CIRCULAR regulations on security management in the field of liquefied petroleum gas pursuant to Decree No. 189/2007/ND-CP on December 27, 2007 and the Government's Decree No. 44/2010/ND-CP dated 14 December 2010 of the Government on the amendments and supplements article 3 of Decree 189/2007/ND-CP on December 27, 2007 of the Government functions duties, powers and organizational structure of the Ministry of industry and trade;
Pursuant to Decree No. 06/CP dated 20 January 1995 from the Government detailing a number of articles of the labor code of occupational safety, hygiene and labour;
Pursuant to Decree No. 110/2002/ND-CP dated 27 December 2002 amending and supplementing a number of articles of Decree No. 06/CP dated 20 January 1995 from the Government detailing a number of articles of the labor code of occupational safety, hygiene and labour;
Pursuant to Decree No. 104/2009/ND-CP on November 9th, 2009 by government regulations dangerous goods list and shipping dangerous goods by motor transport by road;
Pursuant to Decree No. 107/2009/ND-CP on November 26, 2009 by the Government on petroleum gas business;
Pursuant to Decree No. 13/2010/ND-CP dated Feb. 11, 2011 by the Government on oil and gas work safely on land;
Minister of industry and trade regulations on security management in the field of liquefied petroleum gas as follows: Chapter 1.
General provisions article 1. Scope and object this circular applies regulations on the safety management in the field of liquid petroleum gas, applicable to business establishments petroleum and gas organizations and individuals concerned.
Article 2. Explanation of terms In this circular, the terms below are interpreted as follows: 1. liquid petroleum Gas is a mixture mainly of Propane (chemical formula: C3H8) and butane (chemical formula: C4H10) are derived from petroleum, name the Liquiefied Petroleum Gas (LPG).
2. LPG Stations on the bottle is used for media stations, specialized equipment LPG in bottles containing to sell to customers.
3. LPG Stations in the automobile is the station used vehicles, specialized equipment to load directly into the automotive LPG as fuel use for the engine.
4. LPG level Station is the station used vehicles, specialized equipment for LPG gas supply from a fixed tank or staging system bottle containing LPG directly through LPG gas pipeline to customers.
5. the LPG store is the store sell LPG and LPG business pro shop.
6. LPG bottle inspection Station is the station of the auditing implementation types of LPG cylinders.
7. Production facilities, repair the bottle containing the LPG is the base implementation of fabrication, repair the bottle containing LPG.
8. The basis exist containing LPG is the basis of delivery and implementation exist containing LPG with tank.
9. Business establishments in the field of LPG (LPG business establishments) is the base implementation of the production, processing, delivery, and distribution, including: manufacturing, processing of LPG; LPG import export ports; The repository exists containing LPG, LPG bottle preservation repositories and LPG bottle, shops selling LPG, LPG stations into the bottle, tank; LPG station on cars; LPG supply stations; Transport of LPG and LPG vehicles rental.
10. the LPG tank is Turkish to LPG capacity equal to or greater than 0.15 m3.
11. floating tanks are tanks placed on the ground and not fill sand or soil.
12. Tank sink is buried under the ground and tank are covered with sand or soil.
13. land relief tank is tank placed on the ground and is covered with sand or soil.
14. Safe distance is the minimum distance for calculation from the outer edge of the equipment, structures (reservoirs, tanks, tank, LPG import point or home) to the nearest point of the adjacent buildings, equipment to guarantee safety.
15. Danger Zone is the region in which the mixture of LPG and air likely to cause fires.
16. fire compartment Walls are brick walls or concrete or fireproof materials are resistant to fire a minimum of 60 minutes, minimum 2 m level or higher the top of tanks to prevent the thermal radiation from the fire outside the affected reservoirs, while ensuring enough distance to LPG vapor dispersion did not spread to neighbouring buildings or to external fire source when occur LPG leaks.
17. LPG pumps are devices or systems to measure the count the amount of LPG when loaded into a container of used vehicles.
18. Where the need to protect is the East, stay as population areas, schools, hospitals, cinemas, theaters, shops, supermarkets and other places of public entertainment, amusement, industrial, civil works.
19. The source cause fire is the source of energy led to the burning of LPG as the fire ceiling, materials, machinery, equipment when using Active or have the ability to heat or sparks can cause fire or explosive flammable gas mixture.
Article 3. The safety management system, risk assessment and emergency response plan 1. The existing facility contains LPG, LPG stations, LPG stations into the bottle into the automotive LPG supply stations, to perform the construction management system, risk assessment and emergency response plan to the competent agency evaluation and approval.
