupier of the property where the danger exists:

(b)

WorkSafe.

(2A)

The advice in subclause (2) must include—

(a)

details of the nature of the danger; and

(b)

how and why the works, installation, fitting, or appliance presents an immediate danger to life or property; and

(c)

any steps that have been taken, or that the person reasonably believes should be taken, to minimise or eliminate the danger.

(3)
A person commits an offence and is liable on conviction to a level 2 penalty if a person to whom this regulation applies has reasonable grounds to believe that any works, installation, fitting, or appliance presents an immediate danger to life or property and fails to comply with subclause (2).

Compare: SR 1997/60 r 50

Regulation 19 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 19(1)(b): amended, on 31 December 2013, by regulation 10 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 19(2)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 19(2A): inserted, on 1 February 2014, by clause 3 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 19(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 19(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Things deemed electrically safe or electrically unsafe

20 Electrically unsafe works and installations

(1)

Works and installations are deemed to be electrically unsafe if there are not measures in place that do at least 1 of the following:

(a)

prevent accidental direct or indirect contact with exposed fittings or exposed conductive parts of the works or installations:

(b)

provide for the automatic interruption of the power supply to the works or installations on the occurrence of a fault that would cause injury or damage to any person or property:

(c)

prevent an electric current passing through the body of a person on contact with any part of the works or installations, or limit that current so that the magnitude and duration of the shock current cannot exceed the IEC shock current standards.

(2)

Works and installations are also deemed to be electrically unsafe if—

(a)

the characteristics of any fittings used in the works or installations are impaired; or

(b)

conductors are inadequately identified; or

(c)

where colour is used to identify conductors in a standard low voltage domestic installation that is being installed (other than in light fittings, connections to appliances, and wiring within a fitting),—

(i)

the neutral conductor is identified by any colour except black; and

(ii)

black is used to identify a conductor other than the neutral conductor; or

(d)

connections between conductors, and between conductors and other fittings, are not secure and reliable; or

(e)

fittings are installed in such a way that any designed cooling conditions are impaired; or

(f)

fittings that cause or are subject to high temperatures or electric arcs are placed in such a position, or are unguarded, so as to create a risk of ignition of flammable or explosive materials or of injury to persons or damage to property; or

(fa)

any refrigerant used in the works or installation, or used in any fittings or appliances in the works or installation, is substituted with a refrigerant other than a refrigerant with which the works, installation, or fitting—

(i)

is designed to operate (including one of higher toxicity or flammability); or

(ii)

has been adapted to operate safely; or

(fb)

the works or installation, or any fitting or appliance in the works or installation, is retrofitted with a refrigerant other than one with which it has been designed to be retrofitted; or

(fc)

in the case of a domestic installation, any safety or security function of the installation that needs electricity to operate has no manual override in the event of an interruption in the supply of electricity; or

(g)

cables (including underground cables) are inadequately protected against the risk of damage by the nature of their covering or their method of installation; or

(h)

cables are bent beyond their design criteria; or

(i)

there is insufficient space, access, and lighting to operate, maintain, repair, test, and inspect all fittings of the works and installations (other than cables and buried parts of earthing systems) in a safe manner.

(3)
Subclause (2)(fc) does not apply if the safety or security function has a functioning backup system of electricity supply.

Compare: SR 1997/60 r 94(2)

Regulation 20(1)(b): amended, on 10 November 2011, by regulation 8 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 20(2)(fa): inserted, on 1 February 2014, by clause 4(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 20(2)(fb): inserted, on 1 February 2014, by clause 4(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 20(2)(fc): inserted, on 1 February 2014, by clause 4(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 20(3): inserted, on 1 February 2014, by clause 4(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

21 Electrically safe single-wire earth return systems

[Revoked]
Regulation 21: revoked, on 10 November 2011, by regulation 9 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

22 Electrically unsafe low voltage fittings



A low voltage fitting is deemed to be electrically unsafe if—

(a)

the unearthed conductive parts of the fitting are separated from live parts by no more than basic insulation; or

(b)

the fitting is intended to have, or is supplied as having, a safety function, but does not in fact serve that safety function.

Compare: SR 1997/60 r 76A

23 Electrically unsafe appliances

(1)

An appliance is deemed to be electrically unsafe if—

(a)

the voltage at which it operates safely is not appropriately and adequately marked on the appliance; or

(b)

it is not constructed so as to be safe under both normal and abnormal conditions; or

(c)

the accessible unearthed conductive parts of the appliance are separated from live parts by no more than basic insulation; or

(d)

the appliance is fitted with, or is an integral plug device that includes, a flat 2-pin or 3-pin plug with the dimensions specified in AS/NZS 3112 and is not designed to operate safely at standard low voltage; or

(e)

the appliance is a single phase domestic or similar appliance (other than an appliance intended for permanent connection to an installation) fitted with a plug that does not comply with whichever official standard listed in Schedule 4 applies to the appliance; or

(f)

the appliance is a single-phase integral plug device (other than an appliance intended for permanent connection to an installation) that has a plug that does not comply with whichever official standard listed in Schedule 4 applies to the device; or

(g)

the appliance is fitted with, or is an integral plug device that includes, a plug of a rating that is less than—

(i)

the rating specified on the appliance; or

(ii)

if no rating is specified on the appliance, the rating specified in whichever official standard listed in Schedule 4 applies to the appliance.

(2)
Fittings and appliances that are designed and used for patient treatment are not electrically unsafe merely because that treatment may cause injury to the patient.

(3)
Fittings and appliances that are designed and used for animal stunning, meat conditioning, or fishing are not electrically unsafe merely because they may injure animals or fish, as the case may be.

(4)
Subclause (1)(f) does not apply to a free-standing electric range that complies with whichever official standard listed in Schedule 4 applies to the appliance.

Compare: SR 1997/60 r 76A

Regulation 23(1)(d): replaced, on 1 February 2014, by clause 5(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 23(1)(e): replaced, on 1 February 2014, by clause 5(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 23(1)(f): inserted, on 1 February 2014, by clause 5(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 23(1)(g): inserted, on 1 February 2014, by clause 5(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 23(4): inserted, on 1 February 2014, by clause 5(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

24 Electrically unsafe RCDs

(1)
This regulation applies to any standard low voltage RCD that is used in a situation where it is required, by these regulations or any standard, to be used.

(2)

A portable RCD designed or used to protect against electric shock (whether or not it is an RCD referred to in subclauses (3) to (6)) is deemed to be electrically unsafe if, on failure of the supply voltage, it does not do 1 of the following:

(a)

automatically open:

(b)

continue to provide protection.

(3)

An RCD used to protect against electric shock, and that is either installed as part of an installation or is a portable RCD, is deemed to be electrically unsafe if it has a rated residual current exceeding 30 milliamperes and—

(a)

it does not interrupt the current in all live conductors within—

(i)

300 milliseconds when passing its rated residual current; or

(ii)

40 milliseconds when passing 5 times its rated residual current; or

(b)

it interrupts the current in all live conductors when passing leakage current at or below half its rated residual current; or

(c)

it does not meet the limits specified in AS/NZS 3190.

(4)

An RCD installed as part of an installation for the protection of property is deemed to be electrically unsafe if—

(a)

it has a maximum operating time of—

(i)

more than 0.5 seconds at its rated residual current; or

(ii)

more than 0.15 seconds at 5 times its rated residual current; or

(b)

it has a rated residual current exceeding 300 milliamperes.

(5)

An RCD installed as part of an installation to protect against electric shock to patients during patient treatment is deemed to be electrically unsafe if—

(a)

it has a rated residual current exceeding 10 milliamperes; or

(b)

it has a rated residual current of 10 milliamperes or less but—

(i)

it does not interrupt the current in all live conductors within 40 milliseconds when passing its rated residual current and when passing 5 times its rated residual current; or

(ii)

it interrupts the current in all live conductors when passing leakage current at or below 45% of its rated residual current.

(6)

Where an RCD is required by AS/NZS 3000 to be installed to protect children from the risk of electric shock from direct contact, the RCD is deemed to be electrically unsafe if—

(a)

it has a rated residual current exceeding 10 milliamperes; or

(b)

it has a rated residual current of 10 milliamperes or less but—

(i)

it does not interrupt the current in all live conductors within—

(A)

300 milliseconds when passing its rated residual current; or

(B)

40 milliseconds when passing 5 times its rated residual current; or

(ii)

it interrupts the current in all live conductors when passing leakage current at or below half its rated residual current.

Compare: SR 1997/60 r 64

Regulation 24(3)(a): amended, on 10 November 2011, by regulation 11(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(3)(b): amended, on 10 November 2011, by regulation 11(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(4): substituted, on 10 November 2011, by regulation 11(3) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(5)(b)(i): amended, on 10 November 2011, by regulation 11(4) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(5)(b)(ii): amended, on 10 November 2011, by regulation 11(5) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(6): amended, on 10 November 2011, by regulation 11(6) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(6)(b)(i): amended, on 10 November 2011, by regulation 11(7) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 24(6)(b)(ii): amended, on 10 November 2011, by regulation 11(8) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

24A Electrically unsafe safety-critical equipment


Safety-critical equipment used or installed in an ERZ0 or ERZ1 is deemed to be electrically unsafe if the equipment has not been certified in accordance with clause 34 of Schedule 8 as being suitable to remain powered at all times.

Regulation 24A: inserted, on 31 December 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

24B Electrically unsafe electrical work in relation to certain mining electrical equipment

(1)

This regulation applies to electrical work—

(a)

that is performed on mining electrical equipment in an ERZ0 or ERZ1 in a way that compromises the explosion protection properties of that mining electrical equipment:

(b)

that involves the use of testing equipment that is not certified, in accordance with clause 37 of Schedule 8, for use in the ERZ0 or ERZ1 where the equipment is used or is intended to be used.

(2)
Electrical work to which this regulation applies is deemed to be electrically unsafe unless it is carried out under an approval system for live electrical work established as part of the electrical engineering control plan for the mining operation required by the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013.

Regulation 24B: inserted, on 31 December 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

25 Specific installations, fittings, and appliances deemed to be electrically safe



Despite anything in these regulations, the following installations, fittings, and appliances are deemed to be electrically safe if they comply with the standards indicated and are used in accordance with those standards:

(a)

installations, fittings, and appliances in medical locations: all of AS/NZS 2500, AS/NZS 3003, AS/NZS 3551, and NZS 6115:

(b)

electric fences: AS/NZS 3014:

(c)

electric security fences: AS/NZS 3016:

(d)

construction sites: AS/NZS 3012:

(e)

film and television sites: AS/NZS 4249.

Compare: SR 1997/60 r 69B(a), (d), (e)
Regulation 25(a): amended, on 10 November 2011, by regulation 12 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

26 When fittings and appliances in use deemed to be electrically safe

(1)

This regulation applies to a fitting or appliance, other than an electrical medical device, that is in use, or available for use,—

(a)

by an employee or contractor of the owner of the fitting or appliance; or

(b)

by a hirer or lessee under a hire or lease agreement with the owner of the fitting or appliance; or

(c)

by the occupier of premises that are rented or leased from the owner of the fitting or appliance.

(2)
A fitting or appliance described in subclause (1)(a) is deemed to be electrically safe if it has a current tag issued in accordance with AS/NZS 3760.

(3)

A fitting or appliance described in subclause (1)(b) or (c) is deemed to be electrically safe—

(a)

if it has a current tag issued in accordance with AS/NZS 3760; or

(b)

if, at the time it is first made available for use by the hirer, lessee, or occupier, it is supplied with electricity through a portable RCD, or through a circuit protected by an electrically safe RCD, that provides protection from electric shock.

(4)
A fitting described in subclause (1)(b) or (c) is deemed to be electrically safe if it is a fitting that is part of an installation and it complies with AS/NZS 3019.

Compare: SR 1997/60 r 76

Regulation 26: substituted, on 10 November 2011, by regulation 13 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 26(4): inserted, on 1 February 2014, by clause 6 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Part 3 Systems of supply

27 Systems in general

(1)
A person supplying electricity or line function services may choose the configuration and voltage of supply systems for the electricity, subject to this regulation.

(2)
Installations designed and constructed to operate at standard low voltage other than low voltage AC railway signalling equipment must be connected to a MEN system of supply.

(3)
However, subclause (2) does not apply to any fittings that are used, or designed or intended for use, by any person in connection with the generation of electricity for that person’s use and not for supply to any other person.

(4)

If an installation other than low voltage AC railway signalling equipment is supplied with electricity from a MEN system of supply,—

(a)

the installation must have at least 1 MEN switchboard; and

(b)

the switchboard located electrically closest to the point of supply must be a MEN switchboard.

(5)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she connects an installation to a supply of electricity otherwise than in accordance with this regulation.

Compare: SR 1997/60 rr 52(1), (2), (4), 67(a)

Regulation 27(2): amended, on 1 February 2014, by clause 7(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 27(4): amended, on 1 February 2014, by clause 7(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 27(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 27(5): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

28 Voltage supply to installations

(1)

The supply of electricity to installations operating at a voltage of 200 volts AC or more but not exceeding 250 volts AC (calculated or measured at the point of supply)—

(a)

must be at standard low voltage; and

(b)

except for momentary fluctuations, must be kept within 6% of that voltage.

(2)

The supply of electricity to installations operating at other than standard low voltage (calculated or measured at the point of supply)—

(a)

must be at a voltage agreed between the electricity retailer and the customer; and

(b)

unless otherwise agreed between the electricity retailer and the customer, and except for momentary fluctuations, must be maintained within 6% of the agreed supply voltage.

(3)
A person who supplies electricity commits an offence and is liable on conviction to a level 2 penalty if he or she supplies electricity to an installation in breach of this regulation.

Compare: SR 1997/60 rr 53(1), (2), 67(a)

Regulation 28(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 28(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

29 Frequency of electricity supplied

(1)
The frequency of electricity supplied by a person must be maintained within 1.5% of 50 hertz, except for momentary fluctuations.

(2)
The requirement in subclause (1) may be varied for supplies at other than standard low voltage if the supplier and the person receiving the supply agree.

(3)
A person who supplies electricity commits an offence and is liable on conviction to a level 2 penalty if he or she supplies it otherwise than in accordance with this regulation.

Compare: SR 1997/60 rr 55, 67(a)

Regulation 29(2): substituted, on 10 November 2011, by regulation 14 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 29(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 29(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

30 Requirements relating to safety of electricity supplied

(1)

In order to ensure that the supply of electricity is safe,—

(a)

the electrical characteristics of the supply system must not be altered in a way that may cause danger to persons or property; and

(b)

reasonable steps must be taken to ensure that the maximum prospective fault currents on the supply system are limited to reasonable levels.

(2)

A person who supplies electricity or line function services commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

alters the electrical characteristics of the supply system in breach of subclause (1)(a); or

(b)

fails to take reasonable steps to ensure that the maximum prospective fault currents on the supply system are limited to reasonable levels.

Compare: SR 1997/60 r 57

Regulation 30(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 30(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

31 Requirements relating to quality of supply

(1)
In order to preserve the quality of electricity supplied, the use of fittings and appliances must not unduly interfere with the satisfactory supply of electricity to any other person, or impair the safety, or interfere with the operation, of any other fittings or appliances.

(2)

In relation to interference from harmonics, compliance with whichever of the following standards is applicable is deemed to be compliance with subclause (1):

(a)

ECP 36:

(b)

IEC 61000–3–2:

(c)

IEC/TS 61000–3–4:

(d)

IEC 61000–3–12.

(3)

In relation to interference from flicker, compliance with whichever of the following standards is applicable is deemed to be compliance with subclause (1):

(a)

IEC 61000–3–3:

(b)

IEC/TS 61000–3–5:

(c)

IEC 61000–3–11.

(4)

A person commits an offence and is liable on conviction to a level 1 penalty if the person, knowingly or recklessly,—

(a)

uses a fitting or appliance that breaches, or results in the breach of, subclause (1); or

(b)

sells or offers to sell a fitting or appliance that breaches, or results in the breach of, subclause (1).

Compare: SR 1997/60 r 56

Regulation 31(4): substituted, on 10 November 2011, by regulation 15 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 31(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 31(4): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

32 Protection against fault currents

(1)
A person who supplies line function services to a consumer must, in respect of that consumer, provide a service protective fitting (being a fitting that can interrupt the supply of electricity to an installation) of appropriate rating for protection against short-circuits or earth faults on mains.

(2)
A person who supplies line function services commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (1).

Compare: SR 1997/60 rr 62(3), 67(h)

Regulation 32(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 32(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

33 Requirements relating to construction of, or work in vicinity of, telecommunications equipment

(1)

If telecommunications equipment is being constructed in the vicinity of works or installations, the person constructing the telecommunications equipment must ensure that it is constructed so that any induced voltage or earth potential rise that is capable of being created by electricity conveyed through the works or installations and impressed onto the telecommunications equipment is not likely to cause—

(a)

serious harm to any person; or

(b)

significant damage to the telecommunications plant or equipment.

(2)

If works or installations are being constructed in the vicinity of telecommunications equipment, the person constructing the works or installations must ensure that they are constructed so that any induced voltage or earth potential rise that is capable of being created by electricity conveyed through the works and installations and impressed onto the telecommunications equipment is not likely to cause—

(a)

serious harm to any person; or

(b)

significant damage to the telecommunications plant or equipment.

(3)

Voltages impressed onto telecommunications equipment by induction or earth potential rise are deemed not to be likely to cause serious harm to persons if,—

(a)

in respect of a fault in an AC system of supply of electricity,—

(i)

the magnitude and duration of any resulting shock currents cannot exceed curve c2 of Fig 20 of IEC/TS 60479-1; or

(ii)

the impressed voltages do not exceed—

(A)

430 volts AC for fault durations exceeding 0.5 seconds but not exceeding 5 seconds; and

(B)

650 volts AC for fault durations not exceeding 0.5 seconds; or

(b)

in respect of a fault in a DC system of supply of electricity, or in respect of a fault on an electrified railway operating on a DC system of supply of electricity,—

(i)

the magnitude and duration of any resulting shock currents cannot exceed curve c2 of Fig 22 of IEC/TS 60479-1; or

(ii)

the impressed voltages do not exceed 1 000 volts peak.

(4)

Voltages impressed onto telecommunications equipment by induction or earth potential rise are deemed not to be likely to cause significant damage to telecommunications equipment if, in the case of a fault in an AC system of supply of electricity, the impressed voltages do not exceed—

(a)

430 volts AC for fault durations exceeding 0.5 seconds but not exceeding 5 seconds; and

(b)

650 volts AC for fault durations not exceeding 0.5 seconds.

(5)
Voltages impressed onto telecommunications equipment by induction or earth potential rise are deemed not to be likely to cause significant damage to telecommunications equipment if, in the case of a fault in a DC system of supply of electricity or a fault on an electrified railway operating on a DC system of supply of electricity, the impressed voltages do not exceed 1 000 volts peak.

(6)

A person commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

constructs telecommunications equipment in the vicinity of works or installations and fails to comply with the requirements of subclause (1); or

(b)

constructs works or installations in the vicinity of telecommunications equipment and fails to comply with the requirements of subclause (2).

(7)

In this regulation,—
telecommunications equipment means any telecommunications line, structure, device, or thing designed or intended for use for telecommunications purposes
telecommunications line has the meaning given to it in section 2(1) of the Act.

Regulation 33: replaced, on 1 February 2014, by clause 8 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

33A Limits of operation of SWER systems in relation to telecommunications

(1)
This regulation applies to an AC SWER system, other than an AC electrified railway traction system, that has high voltage operational voltage to earth.

(2)

During normal operation, the SWER system must not impress on a telecommunication line—

(a)

a transverse noise voltage, measured at the user’s end of the telecommunication line, greater than 0.5mV; or

(b)

an induced voltage greater than 35 Vr m s.

(3)
During any normal or fault-related operation, the SWER system must not cause earth potential rises coupled to the neutral conductor of a MEN system, or voltages impressed on a telecommunication line, that exceed the maximum voltages in the voltage limit tables of the ITU-T Directives Vol VI:2008.

(4)

In this regulation,—
ITU-T Directives Vol VI:2008 means the ITU-T Directives concerning the protection of telecommunication lines against harmful effects from electric power and electrified railway lines—Vol VI: Danger, damage and disturbance, published in 2008 by the International Telecommunication Union
ITU-T Recommendation K68 means the ITU-T Recommendation K68: Operator responsibilities in the management of electromagnetic interference by power systems on telecommunication systems, published in 2008 by the International Telecommunication Union

psophometric frequency weighted value means the calculated value of an induced voltage resulting from the application to the measured value of the voltage of a factor that recognises that the human ear responds to sounds within the speech frequency range in accordance with weighting factors defined by the psophometric weighting factor table in Appendix 1 of ITU-T Recommendation K68. The psophometrically weighted value of a voltage comprising fundamental and harmonic components is given by the following expression:

Wp=

√(∑(Xf.Pf)2)

P800

where—

Xf

is the measured value of the voltage component at frequency f
Pf

is the psophometric weighting factor at frequency f
P800

is the psophometric weighting factor at frequency 800 Hz

transverse noise voltage means the psophometrically weighted value of the voltage in a telecommunication circuit, measured across a 600-ohm resistor terminating the line when the other end of the line is terminated on a standard telephone line termination, that results when a voltage is impressed on the telecommunication circuit by an electric line.

Regulation 33A: inserted, on 10 November 2011, by regulation 17 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

Part 4 Safety of works

Rules applying in relation to all works

34 Protective fittings for works

(1)
The owner of works must ensure that the works have adequate electrical protection against short circuits and earth faults.

(2)
Where fittings that form part of any works are used to protect against over-current, short-circuiting, earth fault current, overvoltage, under-voltage, and no voltage, the owner of those works must ensure that the fittings are designed and installed to achieve the maximum practicable sensitivity and minimum practicable operating times, within the limits necessary to achieve discrimination, in relation to the characteristics of the circuits or other fittings that those fittings protect.

(3)
The owner or operator of works that contain fittings referred to in subclause (2) must ensure that the fittings are set to achieve the maximum practicable sensitivity and minimum practicable operating times, within the limits necessary to achieve discrimination, in relation to the characteristics of the circuits or other fittings that those fittings protect.

(4)
A person who owns works commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (1) or (2).

(5)
A person who owns or operates works commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (3).

Compare: SR 1997/60 rr 60, 61, 62(1)

Regulation 34(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 34(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 34(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 34(5): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

35 Interference with, or movement of, works

(1)

A person must not interfere with, or move or attempt to move, any works, whether or not the works have been damaged, unless—

(a)

the person obtains permission from the owner or operator of the works; or

(b)

the person is authorised by an enactment; or

(c)

an emergency requires it.

(2)
A person commits an offence and is liable on conviction to a level 1 penalty if he or she breaches subclause (1).

Compare: SR 1997/60 r 93A

Regulation 35(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 35(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

36 Generating facilities and substations

(1)
All electricity generating facilities of works and installations, and all substations, must be secured against access by unauthorised persons.

(2)
An owner or operator of a generating facility or substation commits an offence and is liable on conviction to a level 1 penalty if he or she fails to secure the facility or substation against access by unauthorised persons.

Compare: SR 1997/60 r 89

Regulation 36(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 36(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

37 Works constructed as low voltage installations


If low voltage works are constructed that comply with the requirements of a low voltage installation (as set out in Part 5) then, without affecting the application of any other regulations in this Part to those works, regulation 38 does not apply to the works.

Regulation 37: amended, on 1 February 2014, by clause 9 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

37A Trolley bus supply systems must be treated as works

(1)
A trolley bus supply system that complies, or is intended to comply, with this Part (which is about works) must be treated for all purposes as if it were works to which this Part applies.

(2)
Subclause (1) applies whether or not the trolley bus supply system is an installation to which Part 5 (which is about installations) would otherwise apply.

(3)

In this regulation, trolley bus supply system means a system for the supply of electricity to trolley buses that comprises—

(a)

a contact line system (as defined in BS EN 50119); and

(b)

fittings that have the sole purpose of supplying electricity to trolley buses.

Regulation 37A: inserted, on 10 November 2011, by regulation 18 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

38 Testing works before connecting to supply

(1)
This section applies if prescribed electrical work has been done on any works.

(2)

Before connecting new works to a power supply, the person doing the connection must—

(a)

be satisfied that tests have been carried out that ensure that the completed works are electrically safe; and

(b)

ensure that—

(i)

the polarity and phase rotation of the supply are correct; and

(ii)

the protection of the supply is correctly rated; and

(iii)

the works are compatible with the supply system.

(3)

Before connecting or reconnecting existing works to a power supply following maintenance of, or any alteration of or addition to, the works, the person doing the connection or reconnection must—

(a)

be satisfied that tests have been carried out that ensure that—

(i)

the work done has not reduced the safety of the works; and

(ii)

any alterations or additions are electrically safe; and

(b)

ensure that (where appropriate)—

(i)

the polarity and phase rotation of the supply are correct; and

(ii)

the protection of the supply is correctly rated.

(4)
The person referred to in subclause (2) or (3) may be satisfied that the tests required under subclause (2)(a) or (3)(a) have been carried out on the basis of documentation that he or she has personally sighted that is signed by the person who carried out the relevant testing.

(5)

The person referred to in subclause (2) or (3)—

(a)

may, for the purpose of subclause (2)(b) or (3)(b), rely on documentation that he or she has personally sighted that is signed by the person who carried out the testing as to what the polarity, phase rotation, and protection of the supply are; but

(b)

must determine himself or herself whether the polarity, phase rotation, and protection of the supply are correct.

(6)
A person who connects or reconnects works to a power supply commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (2) or (3).

Compare: SR 1997/60 r 37(1)
Regulation 38: replaced, on 1 February 2014, by clause 10 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Works not covered by audited safety management systems

39 Regulations 40 to 46 do not apply to works covered by audited safety management systems


Regulations 40 to 46 do not apply to works covered by an audited safety management system; regulations 47 to 56 deal with those works instead.

40 Safety checks of works

(1)
Every owner of works must establish and implement a safety checking system that complies with subclause (2) for regularly checking the electrical safety of the works.

(2)

The safety checking system must—

(a)

require that the works are checked for compliance with all the requirements of regulations 41 to 46; and

(b)

provide for periodic checking of the works—

(i)

at reasonable intervals; and

(ii)

by a person who is suitably qualified and has the necessary competencies and experience to carry out the check; and

(c)

require records to be kept of the results of every periodic check.

(3)

A person who owns works commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

fails to comply with subclause (1); or

(b)

fails to carry out the checks required by a system established and implemented in accordance with this regulation.

(4)
A person who operates works commits an offence and is liable on conviction to a level 2 penalty if the works have not been checked as required by a system established for the purposes of this regulation, and the person knows that the works have not been checked, or is reckless as to whether the works have been checked.

Compare: SR 1997/60 rr 60(3), 66(5), 67(f), (j)

Regulation 40(1): amended, on 10 November 2011, by regulation 19(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 40(2)(b): substituted, on 10 November 2011, by regulation 19(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 40(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 40(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 40(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 40(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

41 Structural loading on works

(1)
The owner of works must ensure that the works are designed, constructed, and maintained to minimise as far as practicable the risk of injury to persons or damage to property from the expected structural loading, having regard to the recognised natural occurrences in the areas that the works are or are to be situated.

(2)

The owner of works must ensure that overhead electric lines are constructed of suitable conductors and other fittings so that, as far as practicable, the lines—

(a)

are capable of withstanding, without damage, the likely static and dynamic loading; and

(b)

do not become unsafe or dangerous to the public or to persons likely to work on them.

(3)

If overhead line structures are found to be incapable of supporting structural design loads, the owner of the structures must—

(a)

mark them; and

(b)

repair or replace them within 12 months of finding them to be incapable of supporting the design loads.

(4)

If overhead line structures are found to be at risk of failure under normal structural loads, and there is a risk of injury to any person or damage to property other than that of the owner of the line, the owner of the structures must—

(a)

mark them; and

(b)

repair or replace them not later than 3 months after the finding of the risk of failure.

(5)

A person who owns works commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

constructs or maintains works, or requires works to be designed, in such a way that the works are inconsistent with the requirements set out in subclause (1); or

(b)

fails to comply with any of the obligations in subclauses (2) to (4).

Compare: SR 1997/60 r 66(1)–(4)

Regulation 41(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 41(5): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

42 Requirements for earthing systems in works

(1)

Every owner of works must ensure that the works are protected (whether from within the works or by the supplying works) by an earthing system that is designed, installed, operated, and maintained to ensure, as far as practicable,—

(a)

the effective operation of protection fittings in the event of earth fault currents; and

(b)

that the voltage of each conductor is restricted to a value consistent with the level of insulation applied; and

(c)

that step voltages, touch voltages, and transferred voltages are controlled to prevent danger to any person.

(2)

An earthing system is deemed to comply with subclause (1)(c) if it complies,—

(a)

in the case of a railway electrification system,—

(i)

with IEC 62128-1; and

(ii)

on or after 1 February 2014, with BS EN 50122-1; or

(b)

in every other case, with ECP 35.

(3)
A person who owns works commits an offence and is liable on conviction to a level 2 penalty if the person fails to comply with subclause (1).

Compare: SR 1997/60 rr 60(1), 67(g)

Regulation 42(2): replaced, on 1 February 2014, by clause 11 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 42(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 42(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

43 Isolation fittings for works

(1)
The owner of works must ensure that the works are capable of being isolated from its supply of electricity, whether that capability is provided from within the works or by the supplying works.

(2)
If the works comprise separate parts, the owner must also ensure that each part has an isolation fitting to isolate that part from its supply of electricity.

(3)
A person who owns works commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (1) or (2).

Compare: SR 1997/60 r 65

Regulation 43(2): amended, on 10 November 2011, by regulation 20 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 43(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 43(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

44 High voltage conductors of overhead electric lines

(1)
The owner of works must ensure that high voltage conductors of overhead electric lines are protected (whether from within the works or by the supplying works) by earth fault protection fittings that interrupt fault currents to earth in 5 seconds or less.

(2)
Short-circuit and earth fault protective fittings of the auto-closing type must operate for not more than 3 consecutive closures during a period not longer than 60 seconds, and must not be capable of further reclosures unless manually reset.

(3)

A person who owns works commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

fails to comply with subclause (1); or

(b)

owns works that do not comply with subclause (2).

Compare: SR 1997/60 r 62(5), (6)

Regulation 44(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 44(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

45 Permanent notices on works

(1)
The owner of works must ensure that conspicuous and durable notices reading “Danger Live Wires”, or some equivalent warning, are affixed, and maintained in a legible condition, on all poles or other supports that carry uninsulated conductors and that may be climbed without the use of equipment.

(2)
A person who owns works commits an offence and is liable on conviction to a level 2 penalty if the person fails to comply with subclause (1).

Compare: SR 1997/60 rr 66(6), 67(j)

Regulation 45(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 45(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

46 Keeping records and plans

(1)
The owner of works must keep such records and plans of those works as will enable the owner, if required, to readily locate any fittings of the works.

(2)
A person who owns works commits an offence and is liable on conviction to a level 1 penalty if the person fails to comply with subclause (1).

Compare: SR 1997/60 r 59

Regulation 46(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 46(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Works covered by audited safety management systems

47 Overview


Under section 61A of the Act, electricity generators and electricity distributors that own or operate an electricity supply system (as defined in that section) must implement and maintain safety management systems. Owners or operators of other works may choose to implement and maintain safety management systems as an alternative to complying with regulations 40 to 46. Regulations 48 to 56 set out requirements and other matters relating to safety management systems.

