Release (1958:558) On Electrical Low-Voltage Management Organisation In Relation To Heavy Duty

Original Language Title: Kungörelse (1958:558) om elektrisk svagströmslednings anordnande i förhållande till starkströmsledning

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$40 per month.
1 § with electronic low-voltage management is understood to

communications (telephone, telegraph or radio) or for

signalling, operation, measurement or other similar purposes, in

What electric current do not have such power,

power strength or frequency that can be dangerous for the person, pet

or property.



With electric heavy duty, of course, the direction in which the

electric power has such voltage, current or frequency

that could be dangerous for persons, animals or property. Voltage

as nominal amounts to a maximum of 1,000 volts AC voltage between

phase conductor or a maximum of 1 500 volts DC voltage between poles is called

low voltage. Is the nominal voltage higher than currently

been said, is called the high voltage.



It is up to the Swedish National Electrical Safety Board pursuant to

the provisions of the first and second subparagraphs, determine if the electric

management is attributable to the low-voltage or high current wiring.

Regulation (1994:301).



section 2 of this notice on the temporary non-application owns

the low-voltage line anlägges of the military squad. In the case of the organisation

of such management owns the armed forces as thereupon especially

provided, after consultation with the Swedish National Electrical Safety Board, issue the requisite

provisions. Regulation (1994:676).



section 3 of The framdraga, which intends to low-current led, in the following cases

notify the holders of existing heavy duty,

except where noted below, for consultations on appropriate safeguards:



(a)) when the low-voltage cable must be placed in the air so that it crosses

air management for strong current or otherwise framdragas in the air so near

such a direction that, if the post or other support falls or leader

failure or defects in either line, the second line may be damaged

or strong current may överledas to the low-voltage wire;



(b)) when the low-voltage cable must be placed in the earth so that it crosses

free management of strong current with a voltage of at least forty thousand volts; as well as the



c) when the low-voltage wire holder otherwise than in a) or (b))

means has reasonable grounds to expect that his leadership might be

be exposed to dangerous effect by induction or elevated

markpotentialer from management in power construction, in which

in single phase error may be encountered Earth's tilt power with greater strength than

five hundred amperes, or that his leadership might be exposed to

dangerous impact through influence from the leadership of the strong current at higher

voltage than one hundred thousand volts.



section 4 of the notification pursuant to paragraph 3 (a)), or (b)) required non



(a)) when the air management for weak current, dragas over such air management for

low voltage which is equipped with protective wire;



(b)) when the low-current led to heavy duty framdragas and under

uppläggas on poles for existing low-current led, unless for

This done protection device non need to be amended to protect likewise

the new management threads; or



c) when the low-voltage cable for the fulfilment of the railway or tramway

needs to be framdragas in the Earth in the rail or the area.



Electrical safety authority possesses, in other cases, authorize derogations from paragraph 3 of the

statutory notification requirement. Regulation (1992:1517).



paragraph 5 of the Radio antenna which forms low-current leadership may not so objectives that

It crosses the already existing air management for strong current, or otherwise so

in relation to this, the risk of such damage

or conduction as in section 3 (a)).



Electrical safety authority owns authorize derogations from regulation to antenna not

may cross the air line for strong current. Regulation (1992:1517).



section 6 of the holder of the radio antenna that in paragraph 5 of the said is required to withstand, to this

no cost or other inconvenience to him, be altered or moved, where

so as a result of starkströmslednings framdragande required to

prevent injury or conduction as in section 3 (a)).



section 7 of the Necessary protective device between low-current management and

high current wiring and duct device independent in relation to

both lines, it shall be deemed to form part of duty power supply.



section 8, low-current management shall be carried out with and be maintained at an acceptable

technical standard. To management hearing protective device shall be kept in

such a condition, that the protection device is intended to provide non-

compromised.



§ 9 in the area with detailed plan, the air management for weak current at

crossing with such existing air management for low voltage which is equipped

with protective wire is pulled forward over the low-voltage lead and otherwise placed

at such a height above the ground which is provided by the Electrical safety authority.



Are low-current management of air cable, it may, however, be placed in

the low-voltage line, if the necessary protective measures are taken.

Electrical safety authority, in other cases, admit that the low-voltage line drawn

during the low-voltage lead. Regulation (1992:1517).



section 10 Where air management for weak current is been introduced in the area of

detailed plan, holders of management, where necessary to

free guide for low-voltage is to be together with the protective wire is pulled out from under the

the low-voltage wire, required to at the expense of the low-voltage wire

owners raise their management at the intersection rather than to no more than nine meters

above the ground, in terms of management's lowest conductors at a temperature of

+ 50 degrees Celsius. Regulation (1987:182).



section 11 if the detailed plan has been adopted for the area in which air line

for low voltage and low voltage overhead line drawn up, is

the low-voltage wire holders required to change their management to

cables are to be satisfactory from a safety point of view

arranged on the Swedish National Electrical Safety Board finds that the change is needed. Regulation

(1992:1517).



section 12 of the regulations on low-voltage management organisation

in relation to high current wiring, needed beyond what

provided for in this Decree, shall be communicated by the

Electrical safety authority after consultation with the Swedish Post and Telecom Agency

and the Transport Department.



Holders of the low-voltage lead is required to comply with the

special conditions in respect of the management's organisation in

relation to high current wiring, which for security reasons

decided by the electrical safety authority. Regulation (2010:116).



section 13 has been repealed by Regulation (1992:1517).



14 repealed by Regulation (1992:1517).