2. in case of LPG business establishments including factories manufacturing, processing, port of entry, storage space, LPG stations are adjacent and the same owner, the construction of the risk assessment and emergency response plan was established for the facility.
3. Every year, the basis of the provisions in paragraph 1 of this article are planning to make the rehearsal in an emergency rescue plan was approved.
Article 4. General provisions on safety for the LPG business establishments 1. The LPG business facility must be designed, built, installed and constructed in accordance with the national technical standards and related laws.
2. The LPG business establishments must have full operating processes, troubleshooting procedures and rules about safety was basal leadership approval.
3. The machine, equipment of LPG business establishments must be regularly checked, periodic technical inspection according to the safety regulations.
4. The premises of the LPG business establishments to ensure: a) For fire extinguishing facilities easily accessible;
b) ventilation and convenience for work distribute LPG when leaked, not stagnant and LPG to accumulate;
c) to prevent the access of non-authorised persons.
5. The persons related to the management and operation of the equipment, maintenance, transport, and unloading of LPG business establishments must be trained, professional training, technical safety, explosions and are certified according to the rules.
Article 5. Regulations on safety distance 1. LPG business establishments must ensure the safe distance between the equipment, works to fence the boundary of the base or the places that need protection.
2. Within the scope of the safe distance of the LPG business base, prohibiting the harmful risk activities directly or indirectly to the safety.
Article 6. Regulations on fire prevention of LPG business establishments must: 1. Have adequate fire protection approach.
2. Have fire warning systems, fire extinguishing appliances ensure requests and incendiary materials fit in the base.
3. Certificate of eligibility of prescribed fire.
4. put the signs such as: "banning fire", "non-smoking", "no free duty on", "fire prevention regulations", the fire command and other signage. The plaques are written in Vietnamese, easy to read, and put in a conspicuous position. The size of the letters on the signage must have a minimum height of 120 mm. 5. Take measures to control and prevent the incendiary source.
6. Earthing the equipment and the process under the national technical regulation and periodic checks prescribed.
Chapter 2.
Safety basis exists containing A LPG article 7. General rules for existing base contains the basis exist containing LPG to perform the provisions from Articles 3 to 6 of this circular and other additional measures to prevent the risk of fire, explosion and minimize the risk of leaks of LPG.
Article 8. Regulations for the installation of tank 1. The LPG tank to be placed outdoors, outside, outside the buildings. Do not set the tanks on rooftops, balconies, in the basement and under the works.
2. LPG tanks must be installed in a full range of safety equipment and prescribed test. Tanks must be installed in the emergency shutoff valves.
3. The tank is not set. The horizontal cylindrical tank is not set in line according to the vertical axis, towards the housing or service works.
4. To ensure a safe distance from the tank of LPG to the objects around them according to the provisions in annex 1 attached to this circular.
Article 9. Rules for operating the tank 1. LPG tanks loaded on not exceed specified levels. Loading level indicator on the clock line must have a maximum load level report.
2. All LPG tanks must be protected against corrosion. Protective coatings have to check no more than two years to avoid corrosive phenomena. Periodically to check the thickness of the casing sinks and checked within the prescribed period of 5 years.
Article 10. LPG pipeline 1. Floating pipes of the basis exists that contains LPG, sure platform must have been painted according to the specified color.
2. go to the underground piping must be protected to avoid corrosion by appropriate measures. Periodically to check the pipe, the thickness of the pipes under the rules.
Article 11. Safety technical measures strengthen existing establishments containing LPG in cases not yet fully meet the provisions of distance or to raise the level of safety, facilities exist containing LPG must apply technical measures to strengthen the safety match is stated in section 4 Annex 1 attached to this circular.
Reduced levels of distance towards strengthening measures are specified in section 4 Annex 1 attached to this circular is applicable only to the existing base containing LPG currently exist, do not apply to new construction base.
Chapter 3.
LPG stations to secure bottles of article 12. General rules for LPG stations in LPG Station bottle into bottle must implement the provisions from Articles 3 to 6 of this circular and the following requirements:

1. LPG Stations in the bottle must comply with the provisions from article 16 to article 19 of Decree 107/2009/ND-CP on November 26, 2009 by the Government on petroleum gas business (hereinafter known as Decree No. 107/2009/ND-CP), was issued a certificate of eligibility to the LPG cylinders.
