Key Benefits:
This regulation is intended to achieve a sufficient degree of safety in the event of fire in industrial facilities and facilities.
The presence of fire risk in industrial establishments determines the likelihood of fires, damage and loss generators for people and property, which affect both themselves and your environment.
The basic standard of construction, approved by Royal Decree 2177/1996 of 4 October, lays down the conditions to be met by buildings, excluding those for industrial use, to protect their occupants against risks caused by a fire and to prevent damage to third parties.
The regulation of the conditions to be met by equipment, equipment and systems, as well as their installation and maintenance, in addition to the regulation of installers and maintainers, is provided for in the Regulation of installations. of fire protection, approved by Royal Decree 1942/1993 of 5 November, and in the Order of 16 April 1998.
The Ministry of Industry, Tourism and Trade also deals with regulating fire protection conditions in industrial establishments with a horizontal character, i.e. of industrial activity.
The Third Chamber of the Supreme Court, by the judgment of 27 October 2003, in estimating the administrative dispute-administrative action n ° 495/2001, declares, by default of form, the previous fire safety regulation in the industrial establishments, approved by Royal Decree 786/2001 of 6 July 2001.
Article 12 of Law 21/1992 of 16 July 1992 on Industry deals with the general content of the safety regulations and provides for the instruments necessary for the implementation of this Regulation in respect of the competencies corresponding to other public administrations.
According to them, this regulation is structured in such a way that the regulation meets the basic requirements of a general nature, in order to develop in its annexes the applicable criteria, conditions and requirements technical and therefore subject to possible changes resulting from its development.
This royal decree has been subject to the procedure of information in the field of technical norms and regulations and regulations concerning the services of the information society, regulated in Royal Decree 1337/1999, For the purpose of implementing the provisions of Directive 98 /34/EC of the European Parliament and of the Council of 22 June 1998, as amended by Directive 98 /48/EC of the European Parliament and of the Council of 20 July 1998, 31 July 1998.
This royal decree is approved in the exercise of the powers that, in relation to the matter of industrial safety, have come to attribute expressly to the General Administration of the State the totality of the Autonomy, as has been repeatedly stated in the case law of the Constitutional Court (for all of them, the Sentences of the Constitutional Court 2003/1992, of November 26, and 243/1994, of July 21).
In its virtue, on the proposal of the Minister of Industry, Tourism and Trade, in agreement with the Council of State and after deliberation of the Council of Ministers at its meeting on 3 December 2004,
DISPONGO:
Single item. Adoption of the Regulation.
The Fire Safety Regulation is approved in the industrial establishments, which is inserted below.
Additional disposition first. Technical Guide.
The leading industrial safety management centre of the Ministry of Industry, Tourism and Trade will develop and keep up to date a non-binding technical guide for the practical implementation of the provisions of the Regulation and its technical annexes, which may provide for clarification of general concepts. You will also authorize the use of recognized design guides for the justification of different technical solutions that provide an equivalent level of security.
Additional provision second. Self-protection and security management systems.
In compliance with the provisions of Article 5 of Law 2/1985 of 21 January, of Civil Protection, the Ministry of Industry, Tourism and Trade, according to the Ministry of the Interior, will determine the catalogue of activities In the case of the Commission, the Commission will be able to take the necessary steps to ensure that the Commission is able to take the necessary steps to ensure that the necessary measures are taken. risks, alarm, evacuation and distress. All this, regardless of the provisions of Law 31/1995 of 8 November, of the Prevention of Occupational Risks, and in their regulatory norms to the extent that they could affect the safety and health of workers, and in the Royal Decree 1254-1999 of 16 July 1999 approving measures to control the risks inherent in major accidents involving dangerous substances, as well as of the provisions amending or supplementing the abovementioned rules.
This will determine the industrial establishments that, precept, must implement the fire safety management system in the establishment and develop the corresponding safety manual. fire.
Single transient arrangement. Application regime.
The requirements of the regulation approved by this royal decree will apply, from its entry into force, to the new industrial establishments that will be built or implanted and those already existing that will be transferred, change or modify their activity.
These same requirements will apply to those industrial establishments where extensions or reforms involve an increase in their occupied area or an increase in the level of intrinsic risk.
These requirements will apply to the part affected by the extension or reform, which is generally considered to be the affected area or area of fire.
However, the competent body of the autonomous community may, if it considers it appropriate, require the application of the regulation to other sectors and areas of fire, or even to the industrial establishment as a whole.