48 What safety management systems must do

(1)

Every safety management system must comply with either—

(a)

NZS 7901; or

(b)

regulations 49 and 50.

(2)
Nothing in regulation 49 or 50 applies to safety management systems that comply with NZS 7901.

49 Substantive requirements of safety management systems



Every safety management system must provide for the following:

(a)

the systematic identification of existing and new or potential hazards associated with the works, if possible before, and otherwise as, the hazards arise:

(b)

the assessment by the safety management system operator, at appropriate regular intervals, of the scope and magnitude of each hazard:

(c)

the steps that must be taken to eliminate, isolate, or minimise hazards (both generally and with respect to particular hazards) and to reduce the risks from those hazards:

(d)

the assessment of the effectiveness of steps taken to eliminate, isolate, or minimise hazards and to reduce the risks from hazards:

(e)

the investigation of accidents that involve or affect the works to which the safety management system relates:

(f)

how the safety management system operator proposes to continually enhance the safety management system:

(g)

an audit programme setting out the intervals at which audits must be carried out.

50 Documentation of safety management systems

(1)

Every safety management system must be fully documented, and the documentation must include, at a minimum, a description of the following:

(a)

the works (including its components) to which the safety management system relates:

(b)

all the matters referred to in regulation 49.

(2)
The documentation of the safety management system must be in a format and style that enables anyone auditing it to read it easily.

51 Audit of safety management systems

(1)

Every safety management system must be regularly audited to confirm whether—

(a)

the safety management system complies with NZS 7901 or regulations 49 and 50, as appropriate; and

(b)

the safety management system operator is implementing and maintaining the safety management system as written; and

(c)

the effect of the safety management system is that all practicable steps are taken to prevent the works from presenting a significant risk of—

(i)

serious harm to any member of the public; or

(ii)

significant damage to property owned by a person other than the safety management system operator.

(2)
Every audit must be conducted by an accredited auditor.

(3)
The first audit under this regulation of a safety management system must take place within 2 years after the date on which this regulation comes into force, and thereafter at intervals determined by the auditor but at least once every 5 years.

52 Audit certificate for safety management systems

(1)
If an accredited auditor is satisfied of the matters in regulation 51(1)(a) to (c), the auditor may issue an audit certificate for the safety management system.

(2)
The audit certificate must specify the period for which it is issued, which may be up to 5 years.

(3)
The audit certificate comes into force on and from the date it is issued and remains current for the period for which it is issued, unless earlier cancelled.

53 Statutory declaration by safety management system operator

(1)
Every safety management system operator must, at least once every 5 years, make, and send to WorkSafe, a statutory declaration that confirms that the operator’s safety management system has a current audit certificate.

(2)
However, the first statutory declaration made under this regulation must be made and sent to WorkSafe within 6 months after the first audit of the safety management system.

Regulation 53(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 53(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

54 Cancellation of audit certificate

(1)

An accredited auditor must cancel an audit certificate if—

(a)

the auditor, having conducted an audit, is not satisfied about 1 or more of the matters in regulation 51(1)(a) to (c); or

(b)

WorkSafe requires the accredited auditor to cancel the certificate on the grounds that WorkSafe is satisfied that the audited safety management system is not being implemented.

(2)
On cancelling an audit certificate, the accredited auditor must issue a notice of cancellation to the safety management system operator and give a copy of the notice of cancellation to WorkSafe.

Regulation 54(1)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 54(1)(b): amended, on 10 November 2011, by regulation 21 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 54(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

55 Certification and declaration deemed to be compliance with section 61A of Act

(1)

For the purpose of section 61A of the Act, a person is deemed to be implementing and maintaining a safety management system if—

(a)

the person holds a current audit certificate in respect of an audited safety management system; and

(b)

WorkSafe has received the statutory declaration required by regulation 53 within the time required by that regulation.

(2)
However, until the date that is 2 years after the date on which these regulations come into force, an electricity generator or electricity distributor is deemed to comply with section 61A of the Act if it complies with all of regulations 34 to 46.

Regulation 55(1)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

56 Offences by accredited auditors



An accredited auditor commits an offence and is liable on conviction to a level 2 penalty if that auditor—

(a)

issues an audit certificate under regulation 52 without being satisfied of the matters in regulation 51(1)(a) to (c); or

(b)

fails to cancel an audit certificate in the circumstances in regulation 54(1); or

(c)

fails to issue a notice of cancellation, or give a copy of the notice, as required by regulation 54(2).

Regulation 56: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 56: amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 56: amended, on 10 November 2011, by regulation 22 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

Part 5 Safety of installations

Domestic wiring exemption

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

57 Exemption for domestic electrical wiring work

(1)
A person who carries out prescribed electrical work in reliance on the exemption in section 79 of the Act (exemption for domestic electrical wiring work) must carry it out, and test the work, in accordance with ECP 51.

(2)

For the purposes of section 79(1)(a) of the Act, the domestic electrical wiring work that an owner of premises may do is work of any type described in subclause (3) on a domestic installation that has a maximum demand at or below—

(a)

80 amperes per phase if single-phase; or

(b)

50 amperes per phase if multi-phase.

(3)

The work to which subclause (2) relates is any of the following:

(a)

removing and replacing fuse links:

(b)

connecting and disconnecting fixed-wired appliances:

(c)

relocating existing switches, socket-outlets, and lighting outlets that are supplied with electricity by tough plastic-sheathed cables:

(d)

removing and replacing any of the following kinds of fittings (but only if the work does not involve work on a switchboard):

(i)

switches, socket-outlets, and light fittings:

(ii)

permanent connection units, ceiling roses, cord-grip lampholders, and flexible cords connected to any of them:

(iii)

batten holders:

(iv)

water heater switches:

(v)

thermostats:

(vi)

elements:

(e)

installing, extending, and altering subcircuits (including submains), but only if—

(i)

the person does not enter (whether directly, or by holding any material or equipment, or otherwise) any enclosure where live conductors are likely to be present; and

(ii)

the work is tested and certified in accordance with Part 2 of AS/NZS 3000, before being connected to a power supply, by a person authorised to inspect mains work.

Regulation 57: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Certified designs for installations

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

58 Certified designs

(1)

A design for an installation or part installation is a certified design if—

(a)

it identifies the location or proposed location of the installation or part installation; and

(b)

it identifies the standards (if any) with which the installation or proposed installation, or part installation or proposed part installation, complies or is intended to comply; and

(c)

the person who prepared the design signs and dates it.

(2)

A certified design for an installation or part installation must be such that, if it is installed, tested, inspected, and connected in accordance with the design, the resulting installation or part installation will—

(a)

comply with these regulations; and

(b)

be electrically safe, as required by regulation 14.

(3)
A person who installs, tests, inspects, or connects an installation or part installation to which a certified design relates is entitled (if acting in good faith) to rely on the design as ensuring that, if the installation or part installation is installed, tested, inspected, and connected in accordance with the design, the resulting installation or part installation will comply with subclause (2).

(4)

A person commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

falsely certifies a design for an installation or part installation; or

(b)

certifies a design that does not comply with subclause (2).

Regulation 58: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 58(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Rules for low and extra-low voltage installations

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

59 Low and extra-low voltage installations to comply with AS/NZS 3000

(1)

Every low or extra-low voltage domestic installation, or part of a domestic installation, must be installed, tested, inspected, and connected so as to comply with Part 2 of AS/NZS 3000 if it has a maximum demand at or below—

(a)

80 amperes per phase if single-phase; or

(b)

50 amperes per phase if multi-phase.

(2)

Every other low or extra-low voltage installation or part installation must be installed, tested, inspected, or connected so as to comply with either—

(a)

Part 2 of AS/NZS 3000; or

(b)

a certified design prepared in accordance with Part 1 of AS/NZS 3000.

(3)

A low voltage or extra-low voltage installation or part installation may be maintained or replaced in all or any of the following ways:

(a)

in such a way that the installation or part installation complies with Part 1 or Part 2 of AS/NZS 3000:

(b)

in such a way that the installation or part installation is restored to, or maintained in, its original condition:

(c)

by complying with all manufacturer’s instructions relating to the fittings used in, or affected by, the maintenance or replacement.

(4)
Despite subclause (2), low voltage AC railway signalling equipment must be tested in accordance with ECP 60, and not in accordance with AS/NZS 3000.

(5)
This regulation is subject to regulations 60 to 61A.

Regulation 59: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 59(4): replaced, on 31 December 2013, by regulation 12 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

60 Certain installations must comply with Part 2 of AS/NZS 3000

(1)

The following installations or part installations must be installed, tested, inspected, and connected so as to comply with Part 2 of AS/NZS 3000 and also with the standard indicated:

(a)

an installation or part installation intended for use with electrical medical devices: AS/NZS 3003:

(b)

an installation or part installation in a hazardous area: AS/NZS 60079.14:

(c)

a connectable installation or part of a connectable installation in a mobile medical facility: NZS 6115:

(d)

a connectable installation or part of a connectable installation in a pleasure vessel: AS/NZS 3004.2:

(e)

all other connectable installations or parts of connectable installations: AS/NZS 3001:

(f)

a site installation or part of a site installation that—

(i)

is in a marina: AS/NZS 3004.1; or

(ii)

is in a show or carnival: AS/NZS 3002; or

(iii)

is intended to supply connectable installations in mobile medical facilities: NZS 6115; or

(iv)

is intended to supply any other connectable installation: AS/NZS 3001.

(2)

If any of the following are installed so as to comply with Part 2 of AS/NZS 3000, they must also comply with the standards indicated:

(a)

a refrigeration system (but not a refrigeration appliance): AS/NZS 1677.2:

(b)

an animal stunning or meat conditioning system: NZS 6116:

(c)

a stand-alone power system: AS/NZS 4509.1:

(d)

a photovoltaic array: AS/NZS 5033:

(e)

an emergency power supply in a hospital: AS/NZS 3009:

(f)

a low voltage mains parallel generation system that is connected to the national grid: AS/NZS 3010 and AS 4777.1.

Regulation 60: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

61 Specific rules for installations under Part 1 of AS/NZS 3000

(1)
This regulation applies to any low or extra-low voltage installation that is being, or is to be, installed in accordance with a certified design prepared in accordance with Part 1 of AS/NZS 3000, despite anything in that part of AS/NZS 3000.

(2)

If the installation is a 2-wire or a 4-wire installation in which no conductor is earthed,—

(a)

switches and circuit breakers must be fitted in all conductors used in the installation; and

(b)

all poles must operate substantially together.

(3)
Switches, fuse links, or circuit breakers must not be inserted into an earthing conductor or into any earthing connection.

(4)

The voltage drop must not be more than 5% under maximum load conditions between the point of supply and—

(a)

any socket-outlet within an installation operating at standard low voltage; or

(b)

the supply terminals of any fixed-wired appliance connected to an installation operating at standard low voltage.

Regulation 61: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

61AA Installations in excavated areas must comply with AS/NZS 3007

(1)
An installation that is or will be located in an excavated area above ground (including an installation at an alluvial mining operation, opencast mining operation, or quarrying operation) must be installed, tested, inspected, and connected in accordance with AS/NZS 3007.

(2)
This regulation applies despite anything in Part 1 or Part 2 of AS/NZS 3000.

(3)
Regulation 59 is subject to this regulation.

Regulation 61AA: inserted, on 31 December 2013, by regulation 13 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

61A Rule about 3-pin flat-pin socket-outlets in low voltage installations

(1)

If a 3-pin flat-pin socket-outlet that has the dimensions specified in AS/NZS 3112 is, or is to be, installed in a low voltage installation, it must be installed in such a way that—

(a)

the socket-outlet may be supplied with electricity only at standard low voltage; and

(b)

the earth-continuity conductor is connected to the slot on the radial line; and

(c)

the order of connection, in a clockwise direction when the socket-outlet is viewed from the front, is—

(i)

earth-continuity conductor:

(ii)

active conductor:

(iii)

neutral (or other) conductor.

(2)
This regulation applies despite anything in Part 1 or Part 2 of AS/NZS 3000 or in these regulations.

(3)
A person who installs a socket-outlet referred to in subclause (1) otherwise than in accordance with that subclause commits an offence and is liable on conviction to a level 2 penalty.

Regulation 61A: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 61A(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Rules for high voltage installations

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

62 High voltage installations treated as if works

(1)
All installation, testing, inspection, and connection done on a high voltage installation must be done in accordance with a certified design prepared for the installation.

(2)
Without otherwise limiting the application of this Part to high voltage installations, regulations 34 and 39 to 46 apply to high voltage installations as if references in those regulations to works were references to high voltage installations.

Regulation 62: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Testing prescribed electrical work

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

63 Testing prescribed electrical work on low and extra-low voltage installations

(1)

All prescribed electrical work done on a low or extra-low voltage installation or part installation must be tested—

(a)

for operational safety; and

(b)

to ensure that the installation or part installation is not electrically unsafe; and

(c)

as required by regulation 59 or 60, as the case requires; and

(d)

in the case of an installation or part installation that does not comply with Part 2 of AS/NZS 3000, in accordance with the verification or testing process set out in the certified design for the installation or part installation.

(2)
However, subclause (1) does not apply if the prescribed electrical work is done by a person acting under the exemption in section 79 of the Act (exemption for domestic electrical wiring work) unless, in order to comply with regulation 57, the work is required to be tested.

(3)
A person who fails to test prescribed electrical work as required by this regulation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 63: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 63(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

64 Testing prescribed electrical work on high voltage installations

(1)

Prescribed electrical work done on a high voltage installation must be tested in accordance with regulation 38 as if—

(a)

references in that regulation to works were references to the installation; and

(b)

the reference to documentation were a reference to a certificate of compliance, record of inspection, and any other documentation recording tests and test results.

(2)
A person who fails to test prescribed electrical work on a high voltage installation as required by this regulation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 64: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 64(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Certifying prescribed electrical work

Heading: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

65 Requirement for certificate of compliance

(1)

A certificate of compliance must be issued in accordance with these regulations for all general and high-risk prescribed electrical work done on an installation or part installation that comprises—

(a)

the installation or maintenance of conductors used in the installation or part installation; or

(b)

the installation or maintenance of fittings where the fittings are connected, or intended to be connected, to conductors used in the installation or part installation.

(2)
A person who does low-risk prescribed electrical work may, but is not obliged by these regulations to, issue a certificate of compliance for that work.

(3)
No general prescribed electrical work may be treated as complete until a certificate of compliance is issued for it.

(4)
No high-risk prescribed electrical work may be treated as complete until a certificate of compliance, along with any record of inspection required for the prescribed electrical work, is issued for it.

(5)
A person issuing a certificate of compliance for prescribed electrical work done on an installation or part installation, or an electrical safety certificate for an installation or part installation, is, if he or she is acting in good faith, entitled to rely on the veracity of any certificates of compliance issued within the previous 6 months in respect of prescribed electrical work done on the installation or any part of the installation.

(6)
Despite anything in this regulation, and although the certification, inspection, and supervision of prescribed electrical work is itself prescribed electrical work (by virtue of clause (1)(f) to (h) of Schedule 1), nothing in this clause requires a certificate of compliance to be issued for those kinds of prescribed electrical work.

(7)

Subclauses (1), (3), and (4) do not apply in relation to general or high-risk prescribed electrical work done on an installation or part installation if—

(a)

the owner or operator of the installation has a maintenance management system in place for the installation; and

(b)

the maintenance management system ensures that the information required by regulation 67 to be on a certificate of compliance for the work is recorded in relation to all general and high-risk prescribed electrical work done on the installation.

Regulation 65: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 65(5): replaced, on 31 December 2013, by regulation 14 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

66 Content of certificate of compliance

(1)

Every certificate of compliance for prescribed electrical work must—

(a)

contain a statement confirming that the person issuing the certificate is satisfied that—

(i)

the prescribed electrical work has been done lawfully and safely; and

(ii)

the information in the certificate is correct; and

(b)

provide the information required by regulation 67(1) and (2); and

(c)

include in or on it the authentication mark, as specified in regulation 111B; and

(d)

have attached to it a copy of any manufacturer’s instructions, supplier declarations of conformity, and certified designs used in the course of the prescribed electrical work.

(2)

For the purposes of a certificate of compliance, prescribed electrical work on an installation or part installation has been done lawfully and safely if—

(a)

the work has been done as required by these regulations; and

(b)

the testing required by these regulations has been satisfactorily completed; and

(c)

the installation or part installation on which the work was done is electrically safe; and

(d)

the work has not adversely affected the safety of—

(i)

the installation on which the work was done, or any part of that installation; or

(ii)

any fittings that form part of the installation on which the work was done.

(3)
If it is impractical to attach a copy of a particular manufacturer’s instructions, or of any certified design or supplier declarations of conformity, to a certificate of compliance, the certificate must instead contain a reference to where the documents can be found, in a readily accessible format, through electronic means.

Regulation 66: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

67 Information recorded on certificate of compliance

(1)

Every certificate of compliance must record the following:

(a)

if the work is high-risk work on a low or extra-low voltage installation or part installation, whether the work has been done in accordance with Part 1 of AS/NZS 3000 or in accordance with Part 2 of AS/NZS 3000:

(b)

whether the work has been done in accordance with the certified design for the installation or part installation:

(c)

if the work was required to comply with standards other than, or in addition to, Part 1 or Part 2 of AS/NZS 3000, which standards were complied with:

(d)

whether the work done relied on any manufacturer’s instructions:

(e)

the type of supply system that the installation or part installation is safe to connect to:

(f)

which parts of the installation, if any, are safe to connect to a power supply.

(2)

Every certificate of compliance must also—

(a)

identify the location of the installation or part installation on which prescribed electrical work was done; and

(b)

describe the work done; and

(c)

give the name of the person issuing the certificate; and

(ca)

give the name of any person who, acting under the supervision of the person in paragraph (c), performed any of the prescribed electrical work referred to in the certificate; and

(d)

give the registration number (if any) of every person referred to in paragraph (c) or, if the person issuing the certificate is acting under an employer licence, the employer’s licence number; and

(e)

give the date or dates on which the work was done, or the period within which it was done; and

(f)

be signed and dated by the person issuing the certificate.

(3)
The person issuing a certificate of compliance may include any additional information (such as testing results) on the certificate.

Regulation 67: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 67(2)(c): replaced, on 31 December 2013, by regulation 15 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 67(2)(ca): inserted, on 31 December 2013, by regulation 15 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

68 Who may issue certificate of compliance



A person may issue a certificate of compliance only if—

(a)

the person is authorised to certify the prescribed electrical work to which the certificate relates; or

(b)

in the case of prescribed electrical work carried out under an employer licence, the person is authorised to certify the work under the system of operation used by the employer.

Regulation 68: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

69 Offences relating to certificates of compliance



A person commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

falsely certifies any prescribed electrical work; or

(b)

purports to certify prescribed electrical work when the certificate of compliance does not comply with the requirements of regulation 66(1); or

(c)

issues a certificate of compliance that contains incorrect information; or

(d)

issues a certificate of compliance in relation to particular prescribed electrical work when not authorised to certify that work.

Regulation 69: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 69: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Inspecting prescribed electrical work

Heading: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

70 High-risk prescribed electrical work to be inspected

(1)
All high-risk prescribed electrical work done on a low or extra-low voltage installation or part installation must be inspected as required by regulation 59 or 60, as the case requires.

(2)

All high-risk prescribed electrical work done on a high voltage installation must be inspected so as to verify that the installation complies with—

(a)

ECP 34; and

(b)

regulations 34, 41(1), 42(1), 43(1), and 44(1), as if references in those regulations to works were references to high voltage installations.

(3)

A person who inspects high-risk prescribed electrical work must undertake whatever tests, visual inspection, or other actions are necessary to satisfy the person that—

(a)

that work has been done in accordance with these regulations; and

(b)

the installation or part installation on which that work has been done is, and will be when enlivened, electrically safe.

Regulation 70: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 70(3): amended, on 31 December 2013, by regulation 16(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 70(3)(a): amended, on 31 December 2013, by regulation 16(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 70(3)(b): amended, on 31 December 2013, by regulation 16(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

71 Who may carry out inspection

(1)

A person may inspect high-risk prescribed electrical work only if—

(a)

the person is authorised to inspect high-risk prescribed electrical work; or

(b)

in the case of high-risk prescribed electrical work carried out under an employer licence, the person is authorised to inspect the work under the system of operation used by the employer.

(2)

However, a person may not inspect prescribed electrical work if the person has—

(a)

personally carried out the work; or

(b)

supervised someone else carrying out the work; or

(c)

issued the certificate of compliance for the work.

Regulation 71: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

72 Record of inspection

(1)
A person who carries out an inspection of high-risk prescribed electrical work must prepare a written record of the inspection.

(2)

The record of inspection must—

(a)

identify the work that was inspected; and

(b)

be signed and dated by the person carrying out the inspection; and

(c)

include or have on it the authentication mark, as specified in regulation 111B; and

(d)

if the inspection was carried out in accordance with a standard, identify the standard and state that the inspection was carried out in accordance with that standard; and

(e)

if the inspection was carried out in accordance with a certified design, identify the certified design and state that the inspection was carried out in accordance with that certified design; and

(f)

state whether the work that has been inspected has been done in accordance with these regulations; and

(g)

state whether the installation or part installation on which the work has been done is, and will be (when powered), electrically safe.

(3)
The person who carries out the inspection must attach the certificate of compliance, or a copy of the certificate of compliance, to the record of inspection.

(4)
If the inspection relates to work covered by more than 1 certificate of compliance, the record of inspection must identify the certificates of compliance to which it relates.

Regulation 72: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 72(2): replaced, on 31 December 2013, by regulation 17 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 72(3): replaced, on 31 December 2013, by regulation 17 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 72(4): replaced, on 31 December 2013, by regulation 17 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

72A What happens to records of inspection

(1)

A person who issues a record of inspection must—

(a)

provide a copy of it, within 20 working days after it is issued, to the person who contracted for the prescribed electrical work or, if that person is not readily available, to the owner or occupier of the place on or thing in which the installation or part installation is located; and

(b)

retain a copy, whether in hard copy or electronically, for at least 7 years.

(2)

A person who issues a record of inspection must, on request by any of the following, provide a copy of the record within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the installation is located:

(e)

the person who contracted for the work to which it relates:

(f)

the owner or occupier of the place on or thing in which the installation or part installation is located.

Regulation 72A: inserted, on 31 December 2013, by regulation 18 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

73 Offences relating to inspection



A person who inspects prescribed electrical work commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

fails to inspect the work sufficiently to be satisfied of the matters in regulation 70(3); or

(b)

gives a written record of inspection that is false in a material respect; or

(c)

carries out an inspection and fails to prepare a written record of inspection in accordance with regulation 72.

Regulation 73: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 73: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 73(b): amended, on 31 December 2013, by regulation 19(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 73(c): inserted, on 31 December 2013, by regulation 19(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Connection to power supply after prescribed electrical work

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

73A Before connecting installations to power supply

(1)

Before connecting to a power supply a low or extra-low voltage installation or part installation on which prescribed electrical work has been done, the person doing the connection must—

(a)

be satisfied that the installation or part installation is safe to connect; and

(b)

be satisfied that the testing required by these regulations has been done; and

(c)

if a certificate of compliance is required for the work, either issue or sight a certificate of compliance issued no earlier than 6 months before the installation or part installation is connected; and

(d)

if the work is required to be inspected, either inspect the work and complete a record of inspection or sight a record of inspection given by another person no earlier than 6 months before the installation or part installation is connected; and

(da)

if the work is required to be inspected and a certificate of compliance is required for the work, attach the certificate of compliance or a copy of the certificate of compliance to the record of inspection; and

(e)

in the case of a low voltage installation or part installation, do all of the following:

(i)

ensure that the polarity and phase rotation of the supply are correct:

(ii)

ensure that the protection of the supply is correctly rated:

(iii)

ensure that the installation or part installation to be connected is compatible with the supply system:

(iv)

if the supply is from a MEN system, verify that there is a main earthing system.

(2)
Before a person connects a high voltage installation or part installation to a power supply, the person must comply with the requirements of regulation 38(2) as if references in that regulation to works were references to the installation or part installation.

(3)
If the person who connects an installation or part installation has not done the testing required by these regulations personally, the person must sight documentation, signed by the person who did the tests, that sets out what tests were carried out and what the results were.

(4)
A person who undertakes the connection of an installation or part installation is entitled (if acting in good faith) to rely on the veracity of any certificates of compliance relating to prescribed electrical work done on the installation or part installation, and on the veracity of any equivalent certificate issued under these regulations before 1 July 2013.

(5)
To avoid doubt, in this regulation connection refers to the prescribed electrical work that is the final step that will allow electricity to flow in the installation or part installation on which other prescribed electrical work has been done.

Regulation 73A: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 73A(1)(da): inserted, on 31 December 2013, by regulation 20 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

73B Offence relating to connection


A person who connects an installation or part installation to a power supply in breach of any requirement of regulation 73A commits an offence and is liable on conviction to a level 2 penalty.

Regulation 73B: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 73B: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Reconnection when no general or high-risk prescribed electrical work done

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

74 Reconnecting or restoring power supply to certain low voltage installations

(1)

This regulation applies to a low voltage installation or part installation—

(a)

that has been disconnected or isolated from a power supply; and

(b)

on which no general or high-risk prescribed electrical work has been done since the last disconnection or isolation.

(2)

If the period since the last disconnection or isolation of the installation or part installation is more than 6 months, the person proposing to reconnect or restore supply must, before doing so, give or sight a certificate issued in accordance with section 3 of AS/NZS 3019 that—

(a)

was issued no earlier than 6 months before the date of reconnection or restoration of supply; and

(b)

certifies that the installation or part installation is suitable for continued use; and

(c)

is given by a person authorised to certify mains work.

(3)
A person reconnecting or restoring supply to an installation or part installation is entitled (if acting in good faith) to rely on a written confirmation by the owner of the installation or part installation that no general or high-risk prescribed electrical work has been done on it since it was last disconnected or isolated.

(4)
A person who reconnects or restores supply to an installation or part installation commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with subclause (2).

Regulation 74: replaced, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Certifying installations

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

74A Electrical safety certification

(1AA)

This regulation applies to prescribed electrical work on—

(a)

an installation; or

(b)

a part installation; or

(c)

any fitting that supplies an installation or a part installation with electricity.

(1)

After the work referred to in subclause (1AA) is complete, the person who completed the work must issue an electrical safety certificate for the installation or part installation if the person is satisfied that—

(a)

the installation or part installation is safe to use, on the grounds that it is electrically safe and complies with these regulations; and

(b)

where the prescribed electrical work comprised the maintenance or alteration of, or the addition to, the installation or part installation, the work has not adversely affected any other part of the installation.

(2)
For the purposes of subclause (1), if an installation or part installation was disconnected from a power supply while the prescribed electrical work was done, the work is complete only once the installation or part installation is connected or reconnected to a power supply.

(3)

An electrical safety certificate must—

(a)

include a statement that the person issuing it is satisfied that the installation or part installation is connected to a power supply and is safe to use; and

(b)

clearly state whether the electrical safety certificate relates to the whole of the installation or just to specified parts of it; and

(c)

identify the location of the installation or part installation to which it relates; and

(d)

include or have on it the authentication mark, as specified in regulation 111B; and

(e)

give the date on which the connection was done; and

(f)

be signed and dated by—

(i)

the person who did the connection; and

(ii)

if the person who did the connection was acting under supervision, the supervisor; and

(g)

give the name and registration number of—

(i)

the person who did the connection; or

(ii)

if that person was acting under an employer licence, the employer’s licence number; or

(iii)

if the person in subparagraph (i) was acting under supervision, the registration number of the supervisor.

(4)
If prescribed electrical work is done without disconnecting the power supply, references in subclause (3)(e) to (g) to connection must be taken to be references to the completion of the work.

(5)
An electrical safety certificate issued for an installation or part installation is, for the purposes of section 19(1)(e) of the Building Act 2004, a certificate that confirms that any prescribed electrical work done on the installation or part installation complies with the building code.

Regulation 74A: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74A(1AA): inserted, on 31 December 2013, by regulation 21(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74A(1): amended, on 31 December 2013, by regulation 21(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74A(3)(f): replaced, on 31 December 2013, by regulation 21(3) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74A(3)(g): replaced, on 31 December 2013, by regulation 21(3) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

74B Exception for operators with maintenance management systems



If prescribed electrical work is done on an installation, then despite regulation 74A, an electrical safety certificate does not need to be issued for the installation if—

(a)

the owner or operator of the installation has a maintenance management system in place for the installation; and

(b)

the maintenance management system ensures that information equivalent to the information required by regulation 74A(3) is recorded and kept (except that the authentication mark required by regulation 74A(3)(d) need not be recorded and kept).

Regulation 74B: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74B: amended, on 31 December 2013, by regulation 22(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74B(b): amended, on 31 December 2013, by regulation 22(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

74C Time when electrical safety certificate to be issued


A person who issues an electrical safety certificate for an installation or part installation on which prescribed electrical work has been done (other than referred to in regulation 74B) must do so as soon as practicable after the installation or part installation is connected to a power supply, but in any case no later than 20 working days after connection.

Regulation 74C: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

74D Offences relating to electrical safety certificates



A person commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

issues an electrical safety certificate when not satisfied as required by regulation 74A(1); or

(b)

issues an electrical safety certificate that does not comply with regulation 74A(3); or

(c)

fails to issue an electrical safety certificate, if required to, within the time required by regulation 74C.

Regulation 74D: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74D: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Record-keeping

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

74E What happens to certificates of compliance

(1)

In this regulation,—
certificate of compliance includes any record of inspection included in, or attached to, a certificate of compliance issued under regulation 66

responsible person, in relation to a certificate of compliance, means—

(a)

the person who issued it; or

(b)

if the person who issued the certificate of compliance was acting under an employer licence, the holder of the employer licence.

(c)

[Revoked]

(2)
The responsible person must, within 20 days after completing the work, provide a copy of the certificate of compliance for prescribed electrical work to the person who contracted for the work or, if that person is not readily available, to the occupier or owner of the place or thing in which the installation or part installation is located.

(3)
The responsible person must retain a copy, whether in hard copy or electronically, of every certificate of compliance for at least 7 years.

(4)

A responsible person must, on request by any of the following, provide a copy of the certificate to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the prescribed electrical work was done:

(e)

the person who contracted for the work:

(f)

the owner or occupier of the place or thing in which the installation or part installation is located.

(5)

The owner or occupier of an installation to which regulation 65(7) applies must, on request by any of the following, provide a copy of the information referred to in regulation 65(7)(b), or specified parts of that information, to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the installation is located.

(6)
Nothing in this regulation prevents a person who issues a certificate of compliance from retaining a copy of the certificate, even if he or she is not the responsible person.

Regulation 74E: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74E(1) responsible person paragraph (c): revoked, on 31 December 2013, by regulation 23(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74E(2): amended, on 31 December 2013, by regulation 23(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74E(4)(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 74E(5): amended, on 31 December 2013, by regulation 23(3) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74E(5)(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

74F Details of high-risk work to be lodged on database

(1)

Details of high-risk prescribed electrical work (including details of the certificate of compliance provided in respect of that work) must be lodged on the database referred to in regulation 112A—

(a)

by the person who inspected the work; and

(b)

within 20 working days after the date of the record of inspection.