2. Prohibition of LPG stations layout in bottles in the basement or in the floors of tall buildings.
3. The floor is flat, with charging stations or higher ground around. The case raised the floor space below are filled or if blank must have ventilation measures. Not be stored, preserved objects as well as flammable substances in this space.
4. Safe distance from tank to the objects around, from home recharge the bottle containing LPG to neighboring buildings and to the tanks specified in annex 1 attached to this circular.
Article 13. Check before proceeding to load 1. Check the general condition, tanks, fittings, equipment load is not damaged and there were no signs of leakage.
2. safety equipment, measuring equipment, fire, fire, in good condition and ready to use.
3. safety instructions when LPG have been applied in full. Loading station must have the approved loading processes put in place, which have the largest loading level regulation to not happen the excessive load.
4. do not load the LPG in bottles, at the same time must perform the test when one of the following cases: a) the auditing period too Bottles;
b) Bottle has not been calibrated or could not identify the auditing period.
5. do not load the LPG in bottles, at the same time must perform the reviews to remove or repair the cylinders in the following cases: a) the volume of the shell does not read or not;
b) disabled or damaged bottles in hand or foot ring belt;
c) bottles with physical disabilities in the bottle;
d) Chai visible corrosion;
DD) bottles that traces the arc of fire, due to fire;
e) bottle, van or the pressure reduction mechanism (if fitted) leaking or damaged.
6. LPG is prohibited on bottles of other owners that no contract on LPG cylinders with a loading station, bottles of unknown origin.
Article 14. Reviews removed, fix the bottle 1. The reviews removed the bottle must be the owner of the bottle that contains the following provisions in section 5 of ISO 7762:2007-Bottle contained gas. Welded steel bottles refilled is used for liquefied petroleum gas (LPG). Checkout process before, during and after the load.
2. The bottle doesn't guarantee safety must destroy to not be able to use it again.
3. Only be repaired at the base of bottle production, fix the bottle is eligible and has been issued a certificate.
Article 15. LPG in cylinders contain LPG 1. Made in accordance with bottle LPG loading process of loading station. The amount of LPG in cylinders must be in accordance with the prescribed volume of each type of bottle, but do not be overly regulated in Annex B of ISO 6485:1999-liquid gas (LPG). Intake manifold into the bottle of water to 150 litres. Safety requirements.
2. excessive load bottles must be pulled less amount of LPG admit until reaching the prescribed loading rate (mass, volume).
When withdrawal less the amount of LPG should follow the correct safety procedures and not be discharged directly into the environment.
3. All the cylinders were loaded after excessive discharge of excess amount must be examined again the level of load.
4. The bottle after LPG tightness must be checked, tagged on bottles and sealed the bottle valve.
Article 16. Preservation unloading bottles containing LPG in the loading station 1. The preservation of LPG stations in the bottle must have test equipment, LPG leakage alerts.
2. Place the preserving bottle containing LPG must ensure ventilation, not preserved in the lower places of the surrounding ground, in the cellar, in the basement.
3. LPG bottle container outdoors from 1000 kg or more are divided into ever smaller plots. Bottle container not LPG bottle container must have at least LPG 3 (three) m. LPG bottle container in the home must meet the requirements of volume exist containing, where exist containing prescribed in item 5.3 TCVN 6304:1997-Bottle containing LPG. Safety requirements in the maintenance, unloading and transport.
Chapter 4.
LPG supply stations safety article 17. General rules for the supply of LPG LPG generating stations must implement the provisions from Articles 3 to 6 of this circular and the following requirements: 1. Must comply with the provisions from Article 37 to article 40 of Decree 107/2009/ND-CP and is certified eligible for LPG supply stations.
2. The main items as tanks, pipes, air evaporation must be surrounded by a fence, where the layout is not fenced, the main items are housed in the facility's boundary fence.
3. To ensure convenience for fire, into the station when necessary.
4. The devices placed in the at-risk areas were damaged must be protected by safety measures such as roadblocks, the iron columns, concrete columns and has a sea warning. This safety device must not affect ventilation level of the area exists containing LPG.
5. Must quickly to where customers use LPG troubleshooting problem losing secure when receiving the notification of the client.
Article 18. The provisions for tank installation tank of LPG supply stations in to ensure that the provisions of article 8 and article 9 of this circular and the following requirements: 1. do not place the tank in the basement.
2. Distance from the LPG tank to other flammable liquid tank have ignite under 60oC is not smaller than 7 m. Article 19. Regulations with respect to LPG supply stations by the system bottle contains 1. Maximum capacity of jar repository allows is 1000 kg.
2. Only place the bottle in the container House industry when 700 kg and below capacity to ensure ventilation, fire prevention and safety. Bottle container is separated from other parts of the building by the way sure, ceilings, wallpaper, refractory limited for at least 150 minutes.
3. Store the bottles have the system header must be placed in sheltered housing made of non-flammable materials.
4. bottle container outside the House, industry is the difference with the other buildings or fences boundary of works besides the minimum distance of 1 m with the repository capacity under 400 kg; 3 m for warehouse capacity from 400 kg to 1000 kg.
Article 20. Regulations for chemical vapors when using the evaporation in LPG supply stations must comply with the following rules: 1. Just installed air evaporation ensure safe rooms and is the way tanks or bottles containing a minimum of 1.5 m from the nearest building, a minimum 3 m 2. When chemical vapors inside the building, the air turns somewhat to just put in a floor (ground floor) and a floor lower ground was not around, is clear.
Article 21. Regulations for the reception area from the LPG tank.
1. At the entrance for tank car, must have signage speed limits.
2. the receiving tank area must be clearly marked, the markings must have effective signage position of receiving tank and not for people who do not have a duty to pass when entering into the LPG tank.
3. Top of the tank when facing the main road to LPG import or escape to unencumbered when the emergency evacuation.
Article 22. Use the fire compartment walls 1. Fire compartment walls should not have holes, are solid brick masonry, concrete or other material, to ensure the least fire resistant limit of 150 minutes.
2. The height of walls of fire compartment to store the minimum tank higher than 0.5 m. Chapter 5.
Safe nap stations LPG on the automotive Article 23. General rules for LPG stations on automotive LPG Stations to carry the provisions from Articles 3 to 6 of this circular and the following requirements: 1. Must comply with the conditions from Article 33 to article 36 of Decree 107/2009/ND-CP and was issued a certificate of eligibility to the automotive LPG stations.
2. LPG Stations in the automobile must ensure ventilation requirements, not obscured around, have a protective barrier or preventive measures risk breaking from the outside in the area.
Article 24. Regulation with tanks in LPG station on cars 1. Floating tank was not placed in buildings or put together other flammable liquid container and must ensure a minimum distance of 3 m up to the fence.
2. Depositories of under 0.5 m3 are allowed to put in the necessary protection while ensuring the safe distance to any object not less than 3 m. When arranged in clusters, the number of not more than 5 tanks.
3. Turkish contain no overlap. The tanks in the Turkish must be placed parallel to each other and early Turkish have driven away with any dangerous substance, the container of a flammable explosive, flammable gas or solution else close by.
4. the minimum distance from the edge of the floating tank to the objects around them according to regulations section 1 Appendix 2 attached to this circular.
5. The distance from the floating tank to the tank and the other flammable substance containers must be in accordance with section 2 Appendix 2 attached to this circular.
Article 25. Regulation with tanks in LPG station on cars 1. Tanks sink not set under the area of other flammable liquid container.
2. Depositories have part or all of the part on the ground then the floating on the ground must be covered with sand or dirt with a thickness of not less than 600 mm. RADIUS With Turkish land relief no walled then the slope of the class covered not doing drifting of material covered.
3. When the layout according to the cluster of Turkish, not the husband.
4. the minimum distance of the tanks sank to the objects around them according to the provisions in section 3 Appendix 2 attached to this circular.
Article 26. Regulation for LPG pumps 1. LPG pumps are placed the way LPG tank of at least 10 m 2. To put the point of connection pipes and pumps the loaded LPG for means of ventilation in the place, and a walkway.
3. To insert the coupling attached between the pump column and hoses to supply LPG to cars.
Article 27. Regulations on LPG Station fire on the cars must comply with the regulations on fire prevention in article 6 of this circular and the following provisions: 1. Technology placed on the ground and vehicles to LPG delivery must be connected.
2. for tanks in the loading station has larger capacity of 20 m3 of water spray system to cool the tank top.

3. When using the wall prevents fire: the top of the wall is higher than 0.5 m tank wall of fire compartment arrangement. the distance between the floating tanks to fire compartment walls are as defined in Figure 2 Appendix 2 attached to this circular and the provisions in the national technical regulation.
Chapter 6.
LPG store safety Article 28. General rules for LPG LPG store stores must implement the relevant provisions from Articles 3 to 6 of this circular and the following requirements: 1. Must comply with the conditions from Article 29 to article 32 of Decree 107/2009/ND-CP, be certified eligible LPG business and the provisions of this circular.