(2)
The particular details to be lodged, and the manner in which they must be lodged, are as determined by WorkSafe.

Regulation 74F: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74F heading: amended, on 31 December 2013, by regulation 24(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74F(1): amended, on 31 December 2013, by regulation 24(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74F(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

74G What happens to electrical safety certificates

(1)

A person who issues an electrical safety certificate must—

(a)

provide a copy of it, within 20 working days after it is issued, to the person who contracted for the prescribed electrical work or, if that person is not readily available, to the owner or occupier of the place or thing in which the installation or part installation is located; and

(b)

retain a copy, whether in hard copy or electronically, for at least 7 years.

(2)

A person who issues an electrical safety certificate must, on request by any of the following, provide a copy of the certificate to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the installation is located:

(e)

the person who contracted for the work:

(f)

the owner or occupier of the place or thing in which the installation or part installation is located.

(3)

The owner or occupier of an installation to which regulation 74B applies must, on request by any of the following, provide a copy of the information referred to in regulation 74B(b), or specified parts of that information, to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the installation is located.

Regulation 74G: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74G(2): amended, on 31 December 2013, by regulation 25(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 74G(2)(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 74G(3): replaced, on 31 December 2013, by regulation 25(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

74H Offences relating to record-keeping


A person commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with any of the requirements of regulations 74E to 74G.

Regulation 74H: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 74H: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

Miscellaneous

Heading: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

74I Location of installations



For the purpose of identifying on a certified design, certificate of compliance, or electrical safety certificate the location of an installation or part installation, location means,—

(a)

for an installation or part installation in a permanent location,—

(i)

if the location has a street address, the street address and, if applicable, the place at that street address where the installation or part installation is located; and

(ii)

if the location does not have a street address, a description of the place along with some form of specific identification of the location (such as its GPS co-ordinates); or

(b)

for a connectable installation or part installation, a unique identifier for the connectable installation (such as a chassis number); or

(c)

for an installation or part installation in a thing that will be, but is not yet, in a permanent location, a unique identifier fixed to the thing for the purpose of identifying the location of the installation or part installation.

Regulation 74I: inserted, on 1 July 2013, by regulation 11 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Periodic assessments

75 Periodic assessments of certain installations

(1)

The owners and operators of the following installations must ensure that the installations are periodically assessed as set out below, to determine whether they are electrically safe and otherwise comply with these regulations:

(a)

low voltage installations in caravan parks: in accordance with AS/NZS 3001, at intervals not exceeding 5 years:

(b)

low voltage installations in boat marinas: in accordance with AS/NZS 3004.1, at intervals not exceeding 5 years:

(c)

low voltage installations at demolition and constructions sites: in accordance with AS/NZS 3012:

(d)

low voltage installations at carnivals and fair grounds: in accordance with AS/NZS 3002, at intervals not exceeding 1 year:

(e)

low voltage installations, other than domestic installations, in hazardous areas: in accordance with AS/NZS 60079.17:

(f)

low voltage and extra-low voltage installations intended for use with electrical medical devices situated—

(i)

in mobile medical facilities: in accordance with NZS 6115:

(ii)

in any other medical location: AS/NZS 3003.

(2)
The assessments referred to in subclause (1)(a) to (c) may be undertaken only by a person who is authorised to assess prescribed electrical work on the relevant kind of installation in the relevant location.

(3)
The assessments referred to in subclause (1)(d) to (f) may be undertaken only by any person with the competencies referred to in the relevant standard specified.

(4)

A person who completes a periodic assessment must—

(a)

complete a record of assessment; and

(b)

in the record of assessment,—

(i)

state whether the assessment was carried out in accordance with a standard (and identify that standard); and

(ii)

state whether the assessment was carried out in accordance with a certified design (and identify that certified design); and

(c)

give the record of assessment to the person requesting the assessment; and

(d)

keep a copy of that record of assessment for at least 3 years, or send a copy to WorkSafe.

(4A)
If the relevant standard prescribes a form for a record of assessment, the record of assessment referred to in subclause (4) must be in that form.

(5)
A person who owns and retains in service an installation that is required by this regulation to be periodically assessed commits an offence and is liable on conviction to a level 1 penalty if the installation is not assessed in accordance with subclause (1).

(6)

A person who does an assessment under this regulation commits an offence and is liable on conviction to a level 2 penalty if he or she,—

(a)

in the case of an assessment referred to in subclause (1)(a) to (c), is not authorised to assess that kind of installation in that location; or

(b)

in the case of an assessment referred to in subclause (1)(d) to (f), does not have the appropriate competencies; or

(c)

fails to comply with subclause (4).

(7)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she uses an installation that is required by this regulation to be periodically assessed knowing that subclause (6) applies to the person who did the inspection.

(8)
To avoid doubt, subclause (1) and the intervals referred to in that subclause apply despite anything to the contrary in any of the standards referred to in that subclause.

Compare: SR 1997/60 r 46

Regulation 75(1)(e): amended, on 10 November 2011, by regulation 31(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 75(1)(f)(ii): amended, on 10 November 2011, by regulation 31(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 75(2): amended, on 31 December 2013, by regulation 26(1) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(2): amended, on 31 December 2013, by regulation 26(2) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(3): amended, on 31 December 2013, by regulation 26(2) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(4): replaced, on 31 December 2013, by regulation 26(3) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(4A): inserted, on 31 December 2013, by regulation 26(3) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(5): amended, on 31 December 2013, by regulation 26(4) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 75(5): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 75(6): amended, on 31 December 2013, by regulation 26(5) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(6): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 75(6): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 75(6)(a): amended, on 31 December 2013, by regulation 26(5) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(6)(a): amended, on 31 December 2013, by regulation 26(6) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(6)(b): amended, on 31 December 2013, by regulation 26(5) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(7): amended, on 31 December 2013, by regulation 26(7) of the Electricity (Safety) Amendment Regulations 2013 (SR  2013/494).
Regulation 75(7): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 75(7): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 75(8): inserted, on 31 December 2013, by regulation 26(8) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Connectable installations

76 No supply without warrant of electrical fitness

(1)
Before permitting or authorising a connection for the supply of electricity to a connectable installation in a vehicle, relocatable building, or pleasure vessel, the person supplying electricity must verify that the connectable installation has a current warrant of electrical fitness.

(2)
A person who supplies electricity commits an offence and is liable on conviction to a level 1 penalty if he or she fails to comply with subclause (1).

Compare: SR 1997/60 r 98(5)

Regulation 76(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 76(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

77 Restrictions on use of connectable installations

(1)
A person must not hire or lease out, or offer to hire or lease out, a vehicle, relocatable building, or pleasure vessel that contains a connectable installation unless the connectable installation has a current warrant of electrical fitness.

(2)
A person who hires or leases out, or offers to hire or lease out, a vehicle, relocatable building, or pleasure vessel commits an offence and is liable on conviction to a level 1 penalty if he or she fails to comply with subclause (1).

Compare: SR 1997/60 r 97(4)

Regulation 77(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 77(2): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

78 Issue of warrants of electrical fitness for connectable installations

(1)

The following people may issue warrants of electrical fitness for connectable installations:

(a)

a person who is authorised to inspect mains work:

(b)

a person who, immediately before these regulations come into force, is authorised by the Secretary to issue warrants of electrical fitness, but only in respect of the same class of connectable installations that the authorisation relates to:

(c)

in relation to a connectable installation that has been certified under regulation 66, the person who did the certification (and, to avoid doubt, the warrant may be issued at the same time that the certification is done).

(2)

Every warrant of electrical fitness for a connectable installation must be issued in accordance with AS/NZS 3001, except that a warrant of electrical fitness for a connectable installation—

(a)

in a pleasure vessel must be issued in accordance with AS/NZS 3004.2; and

(b)

in a mobile medical facility must be issued in accordance with NZS 6115; and

(c)

that has been imported must be issued in accordance with AS/NZS 3001, but only after an assessment for compliance with Part 1 of AS/NZS 3000.

(3)

A person who issues a warrant of electrical fitness must—

(a)

give it to the person who requests the warrant; and

(b)

keep a copy of the completed warrant for at least 3 years, or send a copy to WorkSafe; and

(c)

complete a warrant of electrical fitness sticker that is in the form prescribed or approved by WorkSafe; and

(d)

affix the sticker in a prominent place on the connectable installation.

(4)

A warrant of electrical fitness for a connectable installation expires on the earlier of—

(a)

the date on which a new warrant of electrical fitness is issued for the connectable installation; or

(b)

the date that is 4 years from its date of issue or, in the case of a mobile medical facility, 1 year from its date of issue.

(5)

Every warrant of electrical fitness must be in a form that is either—

(a)

the form prescribed by the relevant standard referred to in subclause (2); or

(b)

a form approved by WorkSafe.

(6)
If WorkSafe charges a fee to supply forms of warrants of electrical fitness, the fee must be the fee set out in Schedule 5.

(7)

A person commits an offence and is liable on conviction to a level 1 penalty if he or she—

(a)

issues a warrant of electrical fitness otherwise than in accordance with this regulation; or

(b)

issues a warrant of electrical fitness for a connectable installation that is electrically unsafe; or

(c)

is not authorised to issue a warrant of electrical fitness.

Compare: SR 1997/60 r 97(3), (5)–(7)

Regulation 78(2)(b): amended, on 10 November 2011, by regulation 32 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 78(2)(c): added, on 10 November 2011, by regulation 32 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 78(3)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 78(3)(c): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 78(5)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 78(6): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 78(7): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 78(7): amended, on 1 July 2013, by regulation 7(2) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Part 5A Mining electrical equipment and conductors

Part 5A: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78A Interpretation

(1)

In this Part and Schedule 8, operator,—

(a)

in relation to an alluvial mining operation, means the alluvial mine operator:

(b)

in relation to a mining operation, means the mine operator:

(c)

in relation to a quarrying operation, means the quarry operator.

(2)
For the purpose of identifying on a certified design or electrical safety certificate the location of an alluvial mining operation, a mining operation, or a quarrying operation under this Part or Schedule 8, location has the meaning given to it in regulation 74I.

Regulation 78A: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Alluvial mining operations and quarrying operations

Heading: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78B Obligations in relation to alluvial mining operations and quarrying operations

(1)

Regulations 78C and 78D and Parts 1 and 2 of Schedule 8 apply to—

(a)

all mobile and relocatable mining electrical equipment that is used, installed, or intended to be used at—

(i)

any alluvial mining operation:

(ii)

any quarrying operation; and

(b)

all conductors that are used or intended to be used to supply that equipment with electricity.

(2)
An alluvial mine operator must ensure compliance with the requirements of Parts 1 and 2 of Schedule 8 in relation to all mobile and relocatable mining electrical equipment and conductors supplying that equipment that are used, installed, or intended to be used at an alluvial mining operation.

(3)
An alluvial mine operator who fails to comply or ensure compliance with any requirement in Part 1 or 2 of Schedule 8 in relation to any mobile and relocatable mining electrical equipment or conductor supplying that equipment that is used, installed, or intended to be used at an alluvial mining operation commits an offence and is liable on conviction to a level 2 penalty.

(4)
A quarry operator must ensure compliance with the requirement of Parts 1 and 2 of Schedule 8 in relation to all mobile and relocatable mining electrical equipment and conductors supplying that equipment that are used, installed, or intended to be used at a quarrying operation.

(5)
A quarry operator who fails to comply or ensure compliance with any requirement in Part 1 or 2 of Schedule 8 in relation to any mobile and relocatable mining electrical equipment or conductor supplying that equipment that is used, installed, or intended to be used at a quarrying operation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 78B: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78C Standards for equipment at alluvial mining operations and quarrying operations

(1)

All mobile and relocatable mining electrical equipment and conductors supplying that equipment at an alluvial mining operation or quarrying operation must be—

(a)

designed and constructed so as to comply with whichever official standard listed in Schedule 4 applies to the equipment or conductor; and

(b)

tested, inspected, and connected so as to comply with AS/NZS 3007; and

(c)

installed or relocated in accordance with AS/NZS 3007.

(2)

Mobile and relocatable mining electrical equipment and conductors supplying that equipment at an alluvial mining operation or a quarrying operation may only be maintained or replaced in 1 or more of the following ways:

(a)

such that the equipment and conductors comply with AS/NZS 3007:

(b)

such that the equipment and conductors are restored to, or maintained in, their original condition:

(c)

by complying with all manufacturer’s instructions relating to the equipment and conductors, and other fittings used in, or affected by, the maintenance or replacement.

(3)

An operator commits an offence and is liable on conviction to a level 2 penalty if any mobile and relocatable mining electrical equipment or conductor supplying that equipment that is used at an alluvial mining operation or a quarrying operation—

(a)

has not been designed or constructed in accordance with subclause (1)(a); or

(b)

has not been tested, inspected, or connected in accordance with subclause (1)(b); or

(c)

has not been installed or relocated in accordance with subclause (1)(c); or

(d)

has not been maintained or replaced in accordance with subclause (2).

Compare: SR 2010/36 r 59
Regulation 78C: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78D Periodic assessment of equipment and conductors at alluvial mining operations and quarrying operations

(1)
All mobile and relocatable mining electrical equipment and conductors supplying that equipment at an alluvial mining operation or a quarrying operation must be periodically assessed to determine whether they are electrically safe and otherwise comply with regulation 17(1)(c) and all of the requirements of Part 1 of Schedule 8.

(2)

The assessments referred to in subclause (1) must be carried out—

(a)

at least once annually; and

(b)

in accordance with AS/NZS 3007; and

(c)

by a person who is authorised to inspect mining electrical equipment in the relevant location.

(3)

A person who does a periodic assessment must—

(a)

ensure that the results of the assessment are recorded on the form (if any) approved by WorkSafe; and

(b)

give the record of the assessment to the person requesting the assessment; and

(c)

keep a copy of that record for at least 3 years, or send a copy to WorkSafe.

(4)
An operator commits an offence and is liable on conviction to a level 1 penalty if any mobile or relocatable mining electrical equipment or conductor supplying that equipment is not assessed in accordance with subclause (1).

(5)

A person who does an assessment for the purposes of this regulation commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

is not authorised to inspect mining electrical equipment in the relevant location; or

(b)

fails to comply with subclause (3).

(6)

An operator who uses, or allows any other person to use, any equipment or conductor to which this regulation applies commits an offence and is liable on conviction to a level 2 penalty if—

(a)

the equipment or conductor has not been assessed in accordance with this regulation; and

(b)

the person knows that the equipment or conductor has not been assessed, or is reckless as to whether it has been assessed.

(7)
An operator commits an offence and is liable on conviction to a level 2 penalty if he or she uses, or allows any other person to use, any equipment or conductor that is required by this regulation to be periodically assessed and the operator knows that any person who assessed the equipment or conductor was not authorised to inspect mining electrical equipment in the relevant location.

Compare: SR 2010/36 r 75
Regulation 78D: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Opencast mining operations

Heading: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78E Obligations in relation to opencast mining operations

(1)

Regulations 78F and 78G and Parts 1 and 2 of Schedule 8 apply to—

(a)

all mobile and relocatable mining electrical equipment that is used, installed, or intended to be used at an opencast mining operation; and

(b)

all conductors that are used or intended to be used to supply that equipment with electricity.

(2)
A mine operator must ensure compliance with the requirements of Parts 1 and 2 of Schedule 8 in relation to all mobile and relocatable mining electrical equipment and conductors supplying that equipment that are used, installed, or intended to be used at an opencast mining operation.

(3)
Any mine operator who fails to comply or ensure compliance with any requirement in Part 1 or 2 of Schedule 8 in relation to any mobile and relocatable mining electrical equipment or conductor supplying that equipment that is used, installed, or intended to be used at an opencast mining operation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 78E: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78F Standards for equipment at opencast mining operations

(1)

All mobile and relocatable mining electrical equipment and conductors supplying that equipment at an opencast mining operation must be—

(a)

designed and constructed so as to comply with whichever official standard listed in Schedule 4 applies to the equipment or conductor; and

(b)

tested, inspected, and connected so as to comply with AS/NZS 3007; and

(c)

installed or relocated in accordance with AS/NZS 3007.

(2)

Mobile and relocatable mining electrical equipment and conductors supplying that equipment at an opencast mining operation may only be maintained or replaced in 1 or more of the following ways:

(a)

such that the equipment and conductors comply with AS/NZS 3007:

(b)

such that the equipment and conductors are restored to, or maintained in, their original condition:

(c)

by complying with all manufacturer’s instructions relating to the equipment and conductors, and other fittings used in, or affected by, the maintenance or replacement.

(3)

An operator commits an offence and is liable on conviction to a level 2 penalty if any equipment or conductor that is used at an opencast mining operation—

(a)

has not been designed or constructed in accordance with subclause (1)(a); or

(b)

has not been tested, inspected, or connected in accordance with subclause (1)(b); or

(c)

has not been installed or relocated in accordance with subclause (1)(c); or

(d)

has not been maintained or replaced in accordance with subclause (2).

Compare: SR 2010/36 r 59
Regulation 78F: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78G Safety assessment programmes at opencast mining operations

(1)
A mine operator must establish and implement a safety assessment programme that complies with subclause (2) for regularly assessing the electrical safety of mobile and relocatable mining electrical equipment and conductors supplying that equipment that are used or installed at an opencast mining operation.

(2)

The safety assessment programme must—

(a)

require that all electrical work carried out on mobile and relocatable mining electrical equipment and conductors supplying that equipment is assessed and verified for compliance with regulation 17(1)(c); and

(b)

provide for the periodic assessment of mobile and relocatable mining electrical equipment and conductors supplying that equipment to determine whether they are electrically safe and otherwise comply with all of the requirements of Part 1 of Schedule 8; and

(c)

require records to be kept of—

(i)

the results of every periodic assessment; and

(ii)

details of any issues found during the assessment; and

(iii)

any actions required to be taken in relation to those issues; and

(iv)

any actions that were taken immediately in relation to the issues.

(3)

The assessments referred to in subclause (2)(b) must be carried out—

(a)

at least once annually; and

(b)

in accordance with AS/NZS 3007; and

(c)

by a person who is authorised to inspect mining electrical equipment in the relevant location.

(4)

An operator commits an offence and is liable on conviction to a level 1 penalty if—

(a)

he or she fails to comply with subclause (1):

(b)

any electrical work carried out at the mining operation is not assessed in accordance with subclause (2)(a):

(c)

any mining electrical equipment or conductor is not assessed in accordance with subclause (2)(b):

(d)

he or she fails to keep the records required under subclause (2)(c).

(5)

An operator who uses, or allows any other person to use, any mining electrical equipment or conductor supplying that equipment commits an offence and is liable on conviction to a level 2 penalty if—

(a)

the equipment or conductor has not been assessed in accordance with subclause (3); and

(b)

the operator knows that the equipment has not been assessed, or is reckless as to whether the equipment has been assessed.

(6)
An operator commits an offence and is liable on conviction to a level 2 penalty if he or she uses, or allows any other person to use, any equipment or conductor that is required by this regulation to be periodically assessed and the operator knows that any person who assessed the equipment was not authorised to inspect mining electrical equipment in the relevant location.

Compare: SR 2010/36 r 40
Regulation 78G: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Tunnelling operations and underground mining operations

Heading: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78H Obligations in relation to tunnelling operations

(1)

Regulations 78J and 78K and Parts 1 to 3 of Schedule 8 apply to—

(a)

all mining electrical equipment that is used, installed, or intended to be used at a tunnelling operation; and

(b)

all conductors that are used or intended to be used to supply that equipment with electricity.

(2)
A mine operator must ensure compliance with the requirements of Parts 1 to 3 of Schedule 8 in relation to all mining electrical equipment and conductors supplying that equipment that are used, installed, or intended to be used at a tunnelling operation.

(3)
A mine operator who fails to comply or ensure compliance with any requirement in Parts 1 to 3 of Schedule 8 in relation to any mining electrical equipment or conductor supplying that equipment that is used, installed, or intended to be used at a tunnelling operation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 78H: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78I Obligations in relation to underground mining operations

(1)

Regulations 78J and 78K and Schedule 8 apply to—

(a)

all mining electrical equipment that is used, installed, or intended to be used at an underground mining operation; and

(b)

all conductors that are used or intended to be used to supply that equipment with electricity.

(2)
A mine operator must ensure compliance with the requirements of Schedule 8 in relation to all mining electrical equipment and conductors supplying that equipment that are used, installed, or intended to be used at an underground mining operation.

(3)
A mine operator who fails to comply or ensure compliance with any requirement in Schedule 8 in relation to any mining electrical equipment or conductor supplying that equipment that is used, installed, or intended to be used at an underground mining operation commits an offence and is liable on conviction to a level 2 penalty.

Regulation 78I: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78J Certified designs for mining electrical equipment and conductors at tunnelling operations and underground mining operations

(1)

A mine operator must ensure that there is a certified design for mining electrical equipment and conductors supplying that equipment at—

(a)

every underground mining operation:

(b)

every tunnelling operation.

(2)

A design for mining electrical equipment and conductors is a certified design if—

(a)

it identifies the location or proposed location of—

(i)

all mining electrical equipment installed and used at the tunnelling operation or underground mining operation; and

(ii)

all conductors supplying that equipment; and

(b)

it identifies the standards (if any) with which the following comply or are intended to comply:

(i)

all mining electrical equipment installed and used at the tunnelling operation or underground mining operation; and

(ii)

all conductors supplying that equipment; and

(c)

it is signed and dated by the person or persons who prepared it.

(3)

A certified design for mining electrical equipment and conductors must—

(a)

specify—

(i)

how mining electrical equipment (including cables and other fittings) will be installed; and

(ii)

how conductors will be installed; and

(iii)

how mobile and relocatable mining electrical equipment will be safely used, or is intended to be safely used, at the mining operation; and

(iv)

how the conductors that will supply mobile and relocatable mining electrical equipment will be safely used, or are intended to be safely used, at the tunnelling operation or underground mining operation; and

(v)

requirements for the testing, commissioning, and periodic assessment of the mining electrical equipment and conductors that is required; and

(vi)

in the case of an underground coal mining operation, the controls required to prevent the mining electrical equipment and conductors igniting any flammable gas; and

(vii)

requirements for the maintenance (including repairs and overhauls) of the mining electrical equipment, including safety-critical equipment; and

(viii)

requirements for the calibration and testing of safety-critical equipment; and

(ix)

periodic assessment of safety-critical equipment, including the frequency of verification; and

(b)

be such that, if the mining electrical equipment and conductors supplying that equipment are installed, tested, inspected, and connected in accordance with the design, they will—

(i)

comply with these regulations; and

(ii)

be electrically safe, as required by regulation 14.

(4)

A certified design must be prepared by a competent person or competent persons who—

(a)

are suitably qualified to design a certified design for mining electrical equipment and conductors that are to be installed or used in a tunnelling operation or an underground mining operation (as the case may be); and

(b)

collectively have adequate knowledge, training, skills, and experience of—

(i)

the control of earth potential rise; and

(ii)

the use of relocatable mining electrical equipment; and

(iii)

the performance of safety functions required for mining activities and mining electrical equipment; and

(iv)

risk management; and

(v)

if the certified design is for equipment in an underground coal mining operation, the control of the ignition of methane.

(5)
A person who installs, tests, inspects, or connects mining electrical equipment or conductors to which a certified design under this regulation relates is (if acting in good faith) entitled to rely on the design as ensuring that, if the mining electrical equipment and conductors are installed, tested, inspected, and connected in accordance with the design, they will comply with these regulations.

(6)
For the purpose of subclause (3)(b)(ii), mining electrical equipment and conductors at a tunnelling operation are deemed to be electrically safe if they are installed, tested, inspected, and connected in accordance with a certified design that complies with BS 6164.

(7)

A person commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

falsely certifies a design for mining electrical equipment and conductors; or

(b)

certifies a design that does not comply with this regulation.

Regulation 78J: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78K Safety assessment programmes at tunnelling operations and underground mining operations

(1)
A mine operator must establish and implement a safety assessment programme that complies with subclause (2) for regularly assessing and verifying the electrical safety of all mining electrical equipment and conductors supplying that equipment that are installed or used at a tunnelling or an underground mining operation.

(2)

The safety assessment programme must—

(a)

provide for the periodic assessment of the mining electrical equipment and conductors supplying that equipment that are installed or used at the mining operation—

(i)

at least once annually; and

(ii)

by a person who is authorised to inspect electrical work on mining electrical equipment in the relevant location; and

(b)

require daily assessments of all reeling and trailing cables to ensure that they are not damaged; and

(c)

require daily assessments of the following to ensure that they are operating effectively:

(i)

all safety-critical equipment; and

(ii)

all isolation fittings associated with reeling and trailing cables; and

(d)

require records to be kept of—

(i)

the results of every daily and periodic assessment; and

(ii)

details of any issues found during the assessment; and

(iii)

the actions required to be taken in relation to those issues; and

(iv)

any actions that were taken immediately in relation to those issues.

(3)

Assessments of mining electrical equipment and conductors under subclause (2) must be carried out—

(a)

to determine—

(i)

if the equipment and conductors are electrically safe; and

(ii)

compliance with Part 1 of Schedule 8; and

(iii)

in the case of an underground coal mining operation, whether suitable controls are in place to prevent the equipment and conductors igniting any flammable gas; and

(b)

in accordance with the following:

(i)

in the case of tunnelling operations, BS 6164:

(ii)

in the case of underground mining operations, the equipment’s certified design.

(4)

An operator commits an offence and is liable on conviction to a level 1 penalty if—

(a)

he or she fails to comply with subclause (1):

(b)

any assessment is not carried out in accordance with subclause (2)(a), (b), or (c):

(c)

he or she fails to keep the records required under subclause (2)(d).

(5)

An operator who uses, or allows any other person to use, any mining electrical equipment or conductor supplying that equipment commits an offence and is liable on conviction to a level 2 penalty if—

(a)

the equipment or conductor has not been assessed in accordance with subclause (3); and

(b)

the operator knows that the equipment or conductor has not been assessed, or is reckless as to whether the equipment has been assessed.

(6)
An operator commits an offence and is liable on conviction to a level 2 penalty if he or she uses, or allows any other person to use, any equipment or conductor that is required by this regulation to be periodically assessed and the operator knows that any person who assessed the equipment was not authorised to inspect mining electrical equipment in the relevant location.

Compare: SR 2010/36 r 40
Regulation 78K: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78L General offences

(1)
Any person who installs a socket-outlet referred to in clause 6(1) of Schedule 8 otherwise than in accordance with that subclause commits an offence and is liable on conviction to a level 2 penalty.

(2)
A person who fails to test prescribed electrical work as required by clause 7 or 8 of Schedule 8 commits an offence and is liable on conviction to a level 2 penalty.

(3)

A person who inspects prescribed electrical work commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

fails to inspect the work sufficiently to be satisfied of the matters in clause 9(3) of Schedule 8; or

(b)

gives a written record of inspection that is false in a material respect.

(4)
A person who connects any mining electrical equipment or conductors supplying that equipment in breach of any requirement of clause 12 of Schedule 8 commits an offence and is liable on conviction to a level 2 penalty.

(5)

A person commits an offence and is liable on conviction to a level 2 penalty if he or she—

(a)

issues an electrical safety certificate when he or she is not satisfied as required by clause 13(1) of Schedule 8; or

(b)

issues an electrical safety certificate that does not comply with clause 13(3) of Schedule 8; or

(c)

fails to issue an electrical safety certificate, if required to, within the time required by clause 15 of Schedule 8.

(6)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she fails to comply with any of the requirements of clause 16 of Schedule 8.

Regulation 78L: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Tourist mining operations

Heading: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

78M Obligations in relation to tourist mining operations

(1)

A mine operator of a tourist mining operation must ensure that—

(a)

mining electrical equipment and conductors supplying that equipment are installed, tested, and inspected so as to comply with AS/NZS 3012:

(b)

the supply of electricity to the equipment and conductors does not exceed that of a reduced low voltage system.

(2)
Regulations 78B, 78E, and 78H, and Schedule 8 do not apply to tourist mining operations that comply with subclause (1).

Regulation 78M: inserted, on 31 December 2013, by regulation 27 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Part 6 Safety of fittings and appliances

79 Maintenance of domestic appliances

(1)
A person who carries out prescribed electrical work in reliance on the exemption in section 80 of the Act (exemption for maintenance of domestic appliances) must carry it out in accordance with ECP 50.

(2)
For the purposes of section 80(1)(c) of the Act, the prescribed electrical work that the owner of any appliance may do or assist in doing is work on appliances that operate at low voltage.

Compare: SR 1997/60 r 48

80 New and used fittings and appliances to be electrically safe

(1)
Every new or used fitting, and every new or used appliance, that is sold, offered for sale, supplied, or offered for supply must be electrically safe.

(2)

A new fitting or appliance is, for the purpose of this regulation, deemed to be electrically safe if—

(a)

it complies with—

(i)

AS/NZS 3820; or

(ii)

whichever official standard listed in Schedule 4 applies to the fitting or appliance; or

(b)

in relation to an appliance imported into New Zealand in purported compliance with the Conformity Cooperation Agreement, it complies with the requirements of that Agreement.

(3)

A used appliance is, for the purpose of this regulation, deemed to be electrically safe if, at the time it is sold or offered for sale,—

(a)

it is tested, inspected, and tagged in accordance with AS/NZS 5761; or

(b)

it has been disabled and marked in accordance with AS/NZS 4701; or

(c)

in the case of a used electrical medical device, it is tested and marked in accordance with AS/NZ 3551.

(4)
A person who sells, offers for sale, supplies, or offers for supply a new or used fitting or appliance, knowing that, or being reckless as to whether, the fitting or appliance is electrically unsafe, commits an offence and is liable on conviction to a level 2 penalty.

Compare: 1997/60 r 76

Regulation 80(1): amended, on 1 February 2014, by clause 12(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 80(2): amended, on 1 February 2014, by clause 12(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 80(3): amended, on 1 February 2014, by clause 12(3) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 80(4): amended, on 1 February 2014, by clause 12(4) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 80(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 80(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

81 Evidence of compliance with standards

(1)
A test report or certificate of conformity that shows that a low voltage or extra-low voltage fitting or appliance complies with AS/NZS 3820 or any standard listed in Schedule 4 is conclusive evidence, in the absence of proof to the contrary, of compliance with regulation 80.

(2)

For the purposes of this regulation, a test report is an original or a certified copy of a report issued—

(a)

by a laboratory—

(i)

accredited by International Accreditation New Zealand; or

(ii)

accredited by a body that has a mutual recognition agreement with International Accreditation New Zealand; or

(iii)

approved as a testing laboratory by or under an international agreement between New Zealand and another country (being any territory for whose international relations the government of the country is responsible); or

(b)

under the Certification Body Scheme of the Worldwide System for Conformity Testing and Certification of Electrotechnical Equipment and Components, known as the IECEE CB Scheme.

(3)

For the purposes of this regulation, a certificate of conformity is a certificate issued by—

(a)

a body accredited by the Joint Accreditation System of Australia and New Zealand for product certification; or

(b)

a body accredited by a signatory to the International Accreditation Forum multilateral recognition arrangement for product certification.

Regulation 81(1): amended, on 10 November 2011, by regulation 33 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

82 Offences relating to false or incorrect marking

(1)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she tags or marks a fitting or appliance with a false or incorrect tag or marking relating to electrical safety.