2. construction structure, fire resistant level of minimum tier II store. The store's equipment must be type, minimum 1.5 m LPG bottle way. 3. LPG store employees must be professional training, safety engineering; Must be tested, the testing and certification according to the provisions of Article 52 clause 4 of this circular.
4. Must quickly to where customers use LPG troubleshooting problem losing secure when receiving the notification of the client.
5. LPG outlet must have shared the track import export bottle containing LPG, which must contain the information: the Serial Number of bottles, bottle type, the date indicated on the control bottle, where enter the bottle contains for shop, start date, customer name and address used on the bottle for the delivery, the customer.
Article 29. Regulations on the ground 1. Using a minimum of 12 m2 store.
2. to store quarantined with incendiary sources at least 3 m to the no fire wall; If there is no fire wall requires the distance between incendiary sources and outlets.
Article 30. Existing regulations contained and sold bottle containing LPG 1. Only allowed on display on these bottles do not contain advertising prices of LPG.
2. place bottle containing LPG to ensure ventilation. Not arranged in rooms sealed, enclosed tunnel. The case of warehouses, the repository must have at least 1 door and 1 backup outlet has the door open to the outside.
3. do not store LPG cylinders in the doors, the public walkway.
4. The bottle containing LPG, when sold to customers are intact, sealed, hermetic absolute, guaranteed quality, volume and registered labels.
5. Prohibition of conduct repair cylinders, LPG at the store.
6. Prohibition of the sale of bottles containing LPG mini reloaded (the bottle contains only allows once loaded).
Chapter 7.
Safety in the use and transport of cahi contains A LPG article 31. General rules of use and transport the bottle containing LPG 1. The bottle containing LPG shall: a) the intact original design shape, were technical safety inspection and auditing period not too;
b) register, registered trademarks as prescribed by law;
c) Are properly sealed;
d) have adequate records are stored as prescribed;
DD) native origin, in accordance with the contract of sale, purchase or contract agent of LPG business and meet the requirements specified in article 20, 21 Decree No. 107/2009/ND-CP dated. 2. LPG in cylinders should ensure the correct volume by design, logotype, the quality standard has announced.
3. When provided bottle contains LPG for customers who use LPG store, must give the customer a delivery slip 01 and 01 a save at the store, which must have the minimum information: serial numbers of bottles, bottle type, nearest testing time indicated on the bottle, the name, address and contact phone shop , customer name and address used on the bottle to the client interface,.
Article 32. Safety regulations for the transport of LPG bottle contains up to customers to use motorcycle (two wheels) to transport the bottle containing LPG must be sure rack, bottle must always in a vertical position, the bottle valve facing up.
Prohibiting the transport of LPG bottle contains along with the person in the elevator.
Article 33. Regulations on safety responsibilities of the LPG store for customers to use 1. Must provide documentation and instructions directly the necessary information about the safe use of LPG, precautionary measures, the processing steps when the LPG leakage; The process of using gas stove, bottles and accessories for customers who use gas stove, bottles containing LPG's shop.
2. Check the tightness of the valves, cylinders, connectors and hoses after the installation of new or replacement LPG bottle contains complete, has witnessed the process of check and sign to confirm on the report on the delivery of customer use.
3. Just be replaced, provide to the customer the type of accessories ensures safety when using and is specialized types for use with LPG; The hoses must be kind to prevent or protect from the invasive rodent species.
4. Inform customers use to know the rights and responsibilities of clients use LPG to ensure, in particular: a) The details about LPG bottle contains that customers use provided: origin, properly sealed, the trademark, the volume of LPG and LPG bottle contains inspection period;
b) When detecting the bottle containing LPG does not guarantee safety, risks causing fire and explosion (smell LPG Savannah due to the valves, ensure no accessories) must stop using immediately, store LPG to timely remedy; Do not arbitrarily fix, replace equipment;
c) if customers switch to using LPG bottles of other merchants or when there is no need to use the bottle containing LPG, customers use must notify the store selling the LPG to store the recovered LPG cylinders contain LPG.
Article 34. Safe transport of bottles containing LPG car 1. Automotive LPG bottle contains shipping must be licensed under the dangerous goods shipping regulations.
2. The bottles are arranged vertically, the bottle valve at the top. For the bottles with capacity on 99 liters, only ranked a class. bottle capacity under 99 liters allow folded from 2 layers back up but not be taller than the car and between two layers of plywood layer must be lined.
3. Prohibition of automobile parking place near incendiary sources where there are many people and the media. The case of the temporary parking cars for loading and unloading must be parked in place ensuring the safety of the people and do not hinder the other transportation.
Article 35. Shipping safety regulations the bottle containing LPG by 1. When shipping the bottle containing LPG by road must implement the rules on transport of dangerous goods of the maritime industry.
2. Bottle containing LPG in the cavity, decks must be natural ventilation or capture-wind mechanical, intake mouth must be placed in the lowest point of the Bay.
3. do not transport the bottles contain LPG in the sealed container.
4. The compartment containing the cylinders contain LPG must be equipped with fire alarm systems and automatic sprinkler systems.
Article 36. Shipping safety regulations the bottle containing LPG by rail When transporting bottles containing LPG by rail must fulfill the rules of carriage of dangerous goods by rail.
Chapter 8.
Safety in transportation, the transport of LPG with tank Article 37. Rules for who controls transport, escorts, storekeepers who controls the media, escorts, storekeepers are trained in safety techniques and be issued a certificate of safety engineering training in accordance with article 11 of Decree 104/2009/ND-CP on November 9th, 2009 by government regulations dangerous goods list and shipping dangerous goods by means of motor traffic road. The Organization trained and certified technical trainer is made according to the provisions of Article 52 clause 4 of this circular.
Article 38. Prescribed for tank car, tank wagon 1. Tank car, tank wagons transporting LPG tanks must be licensed under the dangerous goods shipping regulations.
2. The outside of each tank of LPG at the side and rear to paste the badge of danger and dangerous signal according to the model in Appendix 3 attached to this circular.
3. On the cabin of the car and into the car must have an emergency contact phone number. Digit height not less than 40 mm. 4. LPG tank, measuring equipment on tank car, tank wagons must comply with the national technical regulation relates and is calibrated according to the regulations.
Article 39. Regulation of LPG tank car forwarding, wagon Turkish 1. General provisions a) only allow the means of delivery of LPG and other facilities necessary for the operation of the station goes into storage areas, export and import of LPG;
b) drivers are often directly in the area of import vehicles during import of LPG. Immediately after delivery is complete, must control the media out of the station area;
c) incendiary sources must be monitored and apply safety measures when LPG delivery, specifically:-turn off the motor within the minimum radius of 5 m around the point of export and import of LPG, except dedicated engine driven pumps, compressors to export and import of LPG;
-Banned: smoking, flame cutting, welding, metal ceilings, portable power tools, mobile phones, pagers and other incendiary sources within a 15 m radius;
-When exporting LPG from the tank to the tank on the right off the air flow equipment, such as the large fan, has the top-the way LPG point within a radius of 15 m; Off the air, the device has a bare flame, spark, heat source.
d) when the car to LPG delivery, must put the sea warning "STOP", "BANNED" fire in the head and the tail tank. Turkish wagon must have measures to prevent the avoidance of other locomotives, carriages collide;
DD) When exporting LPG, must check confirmed that Turkish get LPG and accessories of Turkish eligibility prescribed safety. The production of LPG from tank wagons or tank to check for sure, the capacity exists, the amount of Turkish get LPG.
2. Safety rules when a tank car for LPG delivery) pending delivery of LPG tank car, parking in a safe place must have appropriate barriers, a fire source at least 7 m, the tank must be towards the exit door. Do not tank car or operate in enclosed building on 3 sides;
b) before implementing the LPG tank car forwarding operation must be earthed and insert the front tires be sure;
c) When delivery of LPG tank car must be parked at the station, in the location specified by the station. Parking position Turkish when export and import of LPG is convenient to connect the tube and the valve operation, head back to the exit. The exit of the airport does not have prevented delivery of LPG throughout the process.
3. Safety rules when LPG tank wagons for express delivery

When delivery of LPG for the Turkish train wagons have to be fixed tank wagons with brakes; The wagon Turkish must be arranged so that the tank's valve in the box on the same side of the train.
Article 40. Shipping safety regulations LPG tank 1. LPG tank transportation by means of road a) drivers Turkish must complete executive regulations of the road traffic industry in transportation of dangerous goods;
b) parking not Turkish freighter overnight parking, are in public places, in the curb in time 2 hours, except in cases of damaged tank car or waiting at the point of delivery and must ensure:-parking Not under power lines;
-Parking is far away from residential areas to a minimum of 15 m;
-Keep away from the flame of the ceiling;
-Keep away from the flammable, explosive.