(2)

A person commits an offence and is liable on conviction to a level 2 penalty if he or she sells or offers for sale a fitting or appliance that bears CCC marks, but the marks—

(a)

were applied otherwise than in accordance with the Conformity Cooperation Agreement; or

(b)

do not comply with that Agreement.

Compare: 1997/60 r 100(ab)

Regulation 82(1): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 82(1): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 82(2): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 82(2): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

83 Supplier declaration of conformity required before sale of declared medium risk articles

(1)
WorkSafe may, by notice in the Gazette, declare that particular low voltage or extra-low voltage fittings or appliances, or particular types or classes of low voltage or extra-low voltage fittings or appliances, are medium risk fittings or appliances (in this regulation called declared medium risk articles).

(2)

A declared medium risk article may not be sold, offered for sale, supplied, or offered for supply unless—

(a)

the supplier (being the New Zealand manufacturer or importer) has made a supplier declaration of conformity in respect of the article; or

(b)

the article is deemed to be approved by WorkSafe under regulation 83A and all relevant terms and conditions of the deemed approval are complied with.

(3)

A supplier declaration of conformity must—

(a)

contain a description of the declared medium risk article; and

(b)

contain a statement that the article complies with—

(i)

the appropriate standard listed in Schedule 4; or

(ii)

AS/NZS 3820; or

(iii)

the Conformity Cooperation Agreement; and

(c)

[Revoked]

(d)

be in the form that is prescribed by WorkSafe or, if no form is prescribed, comply with ISO/IEC 17050–1.

(3A)
For the purposes of issuing a certificate of compliance for prescribed electrical work done on an installation or part installation, or for issuing an electrical safety certificate for an installation or part installation, the person issuing the certificate is entitled (if acting in good faith) to rely on the veracity of any supplier declaration of conformity relating to any articles used in or incorporated into the installation.

(3B)

A supplier declaration of conformity ceases to be valid (and a new supplier declaration of conformity is required before the article can be sold, supplied, offered for sale, or offered for supply under subclause (2)) if—

(a)

any material change has been made to the article or the article’s product specifications; or

(b)

the statement required by subclause (3)(b) is no longer correct because certification has been withdrawn.

(4)

A person who sells, offers for sale, supplies, or offers for supply a declared medium risk article commits an offence and is liable on conviction to a level 2 penalty—

(a)

if, at the time of the sale, offer for sale, supply, or offer for supply,—

(i)

a supplier declaration of conformity for the article has not been made; or

(ii)

the article is not deemed to be approved by WorkSafe under regulation 83A; or

(iii)

the article is deemed to be approved by Worksafe under regulation 83A but all the terms and conditions of the deemed approval have not been complied with; or

(b)

if, within 10 days after being asked by WorkSafe to provide a test report or other document that shows how the article complies with the relevant standard, the person fails to provide a copy of that report or document; or

(c)

if, within 10 days after being asked by WorkSafe or a purchaser or potential purchaser of a declared medium risk article (to which subclause (2)(a) applies) to provide a copy of the supplier declaration, the person fails to provide a copy of the declaration.

Compare: SR 1997/60 r 101A

Regulation 83(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 83(1): amended, on 10 November 2011, by regulation 34(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 83(2): replaced, on 1 February 2014, by clause 13(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 83(3)(c): revoked, on 10 November 2011, by regulation 34(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 83(3)(d): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 83(3A): inserted, on 1 July 2013, by regulation 12 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 83(3B): inserted, on 1 February 2014, by clause 13(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 83(4): substituted, on 10 November 2011, by regulation 34(3) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 83(4): amended, on 1 February 2014, by clause 13(3) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 83(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 83(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 83(4)(a): replaced, on 1 February 2014, by clause 13(4) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 83(4)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 83(4)(c): amended, on 1 February 2014, by clause 13(5) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 83(4)(c): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

83A Deemed approval by WorkSafe for sale of medium risk EESS products

(1)

A declared medium risk article is deemed to have WorkSafe’s approval if—

(a)

the article is a registered EESS product; and

(b)

the New Zealand manufacturer or importer is a registered EESS supplier in respect of that article.

(2)
WorkSafe may, by notice in the Gazette, specify conditions to which a deemed approval is subject.

(3)

WorkSafe may, by notice in the Gazette,—

(a)

vary or withdraw any deemed approval; or

(b)

vary or revoke any conditions, or specify additional conditions, to which the deemed approval is subject.

(4)
A notice given under subclause (2) or (3) takes effect on the seventh day after the date of notification.

Regulation 83A: inserted, on 1 February 2014, by clause 14 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

84 Declared high risk articles not to be sold unless approved

(1)
WorkSafe may, by notice in the Gazette, declare that particular low voltage or extra-low voltage fittings or appliances, or particular types or classes of low voltage or extra-low voltage fittings or appliances, are high risk fittings or appliances (in this regulation and regulations 85 and 86 called declared high risk articles).

(2)

A declared high risk article may not be sold, offered for sale, supplied, or offered for supply unless—

(a)

it is approved for sale by WorkSafe under regulation 85 and all conditions of the approval are complied with; or

(b)

it is deemed, under regulation 86, to be approved by WorkSafe, and all relevant terms and conditions of the deemed approval are complied with.

(3)

A person who sells, offers for sale, supplies, or offers for supply a declared high risk article commits an offence and is liable on conviction to a level 2 penalty if—

(a)

the article is not approved for sale under regulation 85; or

(b)

the article is approved for sale under regulation 85, or deemed to be approved under regulation 86 or 86A, but all relevant terms and conditions of the approval or deemed approval are not complied with.

Compare: SR 1997/60 r 101(1), (9)

Regulation 84(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 84(1): amended, on 10 November 2011, by regulation 35 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 84(2): amended, on 1 February 2014, by clause 15(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 84(2)(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 84(2)(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 84(3): amended, on 1 February 2014, by clause 15(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 84(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 84(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 84(3)(b): amended, on 1 February 2014, by clause 15(3) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

85 Approval by WorkSafe for sale of declared high risk articles

(1)
Any person may apply to WorkSafe for approval to sell a declared high risk article by applying in a form prescribed by WorkSafe and paying the prescribed fee set out in Schedule 5.

(2)
WorkSafe may refer the application to an experienced person for advice on compliance by the declared high risk article with electrical safety requirements.

(3)
WorkSafe must notify the applicant in writing of his or her decision and, if the application is approved, must notify the applicant of any conditions of the approval imposed by WorkSafe.

(4)

WorkSafe may, on giving 10 days’ notice in writing to the applicant,—

(a)

vary or withdraw the approval; or

(b)

vary or revoke any condition, or specify any additional conditions, to which the approval is subject.

Compare: SR 1997/60 r 101(2)–(8)

Regulation 85 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 85(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 85(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 85(3): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 85(4): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

86 Deemed approval by WorkSafe for sale of declared high risk articles

(1)

A declared high risk article is deemed to have WorkSafe’s approval if the article—

(a)

is approved or certified by an organisation or agency, or under a programme or regime, recognised by WorkSafe under subclause (2); and

(b)

complies, as required, with any terms or conditions of the approval or certification.

(2)
WorkSafe may, by notice in the Gazette, recognise an organisation or agency, or a programme or regime of compliance, for the purposes of subclause (1).

(3)
WorkSafe may, by notice in the Gazette, specify conditions to which a deemed approval is subject.

(4)

WorkSafe may, by notice in the Gazette,—

(a)

vary or withdraw any deemed approval; or

(b)

vary or revoke any conditions, or specify additional conditions, to which the deemed approval is subject.

(5)
A notice given under subclause (4) takes effect on the seventh day after the date of notification.

Compare: 1997/60 r 101(6)(b), (7)(b), (8), (9), (10)

Regulation 86 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 86(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 86(1)(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 86(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 86(3): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 86(4): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

86A Deemed approval by WorkSafe for sale of high risk EESS products

(1)

A declared high risk article is deemed to have WorkSafe’s approval if—

(a)

the article is a registered EESS product; and

(b)

the New Zealand manufacturer or importer is a registered EESS supplier in respect of that article.

(2)
WorkSafe may, by notice in the Gazette, specify conditions to which a deemed approval is subject.

(3)

WorkSafe may, by notice in the Gazette,—

(a)

vary or withdraw any deemed approval; or

(b)

vary or revoke any conditions, or specify additional conditions, to which the deemed approval is subject.

(4)
A notice given under subclause (2) or (3) takes effect on the seventh day after the date of notification.

Regulation 86A: inserted, on 1 February 2014, by clause 16 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

87 Prohibitions relating to fittings and appliances

(1)
If WorkSafe believes on reasonable grounds that a fitting or appliance is, or may be, electrically unsafe, WorkSafe may prohibit all or any of the following activities in relation to the fitting or appliance: its manufacture, importation, sale (including an offer to sell), or use (including installation).

(2)
If a fitting or appliance is imported into New Zealand in purported compliance with the Conformity Cooperation Agreement but it does not in fact comply with the Conformity Cooperation Agreement, WorkSafe may prohibit all or any of the following activities in relation to the fitting or appliance: its importation, sale (including an offer to sell), installation, or use (including installation).

(3)

A prohibition under this regulation—

(a)

must be made by notice in the Gazette; and

(b)

takes effect on and from the date specified for the purpose in the notice, which must be later than the date of publication of the notice in the Gazette; and

(c)

must adequately describe the fitting or appliance, or class of fitting or appliance, being prohibited; and

(d)

must give brief reasons for the belief that the fitting or appliance,—

(i)

if subclause (1) applies, is or may be electrically unsafe; or

(ii)

if subclause (2) applies, does not comply with the Conformity Cooperation Agreement.

(4)
If WorkSafe knows a New Zealand address of the manufacturer, importer, seller, or user concerned, WorkSafe must give notice of the prohibition to that person before the date specified in the notice in the Gazette as the date on which the prohibition takes effect.

(5)
A prohibition made under this regulation may be varied or revoked in the same way that it may be made.

(6)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she manufactures, imports, sells (including offering to sell), or uses (including installs) any fitting or appliance contrary to a prohibition made under this regulation.

Compare: SR 1997/60 r 102

Regulation 87(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 87(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 87(4): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 87(6): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 87(6): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

88 Supply of electricity to hand-held appliances

(1)

Hand-held appliances must be connected to a supply of electricity by—

(a)

a plug of suitable capacity; or

(b)

a cord connector of suitable capacity; or

(c)

a permanent connection.

(2)
The voltage of electricity supplied to a hand-held appliance must not exceed 250 AC volts to earth.

(3)
A person commits an offence and is liable on conviction to a level 2 penalty if he or she installs or uses a hand-held appliance when either subclause (1) or (2) is not complied with.

Compare: SR 1997/60 rr 77(1), (2)

Regulation 88(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 88(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

89 Use of hand-held appliances in certain high-risk situations

(1)

If a hand-held appliance (including a hand-held lighting appliance) is used by a person who is partly or wholly immersed in a conducting substance, or who is in a substantially conductive situation, the appliance must be—

(a)

fixed-wired and connected through a continuous flexible cord to a supply of electricity from a source isolated from earth with a voltage between conductors not exceeding 250 AC volts; or

(b)

supplied with electricity from a safety extra-low voltage source; or

(c)

double-insulated and supplied with electricity through an RCD that provides protection against electric shock.

(2)

If a hand-held appliance (including a hand-held lighting appliance) is used indoors in a situation that is normally damp, or is used outdoors, or in a building or structure under construction, the appliance must be—

(a)

fixed-wired and connected through a continuous flexible cord to a supply of electricity from a source isolated from earth with a voltage between conductors not exceeding 250 AC volts; or

(b)

supplied with electricity from a safety extra-low voltage source; or

(c)

supplied with electricity from a monitored earth circuit where the supply to the appliance is automatically interrupted if the earth to the appliance is broken or detached; or

(d)

supplied with electricity from a source connected to earth so that the voltage to earth will not be greater than 55 AC volts; or

(e)

supplied with electricity through an RCD that provides protection against electric shock; or

(f)

supplied with electricity from a source isolated from earth with a voltage between conductors not exceeding 250 AC volts; or

(g)

double-insulated.

(3)

A person commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

uses a hand-held appliance in breach of subclause (1) or (2); or

(b)

allows another person to use a hand-held appliance in a manner that breaches subclause (1) or (2); or

(c)

supervises the use of a hand-held appliance and that use breaches the requirements of subclause (1) or (2).

Compare: SR 1997/60 r 77(3), (4)

Regulation 89 heading: amended, on 1 February 2014, by clause 17(1) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 89(1): amended, on 1 February 2014, by clause 17(2) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 89(2): amended, on 1 February 2014, by clause 17(3) of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 89(2)(c): amended, on 10 November 2011, by regulation 36(1)(a) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 89(2)(c): amended, on 10 November 2011, by regulation 36(1)(b) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 89(3): substituted, on 10 November 2011, by regulation 36(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 89(3): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 89(3): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

89A Use of hand-held appliances in cramped spaces

(1)

If a hand-held appliance (including a hand-held lighting appliance) is used by a person who is in a space where physical movement is severely restricted or obstructed (including, if appropriate, in a motor vehicle workshop), the appliance must be—

(a)

fixed-wired and connected through a continuous flexible cord to a supply of electricity from a source isolated from earth with a voltage between conductors not exceeding 250 AC volts; or

(b)

supplied with electricity from a safety extra-low voltage source; or

(c)

double-insulated and supplied with electricity through an RCD that provides protection against electric shock.

(2)

A person commits an offence and is liable on conviction to a level 2 penalty if the person—

(a)

uses a hand-held appliance in breach of subclause (1); or

(b)

allows another person to use a hand-held appliance in a manner that breaches subclause (1); or

(c)

supervises the use of a hand-held appliance and that use breaches the requirements of subclause (1).

Regulation 89A: inserted, on 1 February 2014, by clause 18 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Testing appliances

90 Testing appliances after certain work done on them

(1)

A person must comply with subclause (2) before releasing an appliance from his or her control if the person has—

(a)

done any prescribed electrical work on the appliance; or

(b)

done any work on the appliance that may affect its electrical safety.

(2)

The person must test the appliance and either—

(a)

confirm that it is electrically safe in accordance with the following:

(i)

in the case of prescribed electrical work done in reliance on section 80 of the Act (exemption for maintenance of domestic appliances): ECP 50:

(ii)

in the case of low or extra-low voltage electrical medical devices: AS/NZS 3551:

(iii)

in the case of all other low or extra-low voltage appliances: AS/NZS 5762; or

(b)

if the appliance is electrically unsafe, adequately disable and mark it.

(3)
A person is deemed to comply with subclause (2)(b) if he or she disables and marks the appliance in accordance with AS/NZS 4701.

(4)
A person who fails to comply with subclause (2) commits an offence and is liable on conviction to a level 2 penalty.

Compare: SR 1997/60 r 38

Regulation 90(2)(a): amended, on 10 November 2011, by regulation 37 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 90(4): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 90(4): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Periodic assessment of electrical medical devices

Heading: replaced, on 1 February 2014, by clause 19 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

91 Periodic assessment of electrical medical devices

(1)
The owner of an electrical medical device must ensure that the device is periodically assessed in accordance with AS/NZS 3551 to determine whether it is electrically safe and complies with that standard.

(2)
The results of each periodic assessment must be recorded in accordance with AS/NZS 3551, and the owner must retain the record.

(3)

The person who completes the assessment must—

(a)

give the record of the assessment to the person who requested the assessment; and

(b)

keep a copy of it for at least 3 years, or send a copy to WorkSafe.

(4)
A person who owns an electrical medical device commits an offence and is liable on conviction to a level 1 penalty if the device is not assessed in accordance with subclause (1).

(5)
A person who owns or operates an electrical medical device commits an offence and is liable on conviction to a level 1 penalty if the person uses, or allows another person to use, the electrical medical device knowing that it has not been assessed as required by this regulation, unless, because of an emergency, use of the device is justified in the circumstances.

Compare: SR 1997/60 r 46(2)(c), (d), (3), (4)
Regulation 91: replaced, on 1 February 2014, by clause 19 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Part 7 Registration, employer licences, and Board provisions

What supervised persons and trainees may do

92 Limits of work that supervised persons may do

(1)

For the purposes of section 76(a) of the Act, the prescribed electrical work that a person who is under supervision may do, or assist in doing, is any work that is within the scope of work that the person’s supervisor is authorised to do, except that a person under supervision may not—

(a)

connect or disconnect a supply of electricity to works or an installation or appliance; or

(b)

do any certification or inspection of works, installations, fittings, or appliances.

(2)
Despite section 76(c) of the Act, a supervised person may test works, installations, fittings, or appliances that are connected to a power supply provided there is no direct access to live parts at a voltage above extra-low voltage.

93 Limits of work that trainees may do


For the purposes of section 77(1)(a) of the Act, the prescribed electrical work that a trainee may do, or assist in doing, is any work that is within the particular class of work for which the trainee is seeking registration, and that is within the scope of work that the trainee’s supervisor is authorised to do.

Compare: SR 1997/60 r 23

Employer licences

94 Requirements for system of operation of holders of employer licences

(1)

For the purposes of section 115(1)(a) of the Act, the requirements for the system of operation that must be maintained by the holder of an employer licence are that the holder—

(a)

identifies the prescribed electrical work (identified prescribed electrical work) that will be undertaken under the licence; and

(b)

identifies the skills and training required in order to carry out each kind of identified prescribed electrical work; and

(c)

has in place procedures for each of the following:

(i)

carrying out, supervising, and monitoring the identified prescribed electrical work:

(ii)

investigating injuries caused to persons, and damage caused to property, as a result of carrying out any identified prescribed electrical work:

(iii)

taking action to prevent, and in response to, injuries to persons or damage to property that results from carrying out the identified prescribed electrical work; and

(d)

maintains a manual that sets out the matters listed in subclause (2).

(2)

The manual referred to in subclause (1)(d) must set out—

(a)

all the matters referred to in subclause (1)(a) to (c); and

(b)

the names of every employee of the holder who is to carry out identified prescribed electrical work, along with a description of the identified prescribed electrical work that each employee is trained, and has the skills, to do; and

(c)

the location and address of each place of work from which the holder of the licence operates, and that is intended to be covered by the licence; and

(d)

a contact person for the licence, who must be an employee of the holder, identified by name or position.

Compare: SR 1997/60 r 16

95 Certification of system of operation

(1)

For the purposes of section 116(1) of the Act, an approved person may certify a system of operation if the approved person is satisfied that—

(a)

the system of operation is sufficient to ensure that the employer’s employees who do, or assist in doing, prescribed electrical work—

(i)

are competent to carry out the range of work for which they are employed; and

(ii)

receive the supervision and training necessary to ensure that the work is carried out safely and competently, and that the work complies with the requirements of the Act and these regulations; and

(b)

the employer has and maintains a manual referred to in regulation 94(1)(d) that complies with regulation 94(2); and

(c)

the procedures referred to in regulation 94(1)(c) are being followed.

(2)
The form of the certificate may be prescribed by the Board.

96 Approved persons

(1)

For the purposes of section 116(3) of the Act, the class of persons designated as approved persons is the class of persons whose names appear on a list, maintained by the Board, of persons who—

(a)

are accredited auditors; and

(b)

satisfy the Board that they are capable of certifying whether a system of operation complies with section 115(1)(a) and (b) of the Act.

(2)
The Board may remove from the list the name of any person who the Board is satisfied does not meet the requirements of subclause (1) and must give written notice to the person concerned.

(3)
Until the date that is 6 months after the date on which this regulation comes into force, the list must include the name of every person who applies (whether before or after this regulation comes into force) to have his or her name on the list and who satisfies paragraph (a) of subclause (1); but after that date, the list may contain only the names of people who satisfy both paragraph (a) and paragraph (b) of subclause (1).

Regulation 96(1): amended, on 10 November 2011, by regulation 38(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 96(1)(a): substituted, on 10 November 2011, by regulation 38(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

Board provisions

97 Search criteria for register of electrical workers



The register of electrical workers may be searched by reference to any, or any combination, of the following criteria:

(a)

the name, or any part of the name, of a person:

(b)

the name of a town or city:

(c)

a New Zealand post code:

(d)

the name of a company or body corporate:

(e)

a unique identifier issued to an electrical worker or employer licence holder by the Registrar appointed by the Board:

(f)

a licensing class.

98 Form of complaints


Every complaint made to the Board under section 144 of the Act must be made in writing and be addressed to the Registrar appointed by the Board.

99 Fees payable to Board

(1)
The fees specified in Schedule 6 are payable to the Board in respect of the matters specified in that schedule.

(2)
The fees specified in Schedule 6 are inclusive of goods and services tax.

(3)

The Board may waive, refund, or remit the whole or any part of a fee that would otherwise be payable to it in any of the following circumstances:

(a)

the application is for a practising licence that is issued for a period of less than 1 year:

(b)

a fee is overpaid or paid in error:

(c)

a person paying a fee for a particular type of application has, within the previous 12 months, paid a fee for the same type of application:

(d)

in the case of an applicant for a practising licence, the cost of carrying out the Board’s obligations under section 149(k) of the Act in respect of the class of work (or category of the class of work) for which the applicant is registered does not justify charging the full fee for the application:

(e)

a certificate of compliance is sought within 3 months before the Electricity (Safety) Amendment Regulations 2012 come into force.

Compare: SR 1997/60 r 109
Regulation 99(3)(e): inserted, on 1 July 2013, by regulation 13 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Part 8 Working practices

100 Safety responsibilities of person who carries out work

(1)

A person who carries out any prescribed electrical work, or any work referred to in clause (2)(e) to (h) of Schedule 1, must take all practicable steps,—

(a)

before beginning the work, to check that any associated equipment and personal protective equipment to be used by that person is in good order and condition, and is safe for its intended use; and

(b)

to follow the procedures approved by the employer (if any) for the work to be carried out; and

(c)

to use the associated equipment and the personal protective equipment provided in a competent manner; and

(d)

to comply with AS/NZS 4836 or the certified design for all electrical work carried out on electrical equipment operating at low or extra-low voltage.

(2)
The responsibilities set out in this regulation of a person carrying out work are in addition to, and do not limit, the responsibilities of that person under the Health and Safety in Employment Act 1992.

Compare: SR 1997/60 r 36

Regulation 100(1)(c): amended, on 31 December 2013, by regulation 28(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 100(1)(d): inserted, on 31 December 2013, by regulation 28(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

101 Responsibility of employers for safety of employees

(1)
An employer who employs a person to carry out any prescribed electrical work, or any work referred to in clause (2)(e) to (h) of Schedule 1, must take all practicable steps to ensure the safety of the employee while carrying out the work, and must take the steps described in subclauses (2) and (3) in particular.

(2)

The employer must take all practicable steps to—

(a)

provide safe working procedures for employees to follow when carrying out the work; and

(b)

ensure that any associated equipment and personal protective equipment used by an employee is arranged, designed, made, tested, inspected, and maintained so that it is safe for the employee to use.

(3)

The employer must take all practicable steps to ensure that the employee who carries out the work—

(a)

has adequate knowledge and experience of the type of work being carried out; and

(b)

has been adequately trained in the safe use of the associated equipment, the personal protective equipment, and the procedures for carrying out the work; and

(c)

immediately before the start of the work, checks that the associated equipment and personal protective equipment is in good order and condition; and

(d)

uses the equipment and the procedures that the employer has approved for the work.

(4)
Subclause (3)(a) does not apply if the employee is in training and the employer ensures that the employee is adequately supervised to ensure the safety of the employee.

(5)
The responsibilities of the employer set out in this regulation are in addition to, and do not limit, the responsibilities of the employer under the Health and Safety in Employment Act 1992.

Compare: SR 1997/60 r 35

102 Work on live high voltage overhead electric lines


Work on live high voltage overhead electric lines must be carried out in accordance with ECP 46.

Compare: 1997/60 r 28

103 Work on live conductors of low voltage overhead electric lines in installations

(1)

This regulation applies when a person is working on live conductors of low voltage overhead electric lines in installations—

(a)

that have exposed live metal; or

(b)

if there is a likelihood of accidental contact with any other conductor or bare earthed metal.

(2)
The person may carry out the work only if he or she uses the associated equipment and personal protective equipment that is necesssary to ensure his or her safety and the safety of other persons in the vicinity of the work.

Compare: SR 1997/60 r 29

103A Work on or near bare live conductors in alluvial mining operations, mining operations, and quarrying operations



Every alluvial mine operator, mine operator, and quarry operator must ensure that no mine worker carries out work on a bare live conductor, or so near a bare live conductor as to make it likely that the conductor will be a cause or source of harm to any person, unless—

(a)

it is not reasonable in any circumstances for the conductor to be isolated and earthed; and

(b)

it is reasonable in all the circumstances for the mine worker to work on or near the conductor while it is live; and

(c)

all suitable precautions (including the use of suitable protective equipment) are taken to prevent harm or injury to any person.

Regulation 103A: inserted, on 31 December 2013, by regulation 29 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

104 Work on isolated high voltage fittings

(1)

This regulation applies while a person is working on high voltage fittings that are—

(a)

isolated from a supply of electricity; or

(b)

disconnected from a supply of electricity, if there is a significant risk that the person may suffer serious harm from an electric shock in the event of the fittings becoming live other than by way of reconnection of the supply of electricity.

(2)
The person doing the work must ensure that the fittings are earthed before the work is commenced and that they remain earthed until the work is completed.

(3)

The person doing the work need not comply with subclause (2) if—

(a)

the person carries out the work using the procedures approved by the person’s employer (if any); and

(b)

the person uses appropriate associated equipment.

(4)
The fittings must be sufficiently earthed to protect any person working on them from exposure to a significant risk of electric shock or other injury.

(5)
A temporary earthing device applied to a fitting must be adequate to carry any short circuit current that may flow.

(6)
A person may remove an earthing device to test a fitting, but must take all practicable steps to ensure his or her own safety and the safety of others in the vicinity.

Compare: SR 1997/60 r 32
Regulation 104: substituted, on 10 November 2011, by regulation 39 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

105 Work stringing additional conductors between poles or other supports

(1)
This regulation applies to work that consists of stringing additional conductors between poles or other supports where the poles or other supports already hold conductors.

(2)

The person carrying out work to which this regulation applies must ensure that—

(a)

the existing conductors held by the poles or other supports are isolated and earthed before the work is commenced, and that they remain isolated and earthed until the work is completed; or

(b)

the additional conductors are earthed before the work is commenced, and—

(i)

they remain earthed until the work is completed; and

(ii)

the appropriate associated equipment referred to in regulation 101(2)(b) is used while carrying out the work.

(3)
No person may be on a cross-arm of a pole or other support that carries conductors, other than the cross-arm of a tower or similar structure, while additional conductors are being pulled up or tensioned.

Compare: SR 1997/60 r 31
Regulation 105(3): replaced, on 1 February 2014, by clause 20 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

106 Notices when working on works and installations

(1)
A person carrying out work on works or installations that are isolated from a power supply must, if there is a risk of unintentional enlivening of the works or installations, ensure that suitable notices warning against enlivening are fixed at a point where the power supply may be connected or restored.

(2)
If works or installations have a locking facility for isolating them from the power supply, then any person isolating the works or installations must use that facility to lock the isolation.

Compare: SR 1997/60 r 34(1), (2)
Regulation 106: substituted, on 10 November 2011, by regulation 41 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

107 Offences relating to Part 8


A person commits an offence and is liable on conviction to a level 2 penalty if he or she fails to take all practicable steps to comply with the requirements of any of regulations 100 to 106.

Compare: SR 1997/60 r 51(a)

Regulation 107: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 107: amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Part 9 Miscellaneous

WorkSafe’s powers and obligations

Heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

108 WorkSafe’s power to prescribe forms, etc

(1)
WorkSafe may prescribe any form referred to in these regulations as a form prescribed by WorkSafe.

(2)
WorkSafe may prescribe the form for warrant of electrical fitness stickers for the purpose of regulation 78(3)(c).

Regulation 108 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 108(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 108(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

109 WorkSafe’s power to exempt from requirements

(1)

Worksafe may, if it is satisfied that safety will be ensured despite the exemption and that the extent of the exemption is not broader than is reasonably necessary to address the matters that gave rise to the exemption, exempt specific works, installations, fittings, appliances, associated equipment, persons, or things from any requirement imposed by or under all or any of the following:

(a)

in Part 3, regulations 27(2), 28, 29, 31, and 33:

(b)

in Part 4, regulations 38 and 44:

(c)

in Part 5, regulations 57, 59, 60, 61AA, 74, 74E, and 74G:

(d)

any provision in Part 5A:

(e)

in Part 6, regulations 88, 89, and 91:

(f)

any provision in Schedule 8.

(2)

An application for exemption must—

(a)

specify the precise exemption sought and the reason; and

(b)

demonstrate how safety, including electrical safety, will be ensured if the exemption is granted; and

(c)

be made on a form prescribed by WorkSafe; and

(d)

be accompanied by the fee prescribed in Schedule 5.

(3)

Every exemption—

(a)

must be in writing; and

(b)

must specify the period for which it applies; and

(c)

may impose conditions on the exemption.

(4)

WorkSafe may amend or revoke an exemption—

(a)

if the holder of the exemption asks; or

(b)

in order to prevent potential serious harm to any person or significant damage to property, but only after giving the holder at least 20 working days’ notice of the proposed amendment or revocation; or

(c)

if WorkSafe is satisfied that the holder is not complying, or has not complied, with any conditions on the exemption, in which case the amendment or revocation has effect on the date of, or any later date specified in, WorkSafe’s notice.

(5)

WorkSafe must give notice of an exemption, and any amendment or revocation of an exemption,—

(a)

to the applicant; and

(b)

if the exemption, amendment, or revocation will affect a wider range of people than just the applicant, by notice in the Gazette.

Compare: SR 1997/60 r 103

Regulation 109 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 109(1): replaced, on 31 December 2013, by regulation 30(1) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 109(2)(b): amended, on 10 November 2011, by regulation 42 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Regulation 109(2)(c): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 109(4): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 109(4)(c): amended, on 31 December 2013, by regulation 30(2) of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).
Regulation 109(4)(c): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 109(5): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

110 Issuing urgent instructions, orders, or requirements

(1)
In any case of urgency, WorkSafe may issue instructions, orders, or requirements for securing the protection of persons from injury caused, directly or indirectly, by electricity.

(2)

Any instruction, order, or requirement must be,—

(a)

if the instruction, order, or requirement is specific to a particular person or persons, by notice in writing to that person or persons; or

(b)

if the instruction, order, or requirement is of more general application, by notice in the Gazette.

(3)
No instruction, order, or requirement issued under this regulation may remain in force for more than 6 months from its date of issue, whether or not it is amended after its issue.

(4)
WorkSafe may amend or revoke any instruction, order, or requirement in the same way in which it was originally issued.

(5)
A person who fails to comply with an instruction, order, or requirement issued under this regulation commits an offence and is liable on conviction to a level 2 penalty.

Compare: 1997/60 r 105

Regulation 110(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 110(4): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 110(5): amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).
Regulation 110(5): amended, on 1 July 2013, by regulation 7(1) of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Miscellaneous

111 Gazette notices to be published on Internet site



WorkSafe must ensure that a copy of every notice that is published or given in the Gazette under these regulations—

(a)

is published at the same time as, or as soon as practicable after, it is published in the Gazette on an Internet site maintained by or on behalf of WorkSafe; and

(b)

contains a statement that identifies the Internet site on which a copy of the notice may be found.