2. LPG tank transportation by rail vehicles, safety of waterway forwarding, transporting LPG with tank by means of the railways, waterways must comply with current regulations.
Chapter 9.
Control stations containing A bottle of LPG Article 41. General rules for inspection stations, LPG bottle contains 1. Control stations containing bottles of LPG should have legal personality and be issued a certificate of eligibility LPG bottle contains auditing as defined in point c paragraph 1 Article 56 of Decree 107/2009/ND-CP DATED. 2. Control stations containing LPG cylinders must satisfy the conditions prescribed in article 43 of this circular.
3. the procedure for certification of eligibility test bottles are made according to the provisions of article 45 of this circular.
4. Inspection Station bottle contains LPG LPG business establishments in there own the bottle contains only periodic inspection of LPG cylinders contain LPG owned the facility.
Article 42. Regulation concerning LPG bottle contains 1. Periodic inspection of LPG bottle contains as specified by the manufacturer but not exceeding 5 years period compared to the nearest inspection times. With the bottle used over 20 years, periodic inspection period not exceeding 2 years.
2. To clean the surface of the bottle when making periodic auditing. To make painted bottles and bottle valve replacement when periodic auditing.
3. To conduct the test bottle contains LPG according the steps specified in the approved audit process.
43 things. The conditions to be a qualifying certification test bottle contains inspection stations, LPG bottle containing LPG just being certificate of eligibility test bottle contains LPG when ensuring the following requirements: 1. Must have adequate safety provisions, auditing processes LPG bottle contains is headed for approval under the rules.
2. Having full necessary equipment serves for inspection, specifically: a) LPG recovery equipment left in the bottle;
b) metal thickness gages, ultrasound welding;
c) removable bottle valves;
d) test equipment durable, airtight test;
DD) equipment to remove water;
e) control equipment inside;
g) surface cleaning equipment;
h) Mass Balance;
I) seal equipment;
k) vacuum equipment.
All the devices on the right contains the specifications and performance consistent with the auditing capacity of the station.
3. Have full manpower needed for the inspection service.
Direct staff to perform inspection of bottles must be professional training and safety inspection in bottles and have a minimum work experience of 2 years.
4. Must have adequate fire protection projects are approved, the fire fighting equipment as specified.
Article 44. Records suggest the certification eligibility verification.
Records suggest the certification eligibility verification include: 1. the certification application is eligible for LPG bottle contains control station according to the form prescribed in annex 4 of this circular.
2. A copy of the business registration certificate or decided to form the unit.
3. The list of officers, workers control stations, mission assignment decisions.
4. Copy of certificate of safety training, expertise, training of fire officers, workers control stations.
5. list of equipment for inspection bottles.
6. list of operating procedures and safety rules on the control device.
7. process of bottle calibration inspection stations, control stations, safety regulations.
Article 45. Procedure for certification of eligibility test LPG bottle contains 1. Basis of control stations containing LPG bottle filed directly or sent by post recommended records issued a certificate of eligibility to the LPG bottle contains auditing Industry (technical safety Bureau and industrial environment).
2. The Bureau of safety and environmental engineering industry check the validity, completeness of your profile. Case records are not complete, valid, within 5 (five) working days, notice in writing to the facility to complete the profile.
3. within 7 (seven) working days from the date of receiving documents, safety engineering Bureau and the industrial environment review, evaluation and Industry certification eligibility verification LPG bottle contains the form attached in annex 5 of this circular.
4. Certificate of eligibility verification is provided for each bottle containing LPG inspection stations and effect 2 (two) years from the date of issue. Before the expiration of the certificate (June), the basis of control stations send records of Industry recommended the certification of eligibility for the next term.
Chapter 10.
Production facilities, repair the bottle contains A LPG Article 46. Common rules for production, repair of LPG bottle contains 1. Production facilities, repair the bottle containing LPG should have legal personality and be certified eligible production, fix the bottle containing LPG as specified in point c paragraph 1 Article 56 of Decree 107/2009/ND-CP DATED. 2. Production facilities, repair the bottle containing LPG must meet all the conditions specified in article 47 of this circular.
3. the procedure for certification of eligible production, fix the bottle containing LPG is made according to the provisions of article 49 of this circular.
Article 47. The conditions to be granted the certificate of eligible production, fix the bottle containing LPG production facilities, repair the bottle containing LPG was granted the certificate of eligible production, fix the bottle containing LPG when ensuring the following requirements: 1. Have adequate regulations on safety, the process produced the bottle containing LPG and quality control processes the following products manufactured, has been head of the Department for approval.