Regulation 111: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 111(a): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

111A Consolidation of certificates

(1)

The following certificates relating to an installation may be consolidated in a single document:

(a)

any certificates of compliance (including any associated records of inspection) for prescribed electrical work done on all or any part of the installation:

(b)

any electrical safety certificates for the whole or any part of the installation.

(2)

Where certificates are consolidated—

(a)

if any of the information required by these regulations for each certificate is the same, that information need not be repeated in the consolidated document; and

(b)

the authentication mark needs to be included in or on the document only once.

Regulation 111A: inserted, on 1 July 2013, by regulation 15 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

111B Authentication mark



The authentication mark required by regulations 66, 72, and 74A and clause 11 of Schedule 8 to be included in or on a certificate of compliance, a record of inspection, and an electrical safety certificate must—

(a)

be in the form illustrated in Schedule 7; and

(b)

be of a size, and be placed, so that it is easily visible on the front, or near the top, of the certificate.

Regulation 111B: inserted, on 1 July 2013, by regulation 15 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 111B: amended, on 1 February 2014, by clause 21 of Schedule 1 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

111C Offences relating to application of authentication mark



A person commits an offence and is liable on conviction to a level 2 penalty if he or she includes in or on a document a mark in the form illustrated in Schedule 7 and the document—

(a)

is not, but could reasonably be mistaken for being, a certificate of compliance or an electrical safety certificate; or

(b)

is, or could reasonably be mistaken for being, advertising material.

Regulation 111C: inserted, on 1 July 2013, by regulation 15 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 111C: amended, on 4 October 2013, by regulation 3(2) of the Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409).

112 Details that must be provided in reports of accidents

(1)

A person who is required to notify WorkSafe of an accident, in accordance with section 16 of the Act, must give a full report in writing that sets out the following matters:

(a)

the name and contact details of the person giving notice (which should include, if possible, telephone and fax numbers, and an email address):

(b)

the place, date, and time of the accident:

(c)

a complete description of the accident:

(d)

a description of any injuries, damage, or losses resulting from the accident:

(e)

where known, the names and contact information of any witness, investigator at the scene, or other person who could provide useful information about the accident:

(f)

possible causative factors (if any are known):

(g)

any resuscitation applied, including the method, the length of time applied, the reason for discontinuing, and the name of the person who applied the resuscitation:

(h)

any associated equipment involved, including the type, whether it operated correctly, and any reasons why it did not operate correctly:

(i)

the condition of any associated equipment involved, including its age:

(j)

where known, the name, age, sex, occupation, and residential address of the victim.

(2)
An accident may initially be notified to WorkSafe by telephone, fax, email, or any other electronic means, as long as the full written report is sent to WorkSafe within 2 weeks after that initial notification.

(3)
The full written report may be sent to WorkSafe by post, fax, email, or any other electronic means.

Compare: 1997/60 r 106

Regulation 112(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 112(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 112(3): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

Recording certificate details

Heading: inserted, on 1 July 2013, by regulation 16 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

112A Database for recording certificate details on Internet site



WorkSafe must ensure that there is included on an Internet site, maintained by or on behalf of WorkSafe, a database that records details of the following, in a manner that enables the information to be accessible in accordance with regulation 112B:

(a)

all certificates of compliance (including records of inspection) given for high-risk prescribed electrical work:

(b)

any other certificates as determined by WorkSafe.

Regulation 112A: inserted, on 1 July 2013, by regulation 16 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 112A: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 112A(b): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

112B Access to database

(1)
WorkSafe must ensure that the database referred to in regulation 112A is accessible to members of the public at all reasonable times.

(2)
The database must be able to be searched by members of the public only by reference to the location (as defined in regulation 74I) of the relevant installation.

(3)
However, WorkSafe must ensure that WorkSafe and the Board are able to search the database by reference to whatever search criteria WorkSafe determines will best enable WorkSafe and the Board to fulfil their functions under the Act and these regulations.

Regulation 112B: inserted, on 1 July 2013, by regulation 16 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).
Regulation 112B(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 112B(3): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

Transitional provisions

113 Existing and in-process works, installations, fittings, and appliances

(1)

This regulation applies to works, installations, fittings, and appliances that, on 1 April 2010, were—

(a)

installed, for sale, or in use in New Zealand; or

(b)

under construction or being installed in New Zealand; or

(c)

in transit to New Zealand; or

(d)

the subject of an irrevocable purchasing order by a person in New Zealand.

(2)

Despite anything to the contrary in these regulations, the works, installations, fittings, and appliances—

(a)

may continue to be constructed, installed, sold, or used provided that—

(i)

they are not electrically unsafe; and

(ii)

they complied immediately before 1 April 2010 with the requirements of the Electricity Regulations 1997; and

(iii)

they continue to comply, as a minimum, with the requirements of the Electricity Regulations 1997 as in force immediately before their revocation by these regulations; and

(b)

may, until 1 April 2012, be tested, certified, or inspected in accordance with—

(i)

the Electricity Regulations 1997 as in force immediately before 1 April 2010; or

(ii)

these regulations.

Compare: SR 1997/60 r 68
Regulation 113: substituted, on 10 November 2011, by regulation 43 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

114 Declared articles under previous regulations

(1)
Every fitting or appliance that, immediately before these regulations come into force, is a declared article under regulation 101 of the Electricity Regulations 1997 is a declared high risk article for the purpose of regulation 84 of these regulations, and regulation 84 applies accordingly.

(2)
Every approval, deemed approval, and notice given under regulation 101 of the Electricity Regulations 1997 continues in force as if it had been given under regulation 85 or 86 (as appropriate) of these regulations.

(3)
An application made under regulation 101 of the Electricity Regulations 1997 is, after these regulations come into force, to be treated as if the application were made under regulation 85 of these regulations.

115 Specified fittings and appliances under previous regulations

(1)
Every fitting or appliance that, immediately before these regulations come into force, is the subject of a specification by the Secretary under regulation 101A of the Electricity Regulations 1997 (a specified fitting or appliance) is a declared medium risk article for the purpose of regulation 83 of these regulations, and regulation 83 applies accordingly.

(2)
Every declaration that is made before these regulations come into force in respect of a specified fitting or appliance, and that complies with regulation 101A of the Electricity Regulations 1997, is to be treated as if it is a supplier declaration of conformity that complies with regulation 83 of these regulations.

116 Secretary’s exemptions


An exemption given by the Secretary under regulation 103 of the Electricity Regulations 1997, and still in force immediately before these regulations come into force, continues in force after these regulations come into force as if it had been given under regulation 109 of these regulations on the date on which it was given.

117 Warrants of electrical fitness


A warrant of electrical fitness issued under the Electricity Regulations 1997 is to be treated as if the warrant had been issued, on the date on which it was issued, under regulation 78 of these regulations.

118 Certificates of compliance


The revocation of the Electricity Regulations 1997 does not affect the validity of any certificate of compliance issued under those regulations.

Transitional provision relating to 2011 amendments

Heading: inserted, on 10 November 2011, by regulation 44 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

118A Transitional provision relating to Electricity (Safety) Amendment Regulations 2011

(1)
In this regulation, amendment date means 10 November 2011 (which is the date on which the Electricity (Safety) Amendment Regulations 2011 come into force).

Existing works, installations, fittings, and appliances

(2)

Subclause (3) applies to works, installations, fittings, and appliances that, immediately before the amendment date, are—

(a)

installed, for sale, or in use in New Zealand; or

(b)

under construction or being installed in New Zealand; or

(c)

in transit to New Zealand; or

(d)

the subject of an irrevocable purchasing order by a person in New Zealand.

(3)

Despite anything to the contrary in these regulations, the works, installations, fittings, and appliances may continue to be constructed, installed, sold, or used provided that—

(a)

they are not electrically unsafe; and

(b)

they complied immediately before the amendment date, and continue to comply, with the requirements of these regulations as in force immediately before the amendment date.

Existing declarations of conformity

(4)

Subclause (5) applies to a declaration of conformity that—

(a)

is made before the amendment date; and

(b)

complies with regulation 83 as in force immediately before the amendment date.

(5)
The declaration of conformity must be treated as if it complies with regulation 83 as amended by the Electricity (Safety) Amendment Regulations 2011.

Six-month transition period for compliance with Amendment A of AS/NZS 3000

(6)

Despite regulation 4(4), until the close of the date that is 6 months after the amendment date, any reference in these regulations to AS/NZS 3000 must be treated as if it is a reference to—

(a)

AS/NZS 3000:2007: Electrical installations (known as the Australian/New Zealand Wiring Rules): including Amendment 1; or

(b)

AS/NZS 3000:2007: Electrical installations (known as the Australian/New Zealand Wiring Rules): including Amendment 1 and Amendment A.

Regulation 118A: inserted, on 10 November 2011, by regulation 44 of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

Transitional provision relating to 2012 amendments

Heading: inserted, on 31 December 2013, by regulation 31 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

118B Transitional provision relating to Electricity (Safety) Amendment Regulations 2012

(1)

This regulation applies to works, installations, fittings, and appliances that, immediately before 1 July 2013,—

(a)

were installed, for sale, or in use in New Zealand; or

(b)

were under construction or being installed in New Zealand; or

(c)

were in transit to New Zealand; or

(d)

were the subject of an irrevocable purchasing order by a person in New Zealand.

(2)

Despite anything to the contrary in these regulations, the works, installations, fittings, and appliances may continue to be constructed, installed, sold, or used provided that—

(a)

they are not electrically unsafe; and

(b)

they complied immediately before 1 July 2013 with the requirements of these regulations as in force immediately before 1 July 2013; and

(c)

they continue to comply with the requirements of these regulations as in force immediately before 1 July 2013.

Regulation 118B: inserted, on 31 December 2013, by regulation 31 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Transitional and savings provisions relating to 2013 amendments

Heading: inserted, on 31 December 2013, by regulation 31 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

118C Savings provision for existing mining electrical equipment in relation to Electricity (Safety) Amendment Regulations 2013

(1)

This regulation applies to mining electrical equipment and conductors supplying that equipment that, immediately before 31 December 2013,—

(a)

were installed or in use in New Zealand; or

(b)

were under construction or being installed in New Zealand; or

(c)

were in transit to New Zealand; or

(d)

were the subject of an irrevocable purchasing order by a person in New Zealand.

(2)

Despite anything to the contrary in these regulations, that mining electrical equipment and those conductors may continue to be constructed, installed, or used provided that—

(a)

they are not electrically unsafe; and

(b)

they complied immediately before 31 December 2013 with the requirements of these regulations as in force immediately before 31 December 2013; and

(c)

they continue to comply with the requirements of these regulations as in force immediately before 31 December 2013.

Regulation 118C: inserted, on 31 December 2013, by regulation 31 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

118D Transitional provision relating to Electricity (Safety) Amendment Regulations 2013

(1)
This regulation applies to alluvial mining operations, mining operations, and quarrying operations in New Zealand that were in operation or suspended immediately before 31 December 2013 (existing operations).

(2)

The following provisions do not apply to existing operations until 1 January 2015, unless that operation is abandonned,:

(a)

regulation 24B:

(b)

regulation 78G:

(c)

regulation 78K:

(d)

clause 4 of Schedule 8.

Regulation 118D: inserted, on 31 December 2013, by regulation 31 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Arbitrators

119 Arbitrators

(1)
WorkSafe may from time to time, on request, appoint arbitrators for the purpose of providing opinions on disputes over whether the technical requirements of these regulations have been complied with.

(2)
The term of appointment of any arbitrator is 2 years, unless otherwise agreed between the appointee and WorkSafe.

(3)
The procedure to be used by the arbitrator in carrying out the functions referred to in subclause (1) may be determined by the arbitrator.

(4)
Arbitrators may be paid remuneration by way of fees or allowances, and travelling allowances and expenses, in accordance with the Fees and Travelling Allowances Act 1951, and the provisions of that Act apply accordingly as if an arbitrator were a member of a statutory Board.

(5)
The person who requested the arbitration must pay the prescribed fee, as set out in Schedule 5, at the completion of the arbitration.

Compare: SR 1997/60 r 99

Regulation 119(1): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Regulation 119(2): amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

Revocation and amendments

120 Revocation of Electricity Regulations 1997


The Electricity Regulations 1997 (SR 1997/60) are revoked.

121 Amendment to Electricity (Hazards from Trees) Regulations 2003

(1)
This regulation amends the Electricity (Hazards from Trees) Regulations 2003.

(2)
Regulation 39 is revoked.

122 Amendments to Electricity (China Free Trade Agreement) Regulations 2008

(1)
This regulation amends the Electricity (China Free Trade Agreement) Regulations 2008.

(2)
Regulation 7 is amended by omitting “and is liable on summary conviction to a fine not exceeding $10,000”.

(3)

Regulation 7 is amended by adding the following subclause as subclause (2):

(2)

A person who commits an offence against subclause (1) is liable on summary conviction to,—

(a)

in the case of a natural person, a fine not exceeding $10,000; or

(b)

in any other case, a fine not exceeding $50,000.

(4)
The Schedule is revoked.

Schedule 1 Prescribed electrical work

r 4(1)

1(1)

The following electrical work is prescribed electrical work, unless it is work described in clause 2:

(a)

the installation, connection, or maintenance of conductors used in works or installations:

(b)

the installation, connection, or maintenance of fittings where the fittings are connected, or intended to be connected, to conductors used in works or installations:

(c)

the connection or disconnection of fittings to or from a power supply, other than by means of a plug or pin inserted into a socket, or an appliance connector inserted into an appliance inlet:

(d)

the maintenance of appliances:

(e)

the testing of work described in paragraphs (a) to (d) that—

(i)

is not work described in clause (2); and

(ii)

is required by these regulations; and

(iii)

is carried out for the purpose of compliance with these regulations:

(f)

the certification of work described in paragraphs (a) to (d) that is not work described in clause 2:

(g)

the inspection of work described in paragraphs (a) to (d) that—

(i)

is not work described in clause (2); and

(ii)

is required by these regulations; and

(iii)

is carried out for the purpose of compliance with these regulations:

(h)

the supervision of any work described in paragraphs (a) to (d) that is not work described in clause 2.

(2)

The following electrical work is prescribed electrical work (regardless of whether it is work described in clause 2):

(a)

work done on bolted couplers and restrained couplers used or installed in a mining operation:

(b)

work done on installations, fittings, or appliances in an ERZ0 or ERZ1:

(c)

the connection, reconnection, or disconnection of bolted couplers and restrained couplers used or installed in a mining operation.

Schedule 1 clause 1(1)(a): amended, on 10 November 2011, by regulation 45(1) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 1(1)(b): substituted, on 10 November 2011, by regulation 45(2) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 1(1)(e): substituted, on 10 November 2011, by regulation 45(3) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 1(1)(g): substituted, on 10 November 2011, by regulation 45(4) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 1(2): inserted, on 31 December 2013, by regulation 32 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

2

The following work is not prescribed electrical work:
Low voltage fittings

(a)

work done on low voltage fittings, but only if the work is done in accordance with ECP 51, and without payment or reward, and the work consists of—

(i)

replacing a fuse link with a fuse link or plug-in miniature circuit breaker of an appropriate rating; or

(ii)

affixing a plug, adaptor, cord extension socket, or appliance connector of an appropriate rating to a flexible cord designed for that purpose:

Extra-low voltage supply

(b)

work done on installations, fittings, or appliances that—

(i)

are intended solely for connection to, or are associated solely with, electricity supplies not exceeding extra-low voltage; and

(ii)

are not in a hazardous area:

(c)

work done on installations or fittings that—

(i)

are intended solely for connection to, or are associated solely with, electricity supplies not exceeding extra-low voltage; and

(ii)

are not in a medical location:

(d)

repairing or adjusting fittings, or replacing fittings with the same or comparable fittings, in installations or appliances, but only if the work can be done without exposure to live parts intended to operate at voltages exceeding extra-low voltage:

Operation

(e)

operating works, installations, or appliances, including the loading, removal, or replacement of fuse links:

Isolating and earthing

(f)

operating or switching works, installations, or appliances for the purpose of isolating and earthing the works, installations, or appliances, including manually applying or removing temporary earthing or bonding fittings and manually removing and reinserting fuses:

Electric lines

(g)

constructing overhead electric lines as part of any works, but only if the lines are being installed on poles or other supports that do not carry fittings that are already connected to a power supply:

(h)

constructing underground electric lines as part of any works, but only if the lines are being connected to fittings or installations that are not already connected to a power supply:

Permanent removal

(i)

permanently removing, dismantling, or demolishing works or installations that have been permanently disconnected from a power supply:

Appliances

(j)

maintaining appliances, but only if the work is done in accordance with user instructions prepared by the manufacturer and supplied with the appliance to the user:

(k)

repairing or reworking an appliance, but only if it is undertaken in accordance with the instructions of the original manufacturer of the appliance:

(l)

rewinding coils and armatures:

Testing, teaching, experimenting, etc

(m)

installing temporary conductors between fittings (or between appliances, or between fittings and appliances) or repairing fittings and appliances, but only if the fittings or appliances are used for experimental, testing, demonstration, teaching, or research purposes in any electrical engineering workshop, manufacturing facility, electrical test facility, laboratory, hospital, research project, or teaching institution:

(n)

experimental work on radio transmitters, receivers, and electronic apparatus, but only if the work is not carried out for payment or reward:

Telecommunications work

(o)

work done on or in connection with telecommunications lines or equipment where—

(i)

the lines or equipment operate at telecommunications network voltage; or

(ii)

the magnitude and duration of any shock currents cannot exceed IEC shock current standards; or

(iii)

the work can be done without exposure to voltages that exceed telecommunications network voltage or to shock currents that exceed IEC shock current standards:

Electric cars

(p)

any work on electric cars (being road vehicles that use electricity generated within the vehicle, or electricity supplied from a standard low voltage supply, as its motive energy source):

Electric fences

(q)

any work relating to the conductors, supports, or insulators of electric fences, and connecting them to, or disconnecting them from, an electric fence controller:

Temporary earthing

(r)

applying or removing temporary bonding conductors to or from any metal pipe or tube that forms (whether by design or not) part of an earthing system, but only if the temporary bonding conductor is for the purpose of maintaining a continuous path to earth during work on the pipe or tube:

New Zealand Defence Force apparatus

(s)

assembling and repairing radio apparatus, fire control equipment, or searchlights used solely for defence purposes under the control of the New Zealand Defence Force, but only if the officer or non-commissioned officer who has control of the apparatus, equipment, or searchlight has directed the conditions of security that must be observed in the assembly or repair:

Excluded things

(t)

work on any of the things identified in regulation 3 as things that these regulations do not apply to.

Schedule 1 clause 2(e): amended, on 10 November 2011, by regulation 45(5) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 2(f): amended, on 10 November 2011, by regulation 45(6) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 2(g): amended, on 10 November 2011, by regulation 45(7) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 2(m): amended, on 10 November 2011, by regulation 45(8)(a) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 2(m): amended, on 10 November 2011, by regulation 45(8)(b) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).
Schedule 1 clause 2(r): amended, on 10 November 2011, by regulation 45(9) of the Electricity (Safety) Amendment Regulations 2011 (SR 2011/370).

Schedule 2 Electrical codes of practice and official standards cited in these regulations

r 4(4)
Schedule 2: replaced, on 31 December 2013, by regulation 33 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Electrical codes of practice referred to in regulations

Abbreviation used in regulations

Full title

ECP 34

New Zealand Electrical Code of Practice for Electrical Safe Distances (NZECP 34:2001) approved on 21 December 2001

ECP 35

New Zealand Electrical Code of Practice for Power Systems Earthing (NZECP 35:1993) approved on 18 March 1993

ECP 36

New Zealand Electrical Code of Practice for Harmonic Levels (NZECP 36:1993) approved on 18 March 1993

ECP 46

New Zealand Electrical Code of Practice for High Voltage Live Line Work (NZECP 46.2003) approved on 19 March 2003

ECP 50

New Zealand Electrical Code of Practice for Repair and Maintenance of Domestic Electrical Appliances by the Owner of the Appliance (NZECP 50:2004) approved on 27 July 2004

ECP 51

New Zealand Electrical Code of Practice for Homeowner/Occupier’s Electrical Wiring Work in Domestic Installations (NZECP 51:2004) approved on 27 July 2004

ECP 60

New Zealand Electrical Code of Practice for Inspection, Testing and Certification of Low Voltage A.C. Railway Signalling Control Circuits (NZECP 60:1997) approved on 11 March 1998

Official standards referred to in regulations

Abbreviation used in regulations

Full title

AS 2290.1

AS 2290.1:1990: Electrical equipment for coal mines—Maintenance of electrical equipment for hazardous areas

AS 2290.3

AS 2290.3:1990: Electrical equipment for coal mines—Maintenance and overhaul—Maintenance of gas detecting and monitoring equipment

AS 4777.1

AS 4777.1:2005: Grid connection of energy systems via inverters—Part 1: Installation requirements

AS/NZS 1299

AS/NZS 1299:2009: Electrical equipment for mines and quarries—Explosion-protected three-phase restrained plugs and receptacles for working voltages up to and including 3.3 kV

AS/NZS 1677.2

AS/NZS 1677.2:1998: Refrigerating systems—Part 2: Safety requirements for fixed applications: including Amendments 1 and 2

AS/NZS 1747

AS/NZS 1747:2003: Reeling, trailing and feeder cables used for mining—Repair, testing and fitting of accessories

AS/NZS 1802

AS/NZS 1802:2003: Electric cables—Reeling and trailing—For underground coal mining purposes

AS/NZS 1826

AS/NZS 1826:2008: Electrical equipment for explosive gas atmospheres—Special protection—Type of protection ‘s’

AS/NZS 1972

AS/NZS 1972:2006: Electric cables—Underground coal mining purposes—Other than reeling and trailing

AS/NZS 2500

AS/NZS 2500:2004: Guide to the safe use of electricity in patient care

AS/NZS 3000

AS/NZS 3000:2007: Electrical installations (known as the Australian/New Zealand Wiring Rules): including Amendments 1 and 2, subject to the following modifications:

1. In 4.5.2.3.2, change “warning sign shall be installed” to “warning sign shall be installed or fitted in domestic installations but may be omitted from all other installations”.

2. In 4.18.1(b) and (c), change “all live (active and neutral) conductors” to “all active conductors”.

3. Add a new paragraph to 4.18.2: “In New Zealand, only electrical equipment that is directly associated with the gas supply may be installed in the hazardous areas of a domestic installation, shown in figure 4.10.”

4. Replace 4.18.3 with “In New Zealand, only electrical equipment (including metering equipment) that is directly associated with the gas supply may be installed in the exclusion zones of a domestic installation in figure 4.11.”

AS/NZS 3001

AS/NZS 3001:2008: Electrical installations—Transportable structures and vehicles including their site supplies: including Amendment 1

AS/NZS 3002

AS/NZS 3002:2008: Electrical installations—Shows and carnivals, subject to the variation that references to AS/NZS 3439.4 must be read as references to AS/NZS 3439.4:2009

AS/NZS 3003

AS/NZS 3003:2011: Electrical installations—Patient areas

AS/NZS 3004.1

AS/NZS 3004.1:2008: Electrical installations—Marinas and recreational boats—Part 1: Marinas

AS/NZS 3004.2

AS/NZS 3004.2:2008: Electrical installations—Marinas and recreational boats—Part 2: Recreational boats installations

AS/NZS 3007

AS/NZS 3007:2013: Electrical equipment in mines and quarries—Surface installations and associated processing plant

AS/NZS 3009

AS/NZS 3009:1998: Electric installations—Emergency power supplies in hospitals

AS/NZS 3010

AS/NZS 3010:2005: Electrical installations—Generating sets

AS/NZS 3012

AS/NZS 3012:2010: Electrical installations—Construction and demolition sites

AS/NZS 3014

AS/NZS 3014:2003: Electrical installations—Electric fences: including Amendment 1

AS/NZS 3016

AS/NZS 3016:2002: Electrical installations—Electric security fences: including Amendment 1

AS/NZS 3019

AS/NZS 3019:2007: Electrical installations—Periodic verification

AS/NZS 3112

AS/NZS 3112:2011: Approval and test specification—Plugs and socket-outlets: including Amendment 1

AS/NZS 3190

AS/NZS 3190:2011: Approval and test specification—Residual current devices (current-operated earth-leakage devices)

AS/NZS 3439

AS/NZS 3439.4.2009: Low-voltage switchgear and controlgear assemblies—Part 4: Particular requirements for assemblies for construction sites (ACS)

AS/NZS 3551

AS/NZS 3551:2012: Management programs for medical devices

AS/NZS 3760

AS/NZS 3760:2010: In-service safety inspection and testing of electrical equipment: including Amendments 1 and 2

AS/NZS 3800

AS/NZS 3800:2005: Electrical equipment for explosive atmospheres—Repair and overhaul

AS/NZS 3820

AS/NZS 3820:2009: Essential safety requirements for electrical equipment: including Amendment 1

AS/NZS 3832

AS/NZS 3832:1998: Electrical installations—Cold-cathode illumination systems

AS/NZS 4249

AS/NZS 4249:1994: Electrical safety practices—Film, video and television sites

AS/NZS 4509.1

AS/NZS 4509.1:2009: Stand-alone power systems—Part 1: Safety and installation

AS/NZS 4701

AS/NZS 4701:2000: Requirements for domestic electrical appliances and equipment for reconditioning or parts recycling

AS/NZS 4761.1

AS/NZS 4761.1:2008: Competencies for working with electrical equipment for hazardous areas (EEHA)—Competency Standards

AS/NZS 4836

AS/NZS 4836:2011: Safe working on or near low-voltage electrical installations and equipment

AS/NZS 5033

AS/NZS 5033:2012: Installation and safety requirements for photovoltaic (PV) arrays: including Amendments 1 and 2, subject to the following modification:

In clause 4.4.1.5(c), after “metallic”, insert “high density PVC”.

AS/NZS 5761

AS/NZS 5761:2011: In-service safety inspection and testing—Second-hand electrical equipment prior to sale

AS/NZS 5762

AS/NZS 5762:2011: In-service safety inspection and testing—Repaired electrical equipment

AS/NZS 7000

AS/NZS 7000:2010: Overhead line design—Detailed procedures

AS/NZS 60079.0

AS/NZS 60079.0:2012: Explosive atmospheres—Part 0: Equipment—General requirements

AS/NZS 60079.11

AS/NZS 60079.11:2011: Explosive atmospheres—Part 11: Equipment protection by intrinsic safety ‘i’

AS/NZS 60079.14

AS/NZS 60079.14:2009: Explosive atmospheres—Part 14: Electrical installations design, selection and erection: including Amendment 1

AS/NZS 60079.17

AS/NZS 60079.17:2009: Explosive atmospheres—Part 17: Electrical installations inspection and maintenance: including Amendment 1

AS/NZS 60079.18

AS/NZS 60079.18:2011: Explosive atmospheres—Part 18: Equipment protection by encapsulation ‘m’

AS/NZS 60079.29.2

AS/NZS 60079.29.2:2008: Explosive atmospheres—Gas detectors—Selection, installation, use, and maintenance of detectors for flammable gases and oxygen

AS/NZS 60079.35.1

AS/NZS 60079.35.1:2011: Explosive atmospheres—Caplights for use in mines susceptible to firedamp—General requirements—Construction and testing in relation to the risk of explosion

AS/NZS 60950.1

AS/NZS 60950.1:2011: Information technology equipment—Safety—General requirements: including Amendment 1

AS/NZS 61000.3.2

AS/NZS 61000.3.2:2007: Electromagnetic compatibility (EMC)—Limits—Limits for harmonic current emissions (equipment input current less than or equal to 16 A per phase): including Amendments 1 and 2

AS/NZS 62013.1

AS/NZS 62013.1:2001: Caplights for use in mines susceptible to firedamp—General requirements—Construction and testing in relation to the risk of explosion

BS EN 50119

BS EN 50119:2009: Railway applications—Fixed installations—Electric traction overhead contact lines

BS EN 50122-1

BS EN 50122-1:2011: Railway applications—Fixed installations—Electrical safety, earthing and the return circuit. Part 1: Protective provisions against electric shock: including Amendment 1

BS 6164

BS 6164:2011: Code of practice for health and safety in tunnelling in the construction industry

IEC 60050

IEC 60050-826 Ed 2: International electrotechnical vocabulary—Part 826: Electrical installations

IEC 60079-0

IEC 60079-0 Ed 6.0 Explosive atmospheres—Equipment—General requirements

IEC 60079-33

IEC 60079-33 Ed 1.0 Explosive atmospheres—Equipment protection by special protection ‘s’

IEC 60079-35-1

IEC 60079-35-1 Ed 1.0 Explosive atmospheres—Caplights for use in mines susceptible to firedamp—General requirements—Construction and testing in relation to the risk of explosion

IEC 60913

IEC 60913 Ed 2.0 Railway applications—Fixed installations—Electric traction overhead contact lines

IEC 61000-3-2

IEC 61000-3-2 Ed 3.2 b:2009: Electromagnetic compatibility (EMC)—Part 3-2: Limits—Limits for harmonic current emissions (equipment input current &1e; A per phase): as amended by the deviation in AS/NZS 61000.3.2:2007: including Amendments 1 and 2

IEC 61000-3-3

IEC 61000-3-3 Ed 2.0:2008: Electromagnetic compatibility (EMC)—Part 3-3: Limits—Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems, for equipment with rated current ≤16 A per phase and not subject to conditional connection

IEC 61000-3-4

IEC 61000-3-4 Ed 1.0:1998: Electromagnetic compatibility (EMC)—Part 3-4: Limits—Limitation of emission of harmonic currents in low-voltage power supply systems for equipment with rated current greater than 16 A

IEC 61000-3-11

IEC 61000-3-11 Ed 1.0:2000: Electromagnetic compatibility (EMC)—Part 3-11: Limits—Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage supply systems—Equipment with rated current ≤75 A and subject to conditional connection

IEC 61000-3-12

IEC 61000-3-12 Ed 2.0:2011: Electromagnetic compatibility (EMC)—Part 3-12: Limits—Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase

IEC 62128-1

IEC 62128-1 Ed 2.0 Railway applications—Fixed installations—Electrical safety, earthing and the return circuit—Part 1: Protective provisions against electric shock

IEC/TS 61000-3-5

IEC/TS 61000-3-5 Ed 2.0:2009: Electromagnetic compatibility (EMC)—Part 3-5: Limits—Limitation of voltage fluctuations and flicker in low-voltage power supply systems for equipment with rated current greater than 75 A

IEC/TS 60479-1

IEC/TS 60479-1 Ed 4.0:2005: Effects of current on human beings and livestock—Part 1: General aspects

IEEE 1222

IEEE 1222-2011: IEEE standard for testing and performance for all-dielectric self-supporting (ADSS) fiber optic cable for use on electric utility power lines

ISO/IEC 17050-1

ISO/IEC 17050-1 Ed 1.0:2004: Conformity assessment—Supplier’s declaration of conformity—Part 1: General requirements

NZS 6115

NZS 6115:2006: Electrical installations—Mobile medical facilities: including Amendments 1 and 2

NZS 6116

NZS 6116:2006: Safe application of electricity in the meat processing industry

NZS 7901

NZS 7901:2008: Electricity and gas industries—Safety management systems for public safety

Schedule 2: amended, on 1 August 2014, by regulation 4 of the Electricity (Safety) Amendment Regulations 2014 (LI 2014/253).