2. Have the test equipment to meet the requirements of safety and quality check the bottle containing LPG after manufacture, specifically: a) pressure test system: create a pressure of not less than 3 MPa;
b) system check tightness of gas;
c) non-destructive test equipment: equipment check the quality of welds, Ultrasonic Thickness Gages;
d) control equipment, computer components of the material the bottle;
volume measuring device);
e) angular measuring device.
3. Have full manpower to operate the equipment test and welder meet the requirements: a) technical staff to operate the test equipment must be professional training, technical safety training under the provisions;
b) welder LPG bottle contains must have welding certificates according to the pressure equipment regulations.
4. Must have adequate fire protection projects are approved, the fire fighting equipment as specified.
Article 48. Records suggest that certification of eligible production, fix the bottle containing LPG recommended records issued the certificate of eligible production, fix the bottle containing LPG consists of: 1. the certification application be eligible according to the form prescribed in annex 6 of this circular;
2. A copy of the business registration certificate or decided to form the unit.
3. A list of the technical staff, the staff operate the test equipment, the pressure welder.
4. Copy of certificate of safety training and expertise of the technical staff, the staff operate the test equipment, the pressure welder.
5. list of equipment for inspection bottles containing LPG.
6. list the processes and rules of safety built LPG bottle contains.
7. process produced a bottle containing LPG (including calculating the tensile strength).
8. quality control process the following bottles produced.
Article 49. Procedure for certification of eligible production, fix the bottle containing LPG 1. Production facilities, repair the bottle containing LPG filed directly or send by post the profile recommended certification of eligible production, fix the bottle containing LPG to Industry (technical safety Bureau and industrial environment).
2. The Bureau of safety and environmental engineering industry check the validity, completeness of your profile. Case records are not complete, valid, within 5 (five) working days, notice in writing to the facility to complete the profile.
3. within 7 (seven) working days from the date of receiving documents, safety engineering Bureau and the industrial environment review, evaluation and Industry certification eligible production, fix the bottle containing LPG form in annex 7 attached to this circular.
4. The certificate of eligible production, fix the bottle containing LPG in effect for 5 years from the date of grant. Before the expiration of the certificate (May 1st), production facilities, repair the bottle containing LPG posted records of Industry recommended the certification of eligibility for the next term.
Chapter 11.
Implementation article 50. The responsibility of the Bureau of safety and environmental engineering industry 1. The Organization directs, guides, check the safe in the LPG sector.
2. Approve the risk assessment report, the emergency response plan the basis exists that contains LPG, LPG stations, LPG stations into the bottle at the car, LPG supply stations in State enterprises hold shares dominated by the ministries or the total investment and trading company which represented State capital owner businesses invested abroad.
3. Receiving records, appraised the leadership of Ministries approved the certification of eligibility for LPG bottle contains inspection stations; Production facilities, repair the bottle containing LPG.
Article 51. The responsibility of directing the market administration and market management forces in coordination with the relevant authorities inspect, monitor the LPG business establishments, organizations and individuals involved in the country on the implementation of the provisions of this circular and the provisions of other relevant laws on the business of LPG.

Article 52. The responsibility of the Department of industry and trade of the province, the city in Central 1. Instructions and check the implementation of the regulations on safety in the field of LPG for LPG business establishments on the management.
2. Approve the risk assessment report, the emergency response plan the basis exists that contains LPG, LPG stations, LPG stations into the bottle into the LPG supply stations, cars belonging to local business managers in addition to the provisions of article 50 clause 2 of this circular.
3. Certificate of eligibility on the LPG bottles, qualified certificate in automotive LPG, certificates of eligibility issued LPG, qualified certificate stores selling LPG under the provisions of Decree No. 107/2009/ND-CP. 4. Holding checked and certified technical trainer for who controls transport, escorts, storekeepers, LPG store employees as prescribed.
Article 53. Transitional provisions 1. For the existing facility contains LPG, LPG stations, LPG stations into the bottle in the generating car, LPG was active before the day this circular effect, if it does not meet the requirements of this circular must then apply the fix it solution and enhanced safety measures.
2. After the time limit of 5 years from the date of this circular, all LPG business establishments prescribed in paragraph 1 of this article are fully implementing the provisions of this circular.
Article 54. Terms of implementation 1. In case there are different regulations about the safe distance in the legal text, the national technical regulation shall apply according to the legal texts, the national technical regulation specialized LPG or legal text, the national technical regulation that requires higher.
2. This circular is effective from February 1, 2012.