Schedule 3 Infringement notice and reminder notice

r 12

Form 1 Infringement notice

Section 165B, Electricity Act 1992

Infringement notice number:

This infringement notice is sent under section 165B of the Electricity Act 1992—

to you (see details below):
in respect of an alleged infringement offence (the offence—see details below):
by a person authorised to issue an infringement notice (the informant—see details below).

This notice is served on you on [date] by [specify post or personal service].
Your details

Full name:
Full address:
Telephone number(s):
Date of birth:
Gender:
Occupation:
Details of offence

Nature of offence:
Where it occurred:
When it occurred:
Offence against [specify provision of Electricity Act 1992 or Electricity (Safety) Regulations 2010]
Details of informant

WorkSafe/Secretary/Registrar*

*Select one.

Full address:
Payment of infringement fee

The amount of the infringement fee for the offence is $[amount].

The infringement fee is payable on or before [date], which is 28 days after the date of service.

The fee must be paid to the informant at the informant’s address (see above) by delivering or posting it so that it arrives on or before the due date.

If paying by cheque, the cheque must be made out to [specify] and be crossed not negotiable. When paying, include the following information with the payment:

the infringement notice number (given at the top of this notice):
your full name:
your address for contact, but only if it is different from your address as shown on this notice.

Paying infringement fee by due date

If you pay the infringement fee on or before the due date, no further action will be taken against you.
General inquiries

You may contact the informant at any time. Contacting the informant does not stop the infringement fee being payable by the due date, unless you request a hearing.
If you want further information, or if you want to raise any other matter, write to the informant at the informant’s address (see above). When writing, please give the infringement notice number (given at the top of this notice), your full name, and your address for contact (if different from your address as shown on this notice).
Right to request a hearing

Grounds for request

You should write to the informant if you want to request a hearing on the grounds that—

you deny liability for the offence; or
you admit liability for the offence, but you want a court to consider written submissions by you about any matter, such as the amount of the penalty.

How to make request

If you write to request a hearing, the request must be signed by you and be received by the informant on or before the due date, or by any later time allowed by the informant. When writing, give the infringement notice number (given at the top of this notice), your full name, and your address for contact (if different from your address as shown on this notice).
Denying liability

If you write to request a hearing and deny liability, and if the informant decides to commence court proceedings against you, you will be served with a notice of hearing. The notice will set out the place, date, and time of the hearing before the court.
If the court finds you guilty of the offence, court costs will be imposed on you in addition to any penalty.

If you write to request a hearing but you admit liability, your letter should clearly—

admit liability; and
set out the written submissions that you wish the court to consider.

The informant will file the letter containing your submissions in court. There is no provision for you to make oral submissions at the hearing, or for anyone else to do so on your behalf.
The court will impose court costs on you in addition to any penalty.

In any proceedings, it is a defence if you prove that the infringement fee was paid in full to the informant, at the informant’s address, on or before the due date. Late payment, or payment to an address other than the informant’s address, is not a defence, but late payments may be applied towards any fine and costs you become liable to pay.
If you do nothing

If you have not paid the infringement fee by the due date, and have not requested a hearing on or before that date (or within any further time that the informant allows), the informant may send you a reminder notice. The reminder notice will set out a final due date, which will be the date that is 28 days after the date on which the reminder notice is served on you.
If you do not pay the infringement fee on or before that final due date, and you do not request a hearing on or before that date (or within any further time the informant allows), you will be liable to pay court costs in addition to a fine of the same amount as the infringement fee (less any amount already paid).
Further information

Further information about infringement offences and fees is contained in section 21 of the Summary Proceedings Act 1957 and section 375 of the Criminal Procedure Act 2011. If there is anything in this notice that you do not understand, contact a lawyer.

Schedule 3 form 1: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Schedule 3 form 1: amended, on 1 July 2013, by section 413 of the Criminal Procedure Act 2011 (2011 No 81).

Form 2 Infringement reminder notice

Section 165B, Electricity Act 1992

Infringement notice number:

An infringement notice was sent under section 165B of the Electricity Act 1992—

to you (see details below):
in respect of an alleged infringement offence (the offence—see details below):
by a person authorised to issue an infringement notice (the informant—see details below).

The infringement notice was served on you on [date] by [specify post or personal service].
This reminder notice is served on you on [date] by [specify post or personal service] at [full address at which reminder notice served].
Your details

Full name:
Full address:
Telephone number(s):
Date of birth:
Gender:
Occupation:
Details of offence

Nature of offence:
Where it occurred:
When it occurred:
Offence against [specify provision of Electricity Act 1992 or Electricity (Safety) Regulations 2010]
Details of informant

WorkSafe/Secretary/Registrar*

*Select one.

Full address:
Payment of infringement fee

The amount of the infringement fee for the offence is $[amount].
Final due date

The due date for payment of the infringement fee was [date]. By that date, payment had not been received and you had not requested a hearing.
The final due date is now [date], which is 28 days after the date on which this notice is served on you.

The infringement fee must be paid to the informant at the informant’s address (see above) by delivering or posting it so that it arrives on or before the final due date.

If paying by cheque, the cheque must be made out to [specify] and be crossed not negotiable. When paying, include the following information with the payment:

the infringement notice number (given at the top of this notice):
your full name:
your address for contact, but only if it is different from your address as shown on this notice.

Paying infringement fee by final due date

You can pay the infringement fee to the informant now, at the informant’s address. If you pay it on or before the final due date, no further action will be taken against you.
General inquiries

You may contact the informant at any time. Contacting the informant does not stop the infringement fee being payable by the final due date, unless you request a hearing.
If you want further information, or if you want to raise any other matter, write to the informant at the informant’s address (see above). When writing, please give the infringement notice number (given at the top of this notice), your full name, and your address for contact (if different from your address as shown on this notice).
Right to request a hearing

Grounds for request

You should write to the informant if you want to request a hearing on the grounds that—

you deny liability for the offence; or
you admit liability for the offence, but you want a court to consider written submissions by you about any matter, such as the amount of the penalty.

How to make request

If you write to request a hearing, the request must be signed by you and be received by the informant on or before the final due date, or by any later time allowed by the informant. When writing, give the infringement notice number (given at the top of this notice), your full name, and your address for contact (if different from your address as shown on this notice).
Denying liability

If you write to request a hearing and deny liability, and if the informant decides to commence court proceedings against you, you will be served with a notice of hearing. The notice will set out the place, date, and time of the hearing before the court.
If the court finds you guilty of the offence, court costs will be imposed on you in addition to any penalty.
Admitting liability

If you write to request a hearing but you admit liability, your letter should clearly—

admit liability; and
set out the written submissions that you wish the court to consider.

The informant will file the letter containing your submissions in court. There is no provision for you to make oral submissions at the hearing, or for anyone else to do so on your behalf.
The court will impose court costs on you in addition to any fine.
Defences

In any proceedings, it is a defence if you prove that the infringement fee was paid in full to the informant, at the informant’s address, on or before the final due date. Late payment, or payment to an address other than the informant’s address, is not a defence, but late payments may be applied towards any fine and costs you become liable to pay.
If you do nothing

If you do not pay the infringement fee on or before the final due date, and you do not request a hearing on or before that date (or within any further time that the informant allows), you will be liable to pay court costs in addition to a fine of the same amount as the infringement fee (less any amount already paid).
Further information

Further information about infringement offences and fees is contained in section 21 of the Summary Proceedings Act 1957 and section 375 of the Criminal Procedure Act 2011. If there is anything in this notice that you do not understand, contact a lawyer.

Schedule 3 form 2: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).
Schedule 3 form 2: amended, on 1 July 2013, by section 413 of the Criminal Procedure Act 2011 (2011 No 81).

Schedule 4 Standards applicable to fittings and appliances

r 23(1)
Schedule 4: replaced, on 31 December 2013, by regulation 34 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Contents

1
Household and similar electrical appliances

2
Other electrical appliances

3
Low voltage electrical apparatus

4
Electric wires and cables

5
Switches for circuits, installation protective devices, and connection devices

6
Hand-held motor-operated electric tools

7
Electric welding machines

8
Audio and video products

9
Information technology equipment

10
Electrical medical devices

11
Lighting fittings

12
Lamp control gear

13
Lamps

14
Power transformers, power supplies, reactors, and similar products

15
Mining electrical equipment

1 Household and similar electrical appliances

(1)

In subclause (2),—
standard A means IEC 60335-1 Ed 4.2 as modified by Annex ZZ of AS/NZS 60335.1:2002, including Amendments 1 to 4
standard B means IEC 60335-1 Ed 5.0 as modified by AS/NZS 60335.1:2011
standard C means AS/NZS 60335.1:2002, including Amendments 1 to 4
standard D means AS/NZS 3350.1:2002, including Amendments 1 to 4.

(2)

Standards apply to household and similar electrical appliances as set out in the following table:

Household and similar electrical appliances

Applicable standard

Air-cleaning appliances

Standard A, or standard B, in conjunction with IEC 60335-2-65 Ed 2.1

Amusement machines and personal service machines

Standard A, or standard B, in conjunction with IEC 60335-2-82 Ed 2.1 as modified by Annex ZZ of AS/NZS 60335.2.82:2006, including Amendment 1

Appliances for heating liquids

Standard A, or standard B, in conjunction with IEC 60335-2-15 Ed 5.2 as modified by Annex ZZ of AS/NZS 60335.2.15:2002, including Amendments 1 to 4

Appliances for skin exposure to ultraviolet and infrared radiation

Standard A, or standard B, in conjunction with IEC 60335-2-27 Ed 5.0 as modified by AS/NZS 60335.2.27:2010

Appliances for skin or hair care

Standard A, or standard B, in conjunction with IEC 60335-2-23 Ed 5.2orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-23 Ed 5.1 as modified by Annex ZZ of AS/NZS 60335.2.23:2004, including Amendment 1

Appliances to recover and/or recycle refrigerant from air conditioning and refrigeration equipment

Standard A, or standard B, in conjunction with IEC 60335-2-104 Ed 1.0

Automatic machines for floor treatment for commercial use

Standard B, in conjunction with IEC 60335-2-72 Ed 3.0orUntil 31/05/2016, standard A, or standard B, in conjunction with IEC 60335-2-72 Ed 2.1

Battery chargers

Standard A, or standard B, in conjunction with IEC 60335-2-29 Ed 4.2 as modified by Annex ZZ of AS/NZS 60335.2.29:2004, including Amendments 1 and 2

Blankets, pads, clothing, and similar flexible heating appliances

Standard B, in conjunction with IEC 60335-2-17 Ed 3.0 as modified by AS/NZS 60335.2.17:2012orUntil 26/10/2015, standard A, or standard B, in conjunction with IEC 60335-2-17 Ed 2.2 as modified by Annex ZZ of AS/NZS 60335.2.17:2004, including Amendments 1 and 2

Clocks

Standard A, or standard B, in conjunction with IEC 60335-2-26 Ed 4.1

Clothes dryers and towel rails

Standard A, or standard B, in conjunction with IEC 60335-2-43 Ed 3.2

Commercial dispensing appliances and vending machines

Standard A, or standard B, in conjunction with IEC 60335-2-75 Ed 2.2 as modified by Annex ZZ of AS/NZS 60335.2.75:2005, including Amendment 1

Commercial electric appliances for keeping food and crockery warm

Standard A, or standard B, in conjunction with IEC 60335-2-49 Ed 4.1

Commercial electric bains-marie

Standard A, or standard B, in conjunction with IEC 60335-2-50 Ed 4.1

Commercial electric boiling pans

Standard A, or standard B, in conjunction with IEC 60335-2-47 Ed 4.1

Commercial electric cooking ranges, ovens, hobs, and hob elements

Standard A, or standard B, in conjunction with IEC 60335-2-36 Ed 5.2

Commercial electric deep fat fryers

Standard A, or standard B, in conjunction with IEC 60335-2-37 Ed 5.2

Commercial electric dishwashing machines

Standard A, or standard B, in conjunction with IEC 60335-2-58 Ed 3.1

Commercial electric forced convection ovens, steam cookers, and steam-convection ovens

Standard A, or standard B, in conjunction with IEC 60335-2-42 Ed 5.1

Commercial electric griddles and griddle grills

Standard A, or standard B, in conjunction with IEC 60335-2-38 Ed 5.1

Commercial electric grillers and toasters

Standard A, or standard B, in conjunction with IEC 60335-2-48 Ed 4.1

Commercial electric hoods

Standard A, or standard B, in conjunction with IEC 60335-2-99 Ed 1.0

Commercial electric kitchen machines

Standard A, or standard B, in conjunction with IEC 60335-2-64 Ed 3.1

Commercial electric multi-purpose cooking pans

Standard B in conjunction with IEC 60335-2-39 Ed 6.0orStandard A, or standard B, in conjunction with IEC 60335-2-39 Ed 5.2

Commercial electric rinsing sinks

Standard A, or standard B, in conjunction with IEC 60335-2-62 Ed 3.1

Commercial microwave ovens

Standard A, or standard B, in conjunction with IEC 60335-2-90 Ed 3.1

Commercial refrigerating appliances with an incorporated or remote refrigerant condensing unit or compressor

Standard B in conjunction with IEC 60335-2-89 Ed 2.1orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-89 Ed 2.0 as modified by AS/NZS 60335.2.89:2010, including Amendment 1

Deep fat fryers, frying pans, and similar appliances

Standard B, in conjunction with IEC 60335-2-13 Ed 6.0

Dishwashers

Standard A, or standard B, in conjunction with IEC 60335-2-5 Ed 5.2 as modified by Annex ZZ of AS/NZS 60335.2.5:2002, including Amendments 1 to 3

Drives for gates, doors, and windows

Standard A, or standard B, in conjunction with IEC 60335-2-103 Ed 2.1

Drives for rolling shutters, awnings, blinds, and similar equipment

Standard A, or standard B, in conjunction with IEC 60335-2-97 Ed 2.2

Drives for vertically moving garage doors for residential use

Standard B, in conjunction with IEC 60335-2-95 Ed 3.0

Electric fence energisers

Standard A, or standard B, in conjunction with IEC 60335-2-76 Ed 2.2 as modified by Annex ZZ of AS/NZS 60335.2.76:2003, including Amendments 1 to 3orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-76 Ed 2.1 as modified by Annex ZZ of AS/NZS 60335.2.76:2003, including Amendments 1 to 3

Electric fishing machines

Standard A, or standard B, in conjunction with IEC 60335-2-86 Ed 2.2orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-86 Ed 2.1 as modified by Annex ZZ of AS/NZS 60335.2.86:2002, including Amendments 1 to 4

Electric irons

Standard B, in conjunction with IEC 60335-2-3 Ed 6.0orUntil 26/10/2015, standard A, or standard B, in conjunction with IEC 60335-2-3 Ed 5.2

Electrical animal-stunning equipment

Standard A, or standard B, in conjunction with IEC 60335-2-87 Ed 2.2orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-87 Ed 2.1

Electrical appliances for use with aquariums and garden ponds

Standard A, or standard B, in conjunction with IEC 60335-2-55 Ed 3.1 as modified by Annex ZZ of AS/NZS 60335.2.55:2011

Electrical heat pumps, air conditioners, and dehumidifiers

Standard A, or standard B, in conjunction with IEC 60335-2-40 Ed 4.2

Electrolysers

Standard A, or standard B, in conjunction with IEC 60335-2-108 Ed 1.0 as modified by Annex ZZ of AS/NZS 60335.2.108:2008

Fabric steamers

Standard A, or standard B, in conjunction with IEC 60335-2-85 Ed 2.1

Fans

Standard A, or standard B, in conjunction with IEC 60335-2-80 Ed 2.2 as modified by Annex ZZ of AS/NZS 60335.2.80:2004, including Amendment 1

Fixed immersion heaters

Standard A, or standard B, in conjunction with IEC 60335-2-73 Ed 2.2

Flexible sheet heating elements for room heating

Standard A, or standard B, in conjunction with IEC 60335-2-96 Ed 1.2

Floor treatment and floor cleaning machines, for commercial use

Standard B in conjunction with IEC 60335-2-67 Ed 4.0orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-67 Ed 3.1

Floor treatment machines and wet scrubbing machines

Standard A, or standard B, in conjunction with IEC 60335-2-10 Ed 5.2orUntil 31/05/2014, standard A, or standard B, in conjunction with IEC 60335-2-16 Ed 5.1

Food waste disposers

Standard A, or standard B, in conjunction with IEC 60335-2-16 Ed 5.1

Foot warmers and heating mats

Standard B in conjunction with IEC 60335-2-81 Ed 2.2orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-81 Ed 2.1

Gas, oil, and solid-fuel burning appliances with electrical connections

Standard B, in conjunction with IEC 60335-2-102 Ed 1.1 as modified by Annex ZZ of AS/NZS 60335.2.102:2004, including Amendments 1 and 2

Grills, toasters, and similar portable cooking appliances

Standard A, or standard B, in conjunction with IEC 60335-2-9 Ed 6.0 as modified by Annex ZZ of AS/NZS 60335.2.9:2009, including Amendment 1

Hand-held mains-operated garden blowers, vacuums, and blower vacuums

Standard A, or standard B, in conjunction with IEC 60335-2-100 Ed 1.0 as modified by Annex ZZ of AS/NZS 60335.2.100:2003

Heated carpets and underfloor heating appliances

Standard A, or standard B, in conjunction with IEC 60335-2-106 Ed 1.0

Heated gullies for roof drainage

Standard A, or standard B, in conjunction with IEC 60335-2-83 Ed 1.1

Heating appliances for breeding and rearing animals

Standard A, or standard B, in conjunction with IEC 60335-2-71 Ed 2.2orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-71 Ed 2.1

High pressure cleaners and steam cleaners

Standard B, in conjunction with IEC 60335-2-79 Ed 3.0orUntil 26/10/2015, standard A, or standard B, in conjunction with IEC 60335-2-79 Ed 2.2

Humidifiers

Standard A, or standard B, in conjunction with IEC 60335-2-98 Ed 2.2

Humidifiers intended for use with heating, ventilation, or air-conditioning systems

Standard A, or standard B, in conjunction with IEC 60335-2-88 Ed 2.0

Insect killers

Standard A, or standard B, in conjunction with IEC 60335-2-59 Ed 3.2 as modified by Annex ZZ of AS/NZS 60335.2.59:2005, including Amendments 1 to 3

Instantaneous water heaters

Standard A, or standard B, in conjunction with IEC 60335-2-35 Ed 4.2

Ironers

Standard B, in conjunction with IEC 60335-2-44 Ed 3.2orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-44 Ed 3.1

Kitchen machines

Standard A, or standard B, in conjunction with IEC 60335-2-14 Ed 5.1 as modified by Annex ZZ of AS/NZS 60335.2.14:2007, including Amendment 1

Massage appliances

Standard A, or standard B, in conjunction with IEC 60335-2-32 Ed 4.1

Microwave ovens, including combination microwave ovens

Standard A, or standard B, in conjunction with IEC 60335-2-25 Ed 6.0orUntil 29/04/2014, standard C in conjunction with IEC 60335-2-25 Ed 5.2

Milking machines

Standard A or standard B, in conjunction with IEC 60335-2-70 Ed 2.2orUntil 06/03/2015, standard A, or standard B, in conjunction with IEC 60335-2-70 Ed 2.1

Motor-compressors

Standard B, in conjunction with IEC 60335-2-34 Ed 5.0orUntil 31/05/2016, standard A, or standard B, in conjunction with IEC 60335-2-34 Ed 4.2

Multifunctional shower cabinets

Standard A, or standard B, in conjunction with IEC 60335-2-105 Ed 1.1

Oral hygiene appliances

Standard A, or standard B, in conjunction with IEC 60335-2-52 Ed 3.1

Outdoor barbecues

Standard A, or standard B, in conjunction with IEC 60335-2-78 Ed 2.1 as modified by Annex ZZ of AS/NZS 60335.2.78:2005, including Amendments 1 and 2

Pedestrian-controlled mains-operated lawn scarifiers and aerators

Standard A, or standard B, in conjunction with IEC 60335-2-92 Ed 2.0

Pedestrian-controlled mains-operated lawnmowers

Standard A, or standard B, in conjunction with IEC 60335-2-77 Ed 2.0

Portable heating tools and similar appliances

Standard A, or standard B, in conjunction with IEC 60335-2-45 Ed 3.1orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-45 Ed 3.1

Portable immersion heaters

Standard A, or standard B, in conjunction with IEC 60335-2-74 Ed 2.2

Projectors and similar appliances

Standard A, or standard B, in conjunction with IEC 60335-2-56 Ed 3.1

Pumps

Standard A, or standard B, in conjunction with IEC 60335-2-41 Ed 3.2 as modified by Annex ZZ of AS/NZS 60335.2.41:2004, including Amendment 1

Range hoods and other cooking fume extractors

Standard A, or standard B, in conjunction with IEC 60335-2-31 Ed 4.2 as modified by Annex ZZ of AS/NZS 60335.2.31:2004, including Amendments 1 to 4

Refrigerating appliances, ice-cream appliances, and ice-makers

Standard B, in conjunction with IEC 60335-2-24 Ed 7.1 as modified by AS/NZS 60335.2.24:2010 including Amendment 1orUntil 31/05/2015, standard A, or standard B, in conjunction with IEC 60335-2-24 Ed 7.0 as modified by AS/NZS 60335.2.24:2010

Room heaters

Standard A, or standard B, in conjunction with IEC 60335-2-30 Ed 4.2 as modified by Annex ZZ of AS/NZS 60335.2.30:2009, including Amendment 1

Sauna heating appliances and infrared cabins

Standard B, in conjunction with IEC 60335-2-53 Ed 4.0orUntil 28/10/2014, standard C in conjunction with IEC 60335-2-53 Ed 3.1

Scissors type grass shears

Standard A, or standard B, in conjunction with IEC 60335-2-94 Ed 3.0

Sewing machines

Standard A, or standard B, in conjunction with IEC 60335-2-28 Ed 4.1

Shavers, hair clippers, and similar appliances

Standard A, or standard B, in conjunction with IEC 60335-2-8 Ed 5.2

Spin extractors

Standard A, or standard B, in conjunction with IEC 60335-2-4 Ed 6.0

Spray extraction appliances, for commercial use

Standard B in conjunction with IEC 60335-2-68 Ed 4.0orUntil 31/05/2016, standard A, or standard B, in conjunction with IEC 60335-2-68 Ed 3.2

Stationary circulation pumps for heating and service water installations

Standard B, in conjunction with IEC 60335-2-51 Ed 3.2orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-51 Ed 3.1

Stationary cooking ranges, hobs, ovens, and similar appliances

Standard A, or standard B, in conjunction with IEC 60335-2-6 Ed 5.2 as modified by Annex ZZ of AS/NZS 60335.2.6:2008, including Amendments 1 and 4

Storage water heaters

Standard A, or standard B, in conjunction with IEC 60335-2-21 Ed 5.2 as modified by Annex ZZ of AS/NZS 60335.2.21:2002, including Amendments 1 to 3

Surface-cleaning appliances for household use employing liquids or steam

Standard A, or standard B, in conjunction with IEC 60335-2-54 Ed 4.0

Thermal storage room heaters

Standard A, or standard B, in conjunction with IEC 60335-2-61 Ed 2.2

Toilets

Standard A, or standard B, in conjunction with IEC 60335-2-84 Ed 2.1

Tumble dryers

Standard A, or standard B, in conjunction with IEC 60335-2-11 Ed 7.0 as modified by Annex ZZ of AS/NZS 60335.2.11:2009, including Amendment 1

UV radiation water treatment appliances

Standard B, in conjunction with IEC 60335-2-109 Ed 1.0

Vacuum cleaners and water-suction cleaning devices

Standard A, or standard B, in conjunction with IEC 60335-2-2 Ed 6.0 as modified by AS/NZS 60335.2.2:2010, including Amendment 1

Vaporisers

Standard A, or standard B, in conjunction with IEC 60335-2-101 Ed 1.1

Walk-behind and hand-held lawn trimmers and lawn edge trimmers

Standard A, or standard B, in conjunction with IEC 60335-2-91 Ed 3.0 as modified by Annex ZZ of AS/NZS 60335.2.91:2008, including Amendment 1

Warming plates and similar appliances

Standard A, or standard B, in conjunction with IEC 60335-2-12 Ed 5.1

Washing machines

Standard B, in conjunction with IEC 60335-2-7 Ed 7.1orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-7 Ed 7.0

Water-bed heaters

Standard B, in conjunction with IEC 60335-2-66 Ed 2.2orUntil 26/10/2014, standard A, or standard B, in conjunction with IEC 60335-2-66 Ed 2.1

Wet and dry vacuum cleaners, including power brush, for commercial use

Standard B, in conjunction with IEC 60335-2-69 Ed 4.0 as modified by Annex ZZ of AS/NZS 60335.2.69:2012orUntil 26/10/2015, standard A, or standard B, in conjunction with IEC 60335-2-69 Ed 3.2 as modified by Annex ZZ of AS/NZS 60335.2.69:2003, including Amendments 1 to 3

Whirlpool baths and whirlpool spas

Standard A, or standard B, in conjunction with IEC 60335-2-60 Ed 3.2 as modified by Annex ZZ of AS/NZS 60335.2.60:2006, including Amendment 1

2 Other electrical appliances



Standards apply to other electrical appliances as set out in the following table:

Other electrical appliances

Applicable standard

Electric duct heaters

AS/NZS 3102:2002, including Amendments 1 to 3

Electric toys

IEC 62115 Ed 1.2

Portable inverters

AS/NZS 4763:2011

Smoke detectors

AS/NZS 3100:2009, including Amendments 1 and 2

3 Low voltage electrical apparatus



Standards apply to low voltage electrical apparatus as set out in the following table:

Low voltage electrical apparatus

Applicable standard

Air-break switches

AS/NZS 3133:2008, including Amendments 1 and 2

Appliance couplers for household and similar general purposes

AS/NZS 60320.1:2012orIEC 60320-1 Ed 2.1

Bayonet lampholder adaptors

AS 3119:1994

Bayonet lampholders

AS/NZS 61184:2007orIEC 61184 Ed 3.1, including Amendment 2, as modified by AS/NZS 61184:2007orUntil 30/12/2016, AS/NZS 3117:2007

Ceiling roses

AS/NZS 3113:2005

Cord extension sets

AS/NZS 3199:2007

Cord extension sockets

AS/NZS 3120:2011

Cord-line switches

AS/NZS 3127:2005orIEC 61058-2-1 Ed 2.0

Edison screw lampholders

AS/NZS 60238:2007orIEC 60238 Ed 8.2 as modified by AS/NZS 60238:2007orUntil 30/12/2016, AS/NZS 3140:2007

Electric shaver supply units

AS/NZS 3194:1993, including Amendment 1

Electrical equipment for spa and swimming pools

AS/NZS 3136:2001, including Amendments 1 and 2

Electrical equipment of machines

IEC 60204-1 Ed 5.1

Electrical portable outlet devices

AS/NZS 3105:2012

Interconnection couplers for household and similar equipment

AS/NZS 60320.2.2:2004orIEC 60320-2-2 Ed 2.0

Plugs and socket-outlets

AS/NZS 3112:2011, including Amendment 1

Plugs and socket-outlets for stationary appliances

AS/NZS 3131:2001

Plugs, socket-outlets, and couplers for general industrial application

AS/NZS 3123:2005

Plugs, socket-outlets, and couplers for industrial purposes—dimensional interchangeability requirements for pin and contact-tube accessories

IEC 60309-2 Ed 4.2

Plugs, socket-outlets, and couplers for industrial purposes—general requirements

IEC 60309-1 Ed 4.2

Plugs, socket-outlets, and couplers for industrial purposes—switched socket-outlets and connectors with or without interlock

IEC 60309-4 Ed 1.1

Plugs, socket-outlets, vehicle couplers, and vehicle inlets—conductive charging of electric vehicles

IEC 62196-1 Ed 2.0

Portable electrical control or conditioning devices

AS/NZS 3197:2005, including Amendments 1 and 2

Sewing machine couplers

AS/NZS 60320.2.1:2004orIEC 60320-2-1 Ed 2.0

Socket-outlet adaptors

AS/NZS 3122:2005

Temperature sensing controls

IEC 60730-2-9 Ed 3.1

4 Electric wires and cables



Standards apply to electric wires and cables as set out in the following table:

Electric wires and cables

Applicable standard

Cables for high voltage luminous discharge tube installations

AS/NZS 3166:1993

Electric cables—polymeric insulated—for distribution and service applicationsElectric cables—polymeric insulated—for working voltages up to and including 0.6/1 (1.2) kV

AS/NZS 4961:2003

Electric cables—polymeric insulated—for working voltages up to and including 0.6/1 (1.2) kV

AS/NZS 5000.1:2005, including Amendment 1

Electric cables—polymeric insulated—for working voltages up to and including 450/750 V

AS/NZS 5000.2:2006

Electric cables—polymeric insulated—multicore control cables

AS/NZS 5000.3:2003

Electric flexible cords

AS/NZS 3191:2008orIEC 60227 and IEC 60245 series

Heating cables with a rated voltage of 300/500 V for comfort heating and prevention of ice formation

IEC 60800 Ed 3.0

Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V—flexible cables (cords)

AS/NZS 60227.5:2003, including Amendment 1orIEC 60227-5 Ed 3.0

Rubber insulated cables—rated voltages up to and including 450/750 V—cords and flexible cables

AS/NZS 60245.4:2003, including Amendment 1orIEC 60245-4 Ed 3.0

Rubber insulated cables—rated voltages up to and including 450/750 V—cords for applications requiring high flexibility

IEC 60245-8 Ed 1.2

Rubber insulated cables—rated voltages up to and including 450/750 V—heat-resistant silicone insulated cables

IEC 60245-3 Ed 2.0, including Amendments 1 and 2

5 Switches for circuits, installation protective devices, and connection devices



Standards apply to switches for circuits, installation protective devices, and connection devices as set out in the following table:

Switches for circuits, installation protective devices, and connection devices

Applicable standard

Assemblies for power distribution in public networks

AS/NZS 3439.5:2001orIEC 61439-5 Ed 1.0

Circuit-breakers for overcurrent protection for household and similar installations—circuit-breakers for AC operation

AS/NZS 60898.1:2004orIEC 60898-1 Ed 1.2 as modified by AS/NZS 60898.1:2004orAS/NZS 3111:2009, including Amendment 1

Circuit-breakers for overcurrent protection for household and similar installations—circuit-breakers for AC and DC operation

AS/NZS 60898.2:2004orIEC 60898-2 Ed 1.1 as modified by AS/NZS 60898.2:2004

Contactors and motor-starters—AC semiconductor controllers and contactors for non-motor loads

AS/NZS 3947.4.3:2000orIEC 60947-4-3 Ed 1.2

Control circuit devices and switching elements—DC interface for proximity sensors and switching amplifiers (NAMUR)

AS/NZS 3947.5.6:2000orIEC 60947-5-6 Ed 1.0

Control circuit devices and switching elements—electrical emergency stop device with mechanical latching function

AS/NZS 3947.5.5:2000orIEC 60947-5-5 Ed 1.1

Control circuit devices and switching elements—proximity devices with defined behaviour under fault conditions

AS/NZS 3947.5.3:2000orIEC 60947-5-3 Ed 1.1

Electromagnetic remote-control switches (RCS)

IEC 60669-1 Ed 3.2 as modified by AS/NZS 60669.1:2013 in conjunction with IEC 60669-2-2 Ed 3.0

Electronic switches

IEC 60669-1 Ed 3.2 as modified by AS/NZS 60669.1:2013 in conjunction with IEC 60669-2-1 Ed 4.1 as modified by AS/NZS 60669.2.1:2013

Installation couplers intended for permanent connection in fixed installations

IEC 61535 Ed 1.1

Isolating switches

IEC 60669-1 Ed 3.2 as modified by AS/NZS 60669.1:2013 in conjunction with IEC 60669-2-4, Ed 1.0

Low-voltage assemblies intended to be installed in places where unskilled persons have access for their use

AS/NZS 3439.3:2002orIEC 60439-3 Ed 1.2 as modified by AS/NZS 3439.3:2002

Low-voltage fuses for use by authorised persons

IEC 60269-1 Ed 4.1 in conjunction with IEC 60269-2 Ed 4.0

Low-voltage fuses for use by unskilled persons

IEC 60269-1 Ed 4.1 in conjunction with IEC 60269-3 Ed 4.0

Low-voltage switchgear and controlgears assemblies for construction sites (ACS)

AS/NZS 3439.4:2009orIEC 60439-4 Ed 2.0

Multiple-function equipment—automatic transfer switching equipment

AS/NZS 3947.6.1:2001orIEC 60947-6-1 Ed 2.0

Residual current operated circuit-breakers with integral overcurrent protection for household and similar uses (RCBOs)

AS/NZS 61009.1:2011orIEC 61009-1 Ed 3.0 as modified by AS/NZS 61009.1:2011orAS/NZS 3190:2011

Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs)

AS/NZS 61008.1:2011orIEC 61008-1 Ed 3.0 as modified by AS/NZS 61008.1:2011orAS/NZS 3190:2011

Switches, disconnectors, switch-disconnectors, and fuse-combination units

AS/NZS 3947.3:2001orIEC 60947-3 Ed 3.1

Time-delay switches (TDS)

IEC 60669-1 Ed 3.2 as modified by AS/NZS 60669.1:2013 in conjunction with IEC 60669-2-3 Ed 3.0

Type F and type B residual current operated circuit-breakers with and without integral overcurrent protection for household and similar uses

IEC 62423 Ed 2.0

Type-tested and partially type-tested assemblies

AS/NZS 3439.1:2002orIEC 61439-1 Ed 2.0

6 Hand-held motor-operated electric tools

(1)

In subclause (2),—
standard E means IEC 60745-1 Ed 4.0 as modified by AS/NZS 60745.1:2009
standard F means AS/NZS 60745.1:2003, including Amendments 1 to 3.

(2)

Standards apply to hand-held motor-operated electric tools as set out in the following table:

Hand-held motor-operated electric tools

Applicable standard

Band saws

Standard E in conjunction with IEC 60745-2-20 Ed 1.1

Chain saws

Standard E in conjunction with IEC 60745-2-13 Ed 2.1

Circular saws

Standard E in conjunction with IEC 60745-2-5 Ed 5.0orUntil 29/04/2014, standard E in conjunction with IEC 60745-2-5 Ed 4.0

Concrete vibrators

Standard E in conjunction with IEC 60745-2-12 Ed 2.1 as modified by Annex ZZ of AS/NZS 60745.2.12:2009

Cut-off machines

Standard E in conjunction with IEC 60745-2-22 Ed 1.0 as modified by AS/NZS 60745.2.22:2011

Drain cleaners

Standard E in conjunction with IEC 60745-2-21 Ed 1.1

Drills and impact drills

Standard E in conjunction with IEC 60745-2-1 Ed 2.1

Grinders, polishers, and disc-type sanders

Standard E in conjunction with IEC 60745-2-3 Ed 2.2 as modified by AS/NZS 60745.2.3:2013orUntil 31/05/2015, standard E in conjunction with IEC 60745-2-3 Ed 2.1 as modified by AS/NZS 60745:2011

Hammers

Standard E in conjunction with IEC 60745-2-6 Ed 2.2 as modified by Annex ZZ of AS/NZS 60745.2.6:2009

Hedge trimmers

Standard E in conjunction with IEC 60745-2-15 Ed 2.1

Jointers

Standard E in conjunction with IEC 60745-2-19 Ed 1.1

Other hand-held motor-operated electric tools

AS/NZS 3160:2009 including Amendments 1 and 2

Planers

Standard E in conjunction with IEC 60745-2-14 Ed 2.2

Reciprocating saws (jig and sabre saws)

Standard E in conjunction with IEC 60745-2-11 Ed 2.1

Routers and trimmers

Standard E in conjunction with IEC 60745-2-17 Ed 3.0orUntil 29/04/2014, standard F in conjunction with AS/NZS 60745.2.17:2003

Sanders and polishers other than disc type

Standard E in conjunction with IEC 60745-2-4 Ed 2.1

Screwdrivers and impact wrenches

Standard E in conjunction with IEC 60745-2-2 Ed 2.1 as modified by Annex ZZ of AS/NZS 60745.2.2:2009

Shears and nibblers

Standard E in conjunction with IEC 60745-2-8 Ed 2.1 as modified by Annex ZZ of AS/NZS 60745.2.8:2009

Spray guns for non-flammable liquids

AS/NZS 3160:2009 including Amendments 1 and 2

Strapping tools

Standard E in conjunction with IEC 60745-2-18 Ed 1.1

Tackers

Standard E in conjunction with IEC 60745-2-16 Ed 2.0

Tappers

Standard E in conjunction with IEC 60745-2-9 Ed 2.1

7 Electric welding machines



Standards apply to electric welding machines as set out in the following table:

Electric welding machines

Applicable standard

Limited-duty, portable AC arc welding machines

IEC 60974-6 Ed 2.0orIEC 60974-6 Ed 1.0 as modified by AS 60974.6:2006

8 Audio and video products



Standards apply to audio and video products as set out in the following table:

Audio and video products

Applicable standard

Audio, video, and similar electronic apparatus

AS/NZS 60065:2012orIEC 60065 Ed 7.2 as modified by Annex ZZ of AS/NZS 60065:2012

Power supplies for IT equipment

AS/NZS 60065:2012orIEC 60065 Ed 7.2 as modified by Annex ZZ of AS/NZS 60065:2012

9 Information technology equipment



Standards apply to information technology equipment as set out in the following table:

Information technology equipment

Applicable standard

Information technology equipment

AS/NZS 60950.1:2011orIEC 60950-1 Ed 2.1, as modified by Annex ZZ of AS/NZS 60950.1:2011

Power supplies for IT equipment

AS/NZS 60950.1:2011orIEC 60950-1 Ed 2.1, as modified by Annex ZZ of AS/NZS 60950.1:2011

10 Electrical medical devices

(1)

In subclause (2),—
standard G means IEC 60601-1 Ed 3.0, including Amendment 1
standard H means IEC 60601-1 Ed 2.0, including Amendments 1 and 2.

(2)

Standards apply to electrical medical devices as set out in the following table:

Electrical medical devices

Applicable standard

Ambulatory electrocardiographic systems

Standard G in conjunction with IEC 60601-2-47 Ed 2.0

Anaesthetic systems

Standard G in conjunction with IEC 80601-2-13 Ed 1.0

Automatic cycling non-invasive blood pressure monitoring equipment

Standard G in conjunction with IEC 80601-2-30 Ed 1.0

Blankets, pads, and mattresses intended for heating in medical use

Standard G in conjunction with IEC 80601-2-35 Ed 2.0

Cardiac defibrillators

Standard G in conjunction with IEC 60601-2-4 Ed 3.0

Clinical thermometers for body temperature measurement

Standard G in conjunction with IEC 80601-2-56 Ed 1.0

Collateral standard—Alarm systems in medical electrical equipment and medical electrical systems

Standard G in conjunction with IEC 60601-1-8 Ed 2.1

Collateral standard—Medical electrical equipment and medical electrical systems used in the home healthcare environment

Standard G in conjunction with IEC 60601-1-11 Ed 1.0

Collateral standard—Medical electrical systems

Standard H in conjunction with IEC 60601-1-1 Ed 2.0

Collateral standard—Physiologic closed-loop controllers

Standard G in conjunction with IEC 60601-1-10 Ed 1.0

Collateral standard—Programmable electrical medical systems

Standard H in conjunction with IEC 60601-1-4 Ed 1.1

Collateral standard—Radiation protection in diagnostic X-ray equipment

Standard G in conjunction with IEC 60601-1-3 Ed 2.1

Collateral standard—usability

Standard G in conjunction with IEC 60601-1-6 Ed 3.0

Critical care ventilators

Standard G in conjunction with IEC 80601-2-12 Ed 1.0

Dental extra-oral X-ray equipment

Standard G in conjunction with IEC 60601-2-63 Ed 1.0

Dental intra-oral X-ray equipment

Standard G in conjunction with IEC 60601-2-65 Ed 1.0

Diagnostic and therapeutic laser equipment

Standard G in conjunction with IEC 60601-2-22 Ed 3.1

Direct blood-pressure monitoring equipment

Standard G in conjunction with IEC 60601-2-34 Ed 3.0

Electrocardiographic monitoring equipment

IEC 60601-2-25 Ed 2.0, including Amendment 1andIEC 60601-2-27 Ed 3.0

Electroencephalographs

Standard G in conjunction with IEC 60601-2-26 Ed 2.0

Electromyographs and evoked response equipment

Standard G in conjunction with IEC 60601-2-40 Ed 1.0

Electron accelerators in the range of 1 MeV to 50 MeV

Standard G in conjunction with IEC 60601-2-1 Ed 3.0

Endoscopic equipment

Standard G in conjunction with IEC 60601-2-18 Ed 3.0

External cardiac pacemakers with internal power source

Standard G in conjunction with IEC 60601-2-31 Ed 2.1

Extracorporeally induced lithotripsy

Standard G in conjunction with IEC 60601-2-36 Ed 1.0

Gamma beam therapy equipment

Standard G in conjunction with IEC 60601-2-11 Ed 3.0

Haemodialysis, haemodiafiltration, and haemofiltration equipment

Standard G in conjunction with IEC 60601-2-16 Ed 4.0

High-frequency surgical equipment

Standard G in conjunction with IEC 60601-2-2 Ed 5.0

Infant incubators

Standard G in conjunction with IEC 60601-2-19 Ed 2.0

Infant phototherapy equipment

Standard G in conjunction with IEC 60601-2-50 Ed 2.0

Infant radiant warmers

Standard G in conjunction with IEC 60601-2-21 Ed 2.0

Infant transport incubators

Standard G in conjunction with IEC 60601-2-20 Ed 2.0

Infusion pumps and controllers

Standard G in conjunction with IEC 60601-2-24 Ed 2.0

Lens removal devices and vitrectomy devices for ophthalmic surgery

Standard G in conjunction with IEC 80601-2-58 Ed 1.0

Magnetic resonance equipment for medical diagnosis

Standard G in conjunction with IEC 60601-2-33 Ed 3.1

Mammographic X-ray equipment and mammographic stereotactic devices

Standard G in conjunction with IEC 60601-2-45 Ed 3.0

Medical beds

Standard G in conjunction with IEC 60601-2-52 Ed 1.0

Microwave therapy equipment

Standard G in conjunction with IEC 60601-2-6 Ed 2.0

Multifunction patient monitoring equipment

Standard G in conjunction with IEC 60601-2-49 Ed 2.0

Nerve and muscle stimulators

Standard G in conjunction with IEC 60601-2-10 Ed 2.0

Non-laser light source equipment intended for therapeutic, diagnostic, monitoring and cosmetic/aesthetic use

Standard G in conjunction with IEC 60601-2-57 Ed 1.0

Operating tables

Standard G in conjunction with IEC 60601-2-46 Ed 2.0

Oxygen concentrators for individual patient use

Standard H in conjunction with ISO 8359:1996 including Amendment 1

Peritoneal dialysis equipment

Standard G in conjunction with IEC 60601-2-39 Ed 2.0

Pulse oximeter equipment

Standard G in conjunction with IEC 80601-2-61 Ed 1.0

Radiotherapy simulators

Standard G in conjunction with IEC 60601-2-29 Ed 3.0

Remote-controlled automatically driven gamma-ray afterloading equipment

Standard H in conjunction with IEC 60601-2-17 Ed 2.0

Requirements and tests for electromagnetic compatibility

Standard G in conjunction with IEC 60601-1-2 Ed 3.0

Respiratory gas monitors

Standard G in conjunction with IEC 80601-2-55 Ed 1.0

Screening thermographs for human febrile temperature screening

Standard G in conjunction with IEC 80601-2-59 Ed 1.0

Short-wave therapy equipment

Standard G in conjunction with IEC 60601-2-3 Ed 3.0

Sleep apnoea breathing therapy equipment

Standard H in conjunction with ISO 17510-1:2007

Surgical luminaires and luminaires for diagnosis

Standard G in conjunction with IEC 60601-2-41 Ed 2.0

Therapeutic X-ray generators

Standard G in conjunction with IEC 60601-2-8 Ed 2.0

Transcutaneous partial pressure monitoring equipment

Standard G in conjunction with IEC 60601-2-23 Ed 3.0

Ultrasonic medical diagnostic and monitoring equipment

Standard G in conjunction with IEC 60601-2-37 Ed 2.0

Ultrasonic physiotherapy equipment

Standard G in conjunction with IEC 60601-2-5 Ed 3.0

X-ray equipment for interventional procedures

Standard G in conjunction with IEC 60601-2-43 Ed 2.0

X-ray equipment for radiography and radioscopy

Standard G in conjunction with IEC 60601-2-54 Ed 1.0

X-ray source assemblies and X-ray tube assemblies for medical diagnosis generators

Standard G in conjunction with IEC 60601-2-28 Ed 2.0

11 Lighting fittings

(1)

In subclause (2),—
standard J means IEC 60598-1 Ed 7.0 as modified by Annex ZZ of AS/NZS 60598.1:2003
standard K means AS/NZS 60598.1:2003.

(2)

Standards apply to lighting fittings as set out in the following table:

Lighting fittings

Applicable standard

Air handling luminaires

Standard J in conjunction with IEC 60598-2-19 Ed 1.0, including Amendments 1 and 2orStandard K in conjunction with AS/NZS 60598.2.19:2001

Aquarium luminaires

Standard J in conjunction with IEC 60598-2-11 Ed 1.0

Extra low voltage lighting systems for filament lamps

Standard J in conjunction with IEC 60598-2-23 Ed 1.1 as modified by AS/NZS 60598.2.23:2002orStandard K in conjunction with AS/NZS 60598.2.23:2002

Fixed general-purpose luminaires

Standard J in conjunction with IEC 60598-2-1 Ed 1.0, including Amendment 1 (Annex ZZ of AS/NZS 60598.1:2003 is not applicable)orStandard K in conjunction with AS/NZS 60598.2.1:1998

Floodlights

Standard J in conjunction with IEC 60598-2-5 Ed 2.0 as modified by AS/NZS 60598.2.5:2002orStandard K in conjunction with AS/NZS 60598.2.5:2002

Ground-recessed luminaires

Standard J in conjunction with IEC 60598-2-13 Ed 1.0

Handlamps

Standard J in conjunction with IEC 60598-2-8 Ed 3.0orStandard K in conjunction with AS/NZS 60598.2.8:2002

Lighting chains

Standard J in conjunction with IEC 60598-2-20 Ed 3.0 as modified by AS/NZS 60598.2.20:2002orStandard K in conjunction with AS/NZS 60598.2.20:2002

Luminaires for cold cathode tubular discharge lamps (neon tubes) and similar equipment

Standard J in conjunction with IEC 60598-2-14 Ed 1.0

Luminaires for emergency lighting

Standard J in conjunction with IEC 60598-2-22 Ed 3.2 as modified by Compliance Document for New Zealand Building Code Clause F6orStandard K in conjunction with AS/NZS 60598.2.22:2005 as modified by Compliance Document for New Zealand Building Code Clause F6

Luminaires for road and street lighting

Standard J in conjunction with IEC 60598-2-3 Ed 3.0

Luminaires for stage lighting, television, film, and photographic studios (outdoor and indoor)

Standard J in conjunction with IEC 60598-2-17 Ed 1.2orStandard K in conjunction with AS/NZS 60598.2.17:2006

Luminaires for swimming pools and similar applications

Standard J in conjunction with IEC 60598-2-18 Ed 2.0 as modified by Annex ZZ of AS/NZS 60598.2.18:1998orStandard K in conjunction with AS/NZS 60598.2.18:1998

Luminaires for use in clinical areas of hospitals and health care buildings

Standard J in conjunction with IEC 60598-2-25 Ed 1.0, including Amendment 1orStandard K in conjunction with AS/NZS 60598.2.25:2001

Luminaires with built-in transformers or convertors for filament lamps

Standard J in conjunction with IEC 60598-2-6 Ed 2.0, including Amendment 1orStandard K in conjunction with AS/NZS 60598.2.6:1998

Luminaires with limited surface temperatures

Standard J in conjunction with IEC 60598-2-24 Ed 1.0

Mains socket-outlet mounted nightlights

Standard J in conjunction with IEC 60598-2-12 Ed 2.0 in conjunction with Annex J of AS/NZS 3112:2011

Photo and film luminaires (non-professional)

Standard J in conjunction with IEC 60598-2-9 Ed 2.0, including Amendment 1orStandard K in conjunction with AS/NZS 60598.2.9:2006

Portable general-purpose luminaires

Standard J in conjunction with IEC 60598-2-4 Ed 2.0 as modified by AS/NZS 60598.2.4:2005, including Amendment 1orStandard K in conjunction with AS/NZS 60598.2.4:2005, including Amendment 1

Portable luminaires for children

Standard J in conjunction with IEC 60598-2-10 Ed 2.0 as modified by Annex ZZ of AS/NZS 60598.2.10:1998

Portable luminaires for garden use

Standard J in conjunction with IEC 60598-2-10 Ed 2.0 as modified by Annex ZZ of AS/NZS 60598.2.10:1998

Recessed luminaires

Standard J in conjunction with IEC 60598-2-2 Ed 2.1 as modified by AS/NZS 60598.2.2:2001, including Amendment A

12 Lamp control gear

(1)

In subclause (2),—
standard L means AS/NZS 61347.1:2002
standard M means IEC 61347-1 Ed 2.1 as modified by AS/NZS 61347.1:2002.

(2)

Standards apply to lamp control gear as set out in the following table:

Lamp control gear

Applicable standard

AC supplied electronic ballasts for fluorescent lamps

Standard L in conjunction with AS/NZS 61347.2.3:2004orStandard M in conjunction with IEC 61347-2-3 Ed 1.1, including Amendment 2orIEC 61347-2-3 Ed 2.0

Ballasts for discharge lamps (excluding fluorescent lamps)

Standard L in conjunction with AS/NZS 61347.2.9:2004orStandard M in conjunction with IEC 61347-2-9 Ed 1.2

Ballasts for fluorescent lamps

Standard L in conjunction with AS/NZS 61347.2.8:2003orStandard M in conjunction with IEC 61347-2-8 Ed 1.1

DC or AC supplied electronic ballasts for discharge lamps (excluding fluorescent lamps)

Standard M in conjunction with IEC 61347-2-12 Ed 1.1

DC or AC supplied electronic controlgear for LED modules

Standard L in conjunction with IEC 61347-2-13 Ed 1.0

DC or AC supplied electronic step-down convertors for filament lamps

Standard L in conjunction with AS/NZS 61347.2.2:2007

DC supplied electronic ballasts for aircraft lighting

Standard L in conjunction with AS/NZS 61347.2.6:2002orStandard M in conjunction with IEC 61347-2-6 Ed 1.0orIEC 61347-2-3 Ed 2.0

DC supplied electronic ballasts for emergency lighting

Standard M in conjunction with IEC 61347-2-7 Ed 2.0

DC supplied electronic ballasts for general lighting

Standard L in conjunction with AS/NZS 61347.2.4:2002orStandard M in conjunction with IEC 61347-2-4 Ed 1.0orIEC 61347-2-3 Ed 2.0

DC supplied electronic ballasts for public transport

Standard L in conjunction with AS/NZS 61347.2.5:2002orStandard M in conjunction with IEC 61347-2-5 Ed 1.0orIEC 61347-2-3 Ed 2.0

Electronic inverters and convertors for high-frequency operation of cold start tubular discharge lamps (neon tubes)

Standard L in conjunction with AS/NZS 61347.2.10:2004orStandard M in conjunction with IEC 61347-2-10 Ed 1.1

Glow-starters for fluorescent lamps

AS/NZS 60155:2000, including Amendments 1 and 2orIEC 60155 Ed 4.0, including Amendments 1 and 2, as modified by AS/NZS 60155:2000, including Amendments 1 and 2

Miscellaneous electronic circuits used with luminaires

Standard L in conjunction with AS/NZS 61347.2.11:2003orStandard M in conjunction with IEC 61347-2-11 Ed 1.0

Starting devices (other than glow starters)

Standard L in conjunction with AS/NZS 61347.2.1:2002orStandard M in conjunction with IEC 61347-2-1 Ed 1.1

13 Lamps



Standards apply to lamps as set out in the following table:

Lamps

Applicable standard

Tungsten filament lamps for domestic and similar general lighting purposes

AS/NZS 60432.1:2007orIEC 60432-1 Ed 2.2

Tungsten-halogen lamps for domestic and similar general lighting purposes

AS/NZS 60432.2:2007orIEC 60432-2 Ed 2.2

Tungsten-halogen lamps (non-vehicle)

AS/NZS 60432.3:2007orIEC 60432-3 Ed 2.0

Self-ballasted lamps for general lighting services

AS/NZS 60968:2001orIEC 60968 Ed 2.0

14 Power transformers, power supplies, reactors, and similar products

(1)

In subclause (2),—
standard N means IEC 61558-1 Ed 2.1 as modified by Annex ZZ of AS/NZS 61558.1:2008, including Amendment 1
standard O means AS/NZS 61558.1:2000, including Amendments 1 to 7
standard P means IEC 61558-1 Ed 1.1 as modified by Annex ZZ of AS/NZS 61558.1:2000, including Amendments 1 to 7.

(2)

Standards apply to power transformers, power supplies, reactors, and similar products as set out in the following table:

Power transformers, power supplies, reactors, and similar products

Applicable standard

Auto transformers and power supply units incorporating auto transformers

Standard N in conjunction with IEC 61558-2-13 Ed 2.0

Bell and chime transformers and power supply units

Standard N in conjunction with IEC 61558-2-8 Ed 2.0orUntil 29/04/2014, standard O in conjunction with AS/NZS 61558.2.8:2001

Constant voltage transformers and power supply units

Standard P in conjunction with IEC 61558-2-12 Ed 2.0

Control transformers and power supplies incorporating control transformers

Standard N in conjunction with IEC 61558-2-2 Ed 2.0

Ignition transformers for gas and oil burners

Standard N in conjunction with IEC 61558-2-3 Ed 2.0orUntil 29/05/2014, standard O in conjunction with AS/NZS 61558.2.3:2001

Isolating transformers and power supply units for isolating transformers for general use

Standard N in conjunction with IEC 61558-2-4 Ed 2.0

Isolating transformers for the supply of medical locations

Standard N in conjunction with IEC 61558-2-15 Ed 2.0 as modified by AS/NZS 61558.2.15:2012orUntil 26/10/2015, standard O in conjunction with AS/NZS 61558.2.15:2001

Safety isolating transformers and power supply units for isolating transformers for general use

Standard N in conjunction with IEC 61558-2-6 Ed 2.0 as modified by AS/NZS 61558.2.6:2009

Separating transformers and power supplies incorporating separating transformers for general applications

Standard N in conjunction with IEC 61558-2-1 Ed 2.0

Small reactors

Standard N in conjunction with IEC 61558-2-20 Ed 2.0orUntil 29/04/2014, standard P in conjunction with IEC 61558-2-20 Ed 1.0

Switch mode power supply units and transformers for switch mode power supply units

Standard N in conjunction with IEC 61558-2-16 Ed 1.0

Transformers and power supplies for toys

Standard N in conjunction with IEC 61558-2-7 Ed 2.0

Transformers and power supply units for construction sites

Standard N in conjunction with IEC 61558-2-23 Ed 2.0orUntil 29/04/2014, standard O in conjunction with AS/NZS 61558.2.23:2001

Transformers for class III handlamps for tungsten filament lamps

Standard N in conjunction with IEC 61558-2-9 Ed 2.0orUntil 29/04/2014, standard O in conjunction with AS/NZS 61558.2.9:2003

Transformers for shavers, power supply units for shavers, and shaver supply units

Standard N in conjunction with IEC 61558-2-5 Ed 2.0 as modified by AS/NZS 61558.2.5:2011, including Amendment 1orUntil 28/10/2014, standard O in conjunction with AS/NZS 61558.2.5:2003

15 Mining electrical equipment

(1)
In subclause (2), standard Q means AS/NZS 4871.1:2012.

(2)

Standards apply to mining electrical equipment as set out in the following table:

Mining electrical equipment

Applicable standard

Distribution, control and auxiliary equipment

Standard Q in conjunction with AS/NZS 4871.2:2010

Substations

Standard Q in conjunction with AS/NZS 4871.3:2010

Mains powered electrical mobile machines

Standard Q in conjunction with AS/NZS 4871.4:2010

Battery powered electrical mobile machines

Standard Q in conjunction with AS/NZS 4871.5:2010

Diesel powered machinery and ancillary equipment

Standard Q in conjunction with AS/NZS 4871.6:2013

Electrical wiring systems at extra-low voltage of earth-moving machinery and ancillary equipment for use in mines

AS 4242:1994

Conveyors

AS 1755:2000

Reeling and trailing cables (other than underground coal mining)

AS/NZS 2802:2000, including Amendment 1

Electrical protection devices for mines and quarries

AS/NZS 2081:2011

Remote controls for mining equipment

AS/NZS 4240.1:2009 Remote control systems for mining equipment—Design, construction, testing, installation and commissioningAS/NZS 4240.2:2009 Remote control systems for mining equipment—Operation and maintenance for underground metalliferous miningAS/NZS 4240.3:2013 Remote control systems for mining equipment— Operation and maintenance for underground coal mining

Materials for insulating power conducting components

AS 1147.1-1989

Schedule 5 Prescribed fees payable to WorkSafe

rr 78, 85, 109, 119
Schedule 5 heading: amended, on 16 December 2013, by section 22 of the WorkSafe New Zealand Act 2013 (2013 No 94).

Matter in respect of which fees payable

Fee ($)(GST incl)

Warrant of electrical fitness under regulation 78
1

Application for approval under regulation 85 to sell declared high risk electrical article
400

Application under regulation 109 for exemption from requirements
400

The fee for arbitration (as referred to in regulation 119) is $80 per hour.

Schedule 6 Prescribed fees payable to Board

r 99
Schedule 6: replaced, on 1 July 2013, by regulation 18 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Function

Proposed fee($) (GST inclusive)

Application for registration

175

Application for registration (overseas-trained)

350

Application for provisional licence

91

Application for limited certificate

91

Registration certificate

57

Replacement certificate or licence

57

Certified copy of entry in register

57

Restoration of name to register

114

Application for employer licence

2,470

Application for written examination entry

85

Application for remarking examination

85

Return of examination script

85

Application for late examination

85

Application for practice assessment

85

Annual practising licence applied for electronically

60

Annual practising licence applied for manually

95

Schedule 7 Authentication mark

r 111B
Schedule 7: inserted, on 1 July 2013, by regulation 19 of the Electricity (Safety) Amendment Regulations 2012 (SR 2012/279).

Schedule 8 Rules for mining electrical equipment and conductors

r 13(2)(b)
Schedule 8: inserted, on 31 December 2013, by regulation 35 of the Electricity (Safety) Amendment Regulations 2013 (SR 2013/494).

Contents

1
Interpretation

Part 1 Safety fundamentals

2
Requirements for earthing systems

3
Isolation of equipment from electricity supply

4
Permanent notices

5
Keeping records and plans

Part 2 Electrical work on mining electrical equipment and conductors

6
Rule about 3-pin flat-pin socket-outlets in low voltage installations

7
Testing prescribed electrical work on low and extra-low voltage equipment and conductors

8
Testing prescribed electrical work on high voltage equipment and conductors

9
High-risk prescribed electrical work to be inspected

10
Who may carry out inspection

11
Record of inspection

12
Before connecting mining electrical equipment and conductors to power supply

13
Electrical safety certification

14
Exception for operators with maintenance management systems

15
Time when electrical safety certificate to be issued

16
What happens to electrical safety certificates

Part 3 Requirements for tunnelling operations and underground mining operations

17
Mining electrical equipment must be consistent with certified design

18
Installation of fixed equipment so as to ensure safety

19
Isolating electricity supply to underground parts of mining operation

20
Requirements for earthing equipment

21
Requirements for earthing systems

22
Nominal voltages must be identified on equipment

23
Voltage supply

24
Standards for gas monitors

25
Testing of hand-held equipment and associated cables

Part 4 Additional requirements for underground mining operations

Subpart 1—Additional requirements for all underground mining operations

26
Standards for cables

27
Requirements for reeling or trailing cables

28
Requirements for other cables

Subpart 2—Additional requirements for underground coal mining operations

29
Application of this subpart

30
Equipment to monitor earthing connection must be intrinsically safe

30
Preventing ignition of flammable gas

31
Use of oil-filled and oil-cooled mining electrical equipment prohibited in underground coal mining operation

32
Earth fault current at underground coal mining operations

33
Settings of leakage fault protective devices

34
Use of equipment when safe levels of methane have been exceeded

35
Use of variable-speed drives at underground coal mining operations

Subpart 3—Additional requirements for ERZ0s and ERZ1s

36
Application of this subpart

37
Requirements for mining electrical equipment used or installed in ERZ0 or ERZ1

38
Prescribed electrical work in relation to ERZ0 or ERZ1

39
Maintenance of mining electrical equipment in ERZ0 or ERZ1

40
Overhaul of mining electrical equipment in ERZ0 or ERZ1

41
Replacement of mining electrical equipment components in ERZ0 or ERZ1

42
Testing of mining electrical equipment in ERZ0 or ERZ1

1 Interpretation



In this schedule,—

cable means—

(a)

a conductor that is insulated and has a covering to prevent mechanical damage; and

(b)

includes 2 or more such conductors laid up together, whether or not they are provided with an overall protective covering

explosion risk zone means—

(a)

an ERZ0; or

(b)

an ERZ1; or

(c)

a NERZ

intrinsically safe, in relation to equipment, means designed and built in such a manner that is not capable of creating a charge sufficient to ignite flammable gas
NERZ has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013

operator,—

(a)

in relation to an alluvial mining operation, means the alluvial mine operator:

(b)

in relation to a mining operation, means the mine operator:

(c)

in relation to a quarrying operation, means the quarry operator

reeling cable means any cable that is—

(a)

used or placed in position for conveying electricity to mobile mining electrical equipment; and

(b)

designed to be frequently wound on or off a reeling drum

trailing cable means any cable that is—

(a)

used or placed in position for conveying electricity to mobile mining electrical equipment; and

(b)

designed to be moved with the mobile mining electrical equipment

underground coal mining operation has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013
underground metalliferous mining operation has the meaning given to it in regulation 3(1) of the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013.

Part 1 Safety fundamentals

2 Requirements for earthing systems

(1)

Mining electrical equipment and conductors supplying that equipment must be protected by an earthing system that is designed, installed, operated, and maintained so as to ensure, as far as practicable,—

(a)

the effective operation of isolation fittings in the event of earth fault currents; and

(b)

that the voltage of each conductor is restricted to a value consistent with the level of insulation applied; and

(c)

that step voltages, touch voltages, and transferred voltages are controlled to prevent danger to any person.

(2)
In the event of an earth fault on a reeling or trailing cable used in a tunnelling operation or underground mining operation, the cable and the mining electrical equipment being supplied by those cables must be capable of being isolated from the supply of electricity.

Compare: SR 2010/36 r 42

3 Isolation of equipment from electricity supply


Mining electrical equipment and conductors supplying that equipment must be capable of being isolated (whether that capability is provided from within the equipment or conductor or by an isolation fitting) from the supply of electricity.

Compare: SR 2010/36 r 43

4 Permanent notices

(1)

Durable notices must be conspicuously affixed near every place in an alluvial mining operation, mining operation, or quarrying operation where mining electrical equipment is installed that—

(a)

prohibit unauthorised people from operating or interfering with any mining electrical equipment except for the purpose of isolating the supply of electricity in an emergency; and

(b)

provide advice about what to do in the event of—

(i)

a fire caused by or involving the mining electrical equipment:

(ii)

electric shock to any person (including advice regarding treatment of that person).

(2)

In every underground mining operation, durable notices providing advice about how to isolate the supply of electricity at the surface to the underground parts of the mining operation must be conspicuously affixed—

(a)

at the entrance to the underground parts of the mining operation; and

(b)

near every device that is provided for communication between the underground parts of the mining operation and the surface.

(3)
The notices prescribed in this clause must be maintained in a legible condition.

Compare: SR 1980/51 r 7

5 Keeping records and plans

(1)
An operator of every alluvial mining operation, mining operation, or quarrying operation must keep such records and plans of mining electrical equipment and conductors at the alluvial mining operation, mining operation, or quarrying operation (as the case may be) as will enable the operator to readily locate all mining electrical equipment at the operation.

(2)

An operator must, for at least 7 years, retain—

(a)

every copy of a record of inspection that is provided under regulation 72A(1)(a); and

(b)

every electricity safety certificate that is issued under regulation 74A or clause 13; and

(c)

every record of a safety assessment that is provided under regulation 78D, 78G, or 78K.

Compare: SR 1997/60 r 59

Part 2 Electrical work on mining electrical equipment and conductors

6 Rule about 3-pin flat-pin socket-outlets in low voltage installations

(1)

If a 3-pin flat-pin socket-outlet that has the dimensions specified in AS/NZS 3112 is, or is to be, fitted in low voltage mining electrical equipment, it must be fitted in such a way that—

(a)

the socket-outlet may be supplied with electricity only at standard low voltage; and

(b)

the earth-continuity conductor is connected to the slot on the radial line; and

(c)

the order of connection, in a clockwise direction when the socket-outlet is viewed from the front, is—

(i)

earth-continuity conductor:

(ii)

active conductor:

(iii)

neutral (or other) conductor.

(2)
This clause applies despite anything in Part 1 or 2 of AS/NZS 3000 or in these regulations.

Compare: SR 2010/36 r 61A

7 Testing prescribed electrical work on low and extra-low voltage equipment and conductors



All prescribed electrical work done on low and extra-low voltage mining electrical equipment and conductors supplying that equipment must be tested—

(a)

for operational safety; and

(b)

to ensure that the equipment and conductors are not electrically unsafe; and

(c)

in the case of equipment and conductors used or installed in an alluvial mining operation, an opencast mining operation, or a quarrying operation, in accordance with AS/NZS 3007; and

(d)

in the case of equipment and conductors used or installed in a tunnelling operation or an underground mining operation, in accordance with the verification or testing process set out in the certified design.

Compare: SR 2010/36 r 63

8 Testing prescribed electrical work on high voltage equipment and conductors



Prescribed electrical work done on high voltage mining electrical equipment and conductors supplying that equipment must be tested in accordance with regulation 38 as if—

(a)

references in that regulation to works were references to the equipment and conductors; and

(b)

the reference to documentation were a reference to a record of inspection and any other documentation recording tests and test results.

Compare: SR 2010/36 r 64

9 High-risk prescribed electrical work to be inspected

(1)
All high-risk prescribed electrical work done on mining electrical equipment and conductors supplying that equipment that are used or installed in an alluvial mining operation, an opencast mining operation, or a quarrying operation must be inspected in accordance with AS/NZS 3007.

(2)

All high-risk prescribed electrical work done on high voltage mining electrical equipment and conductors supplying that equipment that are used or installed in a tunnelling operation or an underground mining operation must be inspected so as to verify that the equipment and conductors comply with—

(a)

regulation 17(1)(c); and

(b)

regulations 34, 41(1), 42(1), 43(1), and 44(1), as if references in those regulations to works were references to the equipment and conductors.

(3)

A person who inspects high-risk prescribed electrical work must undertake whatever tests, visual inspections, or other actions are necessary to satisfy the person that—

(a)

that work has been done in accordance with these regulations; and

(b)

the mining electrical equipment and conductors on which that work has been done is, and will be when powered, electrically safe.

Compare: SR 2010/36 r 70

10 Who may carry out inspection

(1)

A person may inspect high-risk prescribed electrical work on mining electrical equipment or conductors only if—

(a)

the person is authorised to inspect high-risk prescribed electrical work; or

(b)

in the case of high-risk prescribed electrical work carried out under an employer licence, the person is authorised to inspect the work under the system of operation used by the employer.

(2)

However, a person may not inspect prescribed electrical work if the person has—

(a)

personally carried out the work; or

(b)

supervised someone else carrying out the work.

Compare: SR 2010/36 r 71

11 Record of inspection

(1)
A person who carries out an inspection of high-risk prescribed electrical work on mining electrical equipment or conductors supplying that equipment must prepare a written record of the inspection.

(2)

The record of inspection must—

(a)

identify the work that was inspected; and

(b)

be signed and dated by the person carrying out the inspection; and

(c)

include or have on it the authentication mark, as specified in regulation 111B; and

(d)

if the inspection was carried out in accordance with a standard, identify the standard and state that the inspection was carried out in accordance with that standard; and

(e)

if the inspection was carried out in accordance with a certified design, identify the certified design and state that the inspection was carried out in accordance with that certified design; and

(f)

state whether the work that has been inspected has been done in accordance with these regulations; and

(g)

state whether the mining electrical equipment and conductors on which the work has been done is, and will be (when powered), electrically safe.

Compare: SR 2010/36 r 72

12 Before connecting mining electrical equipment and conductors to power supply

(1)
This provision applies where prescribed electrical work has been done on mining electrical equipment or conductors supplying that equipment.

(2)

Before connecting low voltage or extra-low voltage mining electrical equipment or conductors to a power supply, the person doing the connection must—

(a)

be satisfied that—

(i)

the mining electrical equipment and conductors are safe to connect; and

(ii)

the testing required by these regulations has been done; and

(iii)

in the case of mining electrical equipment and conductors installed in an ERZ0 or ERZ1, the equipment and conductors meet the explosion protection level required by clause 37; and

(iv)

all conductors have been installed in accordance with these regulations; and

(v)

all safety-critical equipment has been tested and is operational; and

(b)

if the work is required to be inspected, either inspect the work and complete a record of inspection or sight a record of inspection given by another person no earlier than 6 months before the equipment or conductor is connected; and

(c)

do all of the following:

(i)

ensure that the polarity and phase rotation of the supply are correct:

(ii)

ensure that the protection of the supply is correctly rated:

(iii)

ensure that the equipment and conductors are compatible with the supply system.

(3)
Before connecting high voltage mining electrical equipment or conductors to a power supply, the person doing the connection must comply with the requirements of regulation 38 as if references in that regulation to works were references to the mining electrical equipment and conductors.

(4)

If the person who connects mining electrical equipment and conductors has not personally done the testing required by these regulations, the person must sight documentation—

(a)

that is signed by the person who did the tests; and

(b)

that sets out what tests were carried out and what the results were.

(5)
To avoid doubt, in this regulation, connection refers to the prescribed electrical work that is the final step that will allow electricity to flow to the mining electrical equipment or conductors on which other prescribed electrical work has been done.

Compare: SR 2010/36 r 73A

13 Electrical safety certification

(1)

After prescribed electrical work on mining electrical equipment or conductors supplying that equipment is complete, the person who completed the work must issue an electrical safety certificate for the mining electrical equipment and conductors if the person is satisfied that—

(a)

the equipment and conductors are safe to use, on the grounds that they are electrically safe and comply with these regulations; and

(b)

where the prescribed electrical work comprised the maintenance or alteration of, or addition to, the mining electrical equipment or conductors, the work has not adversely affected any other part of the installation.

(2)
For the purposes of subclause (1), if mining electrical equipment and conductors are disconnected from a power supply while the prescribed electrical work was done, the work is complete only once the mining electrical equipment and conductors are connected or reconnected to a power supply.

(3)

An electrical safety certificate must—

(a)

include a statement that the person issuing it is satisfied that the mining electrical equipment and any conductors supplying that equipment are safe to use; and

(b)

clearly identify the equipment and conductors to which it relates; and

(c)

clearly identify the location of the equipment and conductors to which it relates; and

(d)

include or have on it the authentication mark, as specified in regulation 111B; and

(e)

give the date on which the connection was done; and

(f)

be signed and dated by—

(i)

the person who did the connection; and

(ii)

if the person who did the connection was acting under supervision, the supervisor; and

(g)

give the name and registration number of—

(i)

the person who did the connection; or

(ii)

if that person was acting under an employer licence, the employer’s licence number; or

(iii)

if the person in subparagraph (i) was acting under supervision, the registration number of the supervisor.

(4)
If prescribed electrical work is done without disconnecting the power supply, references in subclause (3)(e) to (g) to connection must be taken to be references to the completion of the work.

Compare: SR 2010/36 r 74A

14 Exception for operators with maintenance management systems



If prescribed electrical work is done on any mining electrical equipment or conductor supplying that equipment, then, despite clause 13, an electrical safety certificate does not need to be issued for the equipment or conductor if—

(a)

the operator has a maintenance management system in place for the mining electrical equipment and conductors:

(b)

the maintenance management system ensures that information equivalent to the information required by clause 13(3) is recorded and kept (except that the authentication mark required by clause 13(3)(d) need not be recorded and kept).

Compare: SR 2010/36 r 74B

15 Time when electrical safety certificate to be issued


A person who issues an electrical safety certificate for mining electrical equipment or conductors on which prescribed electrical work has been done must do so as soon as practicable after the mining electrical equipment and conductors are connected or reconnected to a power supply, but in any case no later than 20 working days after connection or reconnection.

Compare: SR 2010/36 r 74C

16 What happens to electrical safety certificates

(1)

A person who issues an electrical safety certificate must—

(a)

provide a copy of it, within 20 working days after it is issued, to the person who contracted for the prescribed electrical work or, if that person is not readily available, to the operator; and

(b)

retain a copy, whether in hard copy or electronically, for at least 7 years.

(2)

A person who issues an electrical safety certificate must, on request by any of the following, provide a copy of the certificate to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the mining electrical equipment is located:

(e)

the person who contracted for the work:

(f)

the operator.

(3)

The operator must, on request by any of the following, provide a copy of that information, or specified parts of that information, to the requester within 10 working days after the request:

(a)

WorkSafe:

(b)

the Board:

(c)

the Registrar:

(d)

the territorial authority of the place where the mining electrical equipment is located.

Compare: SR 2010/36 r 74G

Part 3 Requirements for tunnelling operations and underground mining operations

17 Mining electrical equipment must be consistent with certified design


All mining electrical equipment and conductors supplying that equipment at an underground mining operation or tunnelling operation must be installed, tested, inspected, and connected in accordance with the certified design for the mining operation.

18 Installation of fixed equipment so as to ensure safety



All mining electrical equipment and conductors supplying that equipment, other than mobile or relocatable mining electrical equipment and conductors, must be installed in such a place that—

(a)

the equipment is protected—

(i)

against potential damage from other equipment in use at the mining operation; and

(ii)

from rock or coal that may come loose; and

(b)

the equipment does not become dangerous as a result of interactions with other equipment in use at the mining operation.

19 Isolating electricity supply to underground parts of mining operation


At the entrance to the underground parts of the mining operation there must be a readily accessible means of isolating the supply of electricity to the underground parts of the mining operation.

20 Requirements for earthing equipment



A mine operator must ensure that—

(a)

all mining electrical equipment that is installed or used at the mining operation is protected (whether the capability is provided from within the equipment or by some other means) by an earthing system:

(b)

all metallic parts of mining electrical equipment (including sheaths, coverings, and cable screens) are earthed by connection to an earthing system:

(c)

the neutral point of any high or medium voltage transformer is earthed through a device that limits any earth fault current to not more than 5 amperes:

(d)

all earthing conductors in cables are earthed by connection to an earthing system.

Compare: SR 2010/36 r 42

21 Requirements for earthing systems

(1)
Every earthing system at an underground mining operation or tunnelling operation must comply with the requirements of this clause.

(2)

The earthing system must be designed, installed, operated, and maintained so as to ensure, as far as practicable,—

(a)

the effective operation of isolation fittings in the event of earth fault currents; and

(b)

that the voltage of each conductor is restricted to a value that is consistent with the level of insulation applied; and

(c)

that step voltages, touch voltages, and transferred voltages are controlled to prevent danger to any person.

(3)
The connection of the earthing system to the general mass of the earth must be made at the surface of the mining operation by 1 or more earthing electrodes.

(4)
An earthing system conductor must not have a conductance that is less than that of a copper conductor with a cross-sectional area of 16 mm².

(5)
All joints in and connections to an earthing system must be mechanically secure and electrically effective.

(6)
An earthing system may not contain any automatic circuit-opening devices.

(7)
To avoid doubt, metallic covering of cables may be used as part of an earthing system.

(8)
Subclause (4) does not apply to the metallic covering of cables or to the flexible metallic covering and earthing conductors forming part of flexible cables.

22 Nominal voltages must be identified on equipment



The nominal voltage of all mining electrical equipment must be clearly and visibly marked on the equipment and, if a colour is used to identify the voltage, the following colours must (and may only) be used for the following voltages:

(a)

if the nominal voltage is 125, pink:

(b)

if the nominal voltage is 240, cyan:

(c)

if the nominal voltage is 1 000, blue:

(d)

if the nominal voltage is 6 600, white:

(e)

if the nominal voltage is 11 000, red:

(f)

if the nominal voltage is 66 000, magenta.

23 Voltage supply

Voltage supply to underground parts of underground mining operation

(1)
The supply of electricity to the underground parts of an underground mining operation must not exceed 11 000 volts.

Voltage supply to stationary mining electrical equipment

(2)
The supply of electricity to stationary mining electrical equipment that is used in the underground parts of an underground mining operation must not exceed 6 600 volts.

Voltage supply to relocatable mining electrical equipment

(3)
The supply of electricity to relocatable mining electrical equipment that is used in the underground parts of an underground mining operation must not exceed 11 000 volts.

Voltage supply to mobile mining electrical equipment supplied by trailing or reeling cables

(4)
The supply of electricity to mobile mining electrical equipment supplied by a trailing or reeling cable used in a NERZ of an underground coal mining operation must not exceed 3 300 volts.

(5)
The supply of electricity to mobile mining electrical equipment supplied by a trailing or reeling cable used in an ERZ0 or ERZ1 and fitted with a flammable gas monitor must not exceed 3 300 volts.

(6)
The supply of electricity to mobile mining electrical equipment supplied by a trailing or reeling cable used in an ERZ0 or ERZ1 but not fitted with a flammable gas monitor must not exceed 1 200 volts.

Voltage supply to hand-held equipment

(7)
The supply of electricity to hand-held equipment, including hand-held lighting appliances, used in clean and dry locations in the underground parts of an underground mining operation must not exceed 250 volts.

(8)
The supply of electricity to hand-held equipment, including hand-held lighting appliances, used in any other location in the underground parts of an underground mining operation must not exceed that of a reduced low voltage system.

Voltage supply to lighting

(9)
The supply of electricity to lighting in an ERZ0 or ERZ1 must not exceed 125 volts.

(10)
The supply of electricity to lighting in an NERZ of an underground coal mining operation and in any underground part of an underground metalliferous mining operation must not exceed 250 volts.

24 Standards for gas monitors

(1)

Where a gas monitoring system is used or installed at an underground metalliferous mining operation—

(a)

the flammable gas monitors must be selected, installed, used, and maintained so as to comply with AS/NZS 60079.29.2:

(b)

the levels at which flammable gas monitors will provide warning alerts must be set in accordance with BS 6164:

(c)

any actions taken in response to a flammable gas monitor warning must comply with BS 6164.

(2)
Where a gas monitoring system is used or installed at an underground coal mining operation, the flammable gas monitors at the mining operation must be selected, installed, used, and maintained so as to comply with AS 2290.1.

25 Testing of hand-held equipment and associated cables



All hand-held mining electrical equipment used at an underground mining operation, and all flexible cables associated with that hand-held equipment, must be—

(a)

brought to the surface at least once every 3 months; and

(b)

tested, in accordance with the verification or testing process set out in the certified design,—

(i)

for operational safety; and

(ii)

to ensure that the hand-held equipment and cables are not electrically unsafe.

Compare: SR 1980/51 r 11(3)

Part 4 Additional requirements for underground mining operations

Subpart 1—Additional requirements for all underground mining operations

26 Standards for cables

(1)

All cables installed or used at an underground mining operation must comply with the following standards:

(a)

in the case of reeling or trailing cables, AS/NZS 1802; and

(b)

for all other cables, AS/NZS 1972:

(2)

When cables that are installed or used at an underground mining operation are—

(a)

repaired, they must be repaired and tested in accordance with AS/NZS 1747:

(b)

fitted with accessories, those accessories must be fitted in accordance with AS/NZS 1747.

27 Requirements for reeling or trailing cables

(1)
This clause applies to all reeling cables and trailing cables that are installed or used at an underground mining operation.

(2)
If a reeling or trailing cable is covered with a protective screen, the screen must be securely attached to the metallic structure of the equipment supplied by that cable so as to effectively enclose electrical contact between the equipment and the cable.

(3)
If a reeling or trailing cable is connected to mining electrical equipment, the outer sheath of the cable must be gripped in a manner that will relieve any undue stress on the cable and prevent sharp bends in the cable.

(4)
Cables must be protected from damage.

(5)
Any surplus cable kept at the underground mining operation must be stowed in a figure-of-eight.

(6)
Cables must be removed from the face when they are not immediately required.

(7)
A cable must not be used if it is defective or damaged.

(8)
A damaged or defective cable must immediately be removed from the underground parts of the mining operation to the surface (for repair or removal).

(9)
There must be a switch to isolate the supply of electricity to a cable at the point where a cable is connected to the parent circuit.

(10)

Sections of cable may only be joined by—

(a)

a bolted plug and socket coupling; or

(b)

a restrained plug and socket coupling.

(11)

A cable may only be connected to the mining electrical equipment that it supplies by one of the following means:

(a)

directly:

(b)

by a bolted plug and socket coupling:

(c)

by a restrained plug and socket coupling.

28 Requirements for other cables

(1)
This clause applies to all cables, other than reeling or trailing cables, that are installed or used at an underground mining operation.

(2)

Cables suspended in shafts and in boreholes must—

(a)

either—

(i)

be protected against damage from falling material and from normal winding operations in the shaft; or

(ii)

be placed where they will not be damaged by falling material or by normal winding operations in the shaft; and

(b)

unless they are designed and are able to sustain their own weight, be secured at such intervals and in such a manner as is necessary to relieve them from undue stress.

(3)

Cables suspended in haulage roadways must be—

(a)

kept clear of vehicles and other mobile mining electrical equipment; or

(b)

if it is not possible to comply with paragraph (a), protected from damage that may be caused by passing vehicles and other mobile mining electrical equipment.

(4)
Cables must be suspended at sufficiently frequent intervals, and in such a manner, as to avoid unnecessary sagging of, and undue damage to, the cables.

(5)
Any devices used or installed at an underground mining operation to support cables must be designed to release the cable when the cable is subject to greater stress than it is designed to withstand.

(6)

Cables must not be buried in a roadway, except where it is necessary to—

(a)

take the cable from one side of the roadway to another; or

(b)

avoid an obstruction; or

(c)

protect the cable.

(7)
If a cable is buried, it must be contained inside an enclosure that provides mechanical protection for the cable.

(8)
Coverings on cables must be protected against chemical corrosion in the manner provided for in AS/NZS 3000.

(9)
The material providing insulation for a cable at the end of the cable and at the joins between cables must be effectively sealed in a cable sealing or dividing box to prevent the entry of moisture into the cable.

(10)
The metallic covering of a cable must be securely attached to the metallic structure of the equipment supplied by that cable at the point where the metallic covering of a cable ends so as to effectively enclose electrical contact between the equipment and the cable.

(11)

Where a cable is connected to mining electrical equipment, the outer sheath of the cable must be gripped in order to—

(a)

relieve any undue stress on conductors in the cable; and

(b)

prevent any sharp bends in the conductors.

(12)
Any surplus cable kept at the underground mining operation must be stowed in a figure-of-eight.

(13)

Sections of cable may be joined only by—

(a)

a joint box that is constructed for the purpose; or

(b)

a bolted plug and socket coupling.

(14)

A cable may only be connected to the mining electrical equipment that it supplies either—

(a)

directly; or

(b)

by means of bolted couplers.

Subpart 2—Additional requirements for underground coal mining operations

29 Application of this subpart


Clauses 30 to 35 apply to underground coal mining operations.

30 Equipment to monitor earthing connection must be intrinsically safe


Mining electrical equipment that monitors the continuity of the earthing connection of other mining electrical equipment must be intrinsically safe.

30 Preventing ignition of flammable gas


All mining electrical equipment installed or used in the underground parts of the mining operation must comply with the requirements in the certified design for the equipment and conductors supplying that equipment for preventing the ignition of flammable gas by an electrical source.

31 Use of oil-filled and oil-cooled mining electrical equipment prohibited in underground coal mining operation


No oil-filled or oil-cooled mining electrical equipment may be installed or used in the underground parts of an underground coal mining operation.

32 Earth fault current at underground coal mining operations



The earth fault current at an underground coal mining operation must not exceed,—

(a)

for mains lighting located in an ERZ0 or ERZ1, 1 ampere:

(b)

if 2 or more neutral points are connected together, 2 amperes:

(c)

for every system operating at less than or equal to 1 200 volts, 2 amperes:

(d)

for every system that supplies electricity to mobile electrical equipment in the underground parts of the mining operation and operates at less than 3 300 volts, 2 amperes:

(e)

for every other system, 16 amperes.

33 Settings of leakage fault protective devices


The settings of leakage fault protective devices at an underground coal mining operation must not exceed one-fifth of the earth fault current limit prescribed in clause 32 for the kind of circuit that is being protected.

34 Use of equipment when safe levels of methane have been exceeded

(1)

Mining electrical equipment used or installed in the underground parts of an underground coal mining operation may remain powered when safe levels of methane have been exceeded only if—

(a)

the equipment has been certified EPL Ma; or

(b)

in the case of gas monitors, the monitor has been certified as special protection “s” for Group I.

(2)

In this clause,—

certified means certified as complying with the relevant standard as evidenced by a certificate of conformity issued under one of following:

(a)

the Australian/New Zealand Certification Scheme for explosion-protected electrical equipment:

(b)

the Australian Certification Scheme for explosion-protected electrical equipment:

(c)

the International Electrotechnical Commission Certification Scheme for explosion-protected electrical equipment

certified EPL Ma, in relation to mining electrical equipment, means certified to the relevant standard for EPL Ma that is prescribed in AS/NZS 60079.0 or IEC 60079-0 for that fitting or appliance.

35 Use of variable-speed drives at underground coal mining operations



If a variable-speed drive is used in the underground parts of an underground coal mining operation,—

(a)

the variable-speed drive must be designed (and manufactured) for use in the underground parts of an underground coal mining operation; and

(b)

the manufacturer’s instructions for the variable-speed drive must be kept and made readily available at the mining operation; and

(c)

those instructions must describe how the variable-speed drive is to be installed in the underground parts of an underground coal mining operation in New Zealand; and

(d)

the variable-speed drive must be installed in accordance with the manufacturer’s instructions.

Subpart 3—Additional requirements for ERZ0s and ERZ1s

36 Application of this subpart


Clauses 37 to 42 apply to ERZ0s and ERZ1s.

37 Requirements for mining electrical equipment used or installed in ERZ0 or ERZ1

(1)

All mining electrical equipment used or installed in an ERZ0 must be—

(a)

certified EPL Ma; or

(b)

in the case of gas monitors, certified as special protection “s” for Group I.

(2)

All mining electrical equipment used or installed in an ERZ1 must be,—

(a)

in the case of caplights, certified EPL Ma:

(b)

in the case of portable gas monitors (including portable flammable gas monitors), certified EPL Ma:

(c)

in the case of gas monitors other than portable gas monitors, certified as special protection “s” for Group I:

(d)

in the case of restrained plugs and sockets for working voltages of 3 300 or less,—

(i)

certified EPL Ma or Mb; and

(ii)

certified as complying with AS/NZS 1299:

(e)

in the case of all other mining electrical equipment, certified EPL Ma or Mb.

(3)
Despite subclauses (1) and (2), testing equipment that is not certified (in accordance with those subclauses) may be used in an ERZ0 or ERZ1 if it is used in accordance with an approval system for live electrical work established as part of the electrical engineering control plan required for the mining operation by the Health and Safety in Employment (Mining Operations and Quarrying Operations) Regulations 2013.

(4)

In this clause,—

certified means certified as complying with the relevant standard as evidenced by a certificate of conformity issued under one of following:

(a)

the Australian/New Zealand Certification Scheme for explosion-protected electrical equipment:

(b)

the Australian Certification Scheme for explosion-protected electrical equipment:

(c)

the International Electrotechnical Commission Certification Scheme for explosion-protected electrical equipment

certified EPL Ma, in relation to mining electrical equipment, means certified to the relevant standard for EPL Ma that is prescribed in AS/NZS 60079.0 or IEC 60079-0 for that fitting or appliance
certified EPL Mb, in relation to mining electrical equipment, means certified to the relevant standard for EPL Mb for that fitting or appliance as prescribed in AS/NZS 60079.0 or IEC 60079-0
special protection “s” means special protection “s” for Group I as defined in AS/NZS 1826 or IEC 60079-33.

38 Prescribed electrical work in relation to ERZ0 or ERZ1

(1)
This clause applies from 1 January 2016.

(2)
A mine operator must ensure that no person does, or assists in doing, any prescribed electrical work in relation to mining electrical equipment used or installed in an ERZ0 or ERZ1 unless that person has, or is supervised by a person who has, the competencies for carrying out electrical work that are prescribed in AS/NZS 4761.1.

(3)
For the purpose of subclause (2), WorkSafe may, by notice in the Gazette, recognise any New Zealand Qualifications Authority unit standard, or any other national or international qualification, as demonstrating the minimum competencies prescribed in AS/NZS 4761.1.

39 Maintenance of mining electrical equipment in ERZ0 or ERZ1

(1)
All mobile and relocatable mining electrical equipment installed or used in an ERZ0 or ERZ1 must be maintained so as to comply with AS 2290.1.

(2)
All other mining electrical equipment installed in an ERZ0 or ERZ1 must be maintained so as to comply with AS/NZS 60079.17.

40 Overhaul of mining electrical equipment in ERZ0 or ERZ1


Any overhaul of mining electrical equipment installed or used, or to be installed or used, in an ERZ0 or ERZ1 must be done in accordance with AS/NZS 3800.

41 Replacement of mining electrical equipment components in ERZ0 or ERZ1


The replacement of any component of mining electrical equipment installed or used in an ERZ0 or ERZ1 must be done in accordance with the manufacturer’s instructions for the component or for the equipment.

42 Testing of mining electrical equipment in ERZ0 or ERZ1



A mine operator must ensure that whenever mining electrical equipment installed or used in an ERZ0 or ERZ1 is tested,—

(a)

the equipment is isolated from its supply of electricity; and

(b)

the testing is carried out using equipment that is designed and certified for use as testing equipment for mining electrical equipment installed or used in an ERZ0 or ERZ1 (as applicable).

Rebecca Kitteridge,Clerk of the Executive Council.

Issued under the authority of the Legislation Act 2012.
Date of notification in Gazette: 4 March 2010.

Electricity (Safety) Amendment Regulations 2012

(SR 2012/279)
Jerry Mateparae, Governor-General

Order in Council

At Wellington this 24th day of September 2012
Present:The Right Hon John Key presiding in Council

Pursuant to section 169 of the Electricity Act 1992, His Excellency the Governor-General, acting on the advice and with the consent of the Executive Council, makes the following regulations.

Regulations

1 Title


These regulations are the Electricity (Safety) Amendment Regulations 2012.

2 Commencement


These regulations come into force on 1 July 2013.

3 Principal regulations


These regulations amend the Electricity (Safety) Regulations 2010 (the principal regulations).

Transitional provisions

17 Application of amendments made by these regulations

(1)

In this regulation,—
new regulations means the principal regulations as amended by these regulations
old regulations means the principal regulations as they were immediately before these regulations came into force.

(2)
The new regulations apply to all prescribed electrical work that is started on or after these regulations come into force.

(3)

Prescribed electrical work on an installation or part installation that is in progress when these regulations come into force may, after these regulations come into force, be continued and completed under either the old regulations or the new regulations, but,—

(a)

if the new regulations are applied, they must continue to be applied to all stages of the work (such as testing, inspection, connection, and certification) until the work is finished, and an electrical safety certificate must be issued for the installation or part installation after it is connected to a power supply; and

(b)

if the old regulations continue to be applied,—

(i)

an electrical safety certificate may, but need not, be issued; and

(ii)

if the work is high-risk prescribed electrical work, details of the work may, but need not, be recorded in the certification database.

 Rebecca Kitteridge,Clerk of the Executive Council.
Date of notification in Gazette: 27 September 2012.

Reprints notes

1 General

This is a reprint of the Electricity (Safety) Regulations 2010 that incorporates all the amendments to those regulations as at the date of the last amendment to them.

2 Legal status

Reprints are presumed to correctly state, as at the date of the reprint, the law enacted by the principal enactment and by any amendments to that enactment. Section 18 of the Legislation Act 2012 provides that this reprint, published in electronic form, has the status of an official version under section 17 of that Act. A printed version of the reprint produced directly from this official electronic version also has official status.

3 Editorial and format changes

Editorial and format changes to reprints are made using the powers under sections 24 to 26 of the Legislation Act 2012. See also http://www.pco.parliament.govt.nz/editorial-conventions/.

4 Amendments incorporated in this reprint

Electricity (Safety) Amendment Regulations 2014 (LI 2014/253)
Electricity (Safety) Amendment Regulations 2013 (SR 2013/494)
Medicines Amendment Act 2013 (2013 No 141): section 48
WorkSafe New Zealand Act 2013 (2013 No 94): section 22
Criminal Procedure (Consequential Amendments) Regulations 2013 (SR 2013/409): regulation 3(2)
Electricity (Safety) Amendment Regulations 2012 (SR 2012/279)
Criminal Procedure Act 2011 (2011 No 81): section 413
Electricity (Safety) Amendment Regulations 2011 (SR 2011/370)