The provisions of Chapter IV shall apply from the entry into force for all existing industrial establishments.
This regulation will not apply to this regulation:
(a) To the industrial establishments under construction and to the projects that have been applied for a license of activity at the date of entry into force of this royal decree.
b) To projects approved by public administrations or visas by professional associations at the date of entry into force of this royal decree.
(c) To works carried out in accordance with the projects referred to in paragraph (b), provided that the activity licence is requested within six months of the date of entry into force of this royal decree.
However, the projects and installations referred to in the preceding paragraphs may be adapted, in whole or in part, to this Regulation.
Final disposition first. Competence title.
This royal decree constitutes a regulatory standard of industrial security, which is dictated by the provisions of Article 149.1.13. of the Constitution.
Final disposition second. Faculty of development.
The Minister of Industry, Tourism and Trade is empowered to make the necessary provisions for the development and enforcement of this royal decree.
Final disposition third. Entry into force.
This royal decree will enter into force within 30 days of its publication in the "Official State Gazette".
Given in Madrid, 3 December 2004.
JOHN CARLOS R.
The Minister of Industry, Tourism and Trade,
JOSE MONTILLA AGUILERA
SECURITY REGULATION AGAINST FIRES IN INDUSTRIAL ESTABLISHMENTS
CHAPTER I
Object and Scope
Article 1. Object.
This regulation aims to establish and define the requirements to be met and the conditions to be met by establishments and industrial facilities for their safety in the event of fire, to prevent its appearance and to give the appropriate response, in the event of occurrence, to limit its spread and to enable it to be extinguished, in order to cancel or reduce the damage or losses that the fire may cause to persons or property.
Fire prevention activities will aim to limit the presence of the fire risk and the circumstances that may trigger the fire.
Fire response activities will aim to control or fight the fire, to extinguish it, and to minimize damage or loss it may generate.
This regulation will apply, in addition, to the fire protection measures laid down in the existing provisions governing industrial, sectoral or specific activities in the non- which are provided for in them, which will be fully implemented in their field.
In this regard, the provisions of the supplementary technical instruction MIE APQ-1 of the Regulation on the storage of chemicals, approved by Royal Decree 379/2001 of 6 April, and those provided for in the Technical instructions of the Regulation of oil installations, approved by Royal Decree 2085/1994 of 20 October, are of complete application for the compliance of fire safety requirements.
The conditions set out in this regulation will have the minimum required condition as indicated in article 12.5 of Law 21/1992, of July 16, of Industry.
These minimums are considered to be met:
a) For compliance with the requirements stated in this regulation.
b) By application, for particular cases, of equivalent safety techniques, according to standards or design guides of recognized prestige for the justification of the equivalent technical safety solutions adopted, which must provide at least one level of security comparable to the previous one. This application of equivalent safety techniques shall be duly justified by the project and resolved by the competent authority of the autonomous community.
(c) When the implementation of an industrial establishment takes place in industrial estates with urban planning approved before the entry into force of this regulation or in an existing building in which by its the characteristics cannot be met by any of the regulatory provisions or adapted to subparagraph (b) above, the holder of the establishment must submit to the competent authority of the autonomous community an application for derogation and justify it by its description in the project or technical memory in which the alternative measures taken. The competent authority of the autonomous community in which the industrial establishment is located, in the light of the arguments put forward in the draft or the technical memory, may reject the application, require amendment of the measures alternatives or grant exception authorization, which will always be expressed.
The acceptance of the different technical solutions that are used to provide a general response, that is, of application throughout the territory of the State, will be carried out in accordance with paragraph 1 of the final provision first, by ministerial order.
Article 2. Scope.
1. The scope of this regulation is the industrial establishments. They shall be understood as such:
(a) Industries as defined in Article 3.1 of Law 21/1992 of 16 July of Industry.
b) The industrial storage.
(c) Repair workshops and parking lots of vehicles for the transport of persons and goods transport.
(d) The ancillary or ancillary services of the activities covered by the preceding paragraphs.
2. It shall also apply to all storage of any type of establishment when its total fire load, calculated according to Annex I, is equal to or greater than 3 million Megajoules (MJ).
It will also apply to existing industries prior to the entry into force of this Regulation when their intrinsic risk level, situation or characteristics pose a serious risk to persons, property or property. environment, and thus be determined by the competent autonomic administration.
3. Activities in nuclear establishments or installations, radioactive materials, mineral extraction, agricultural activities and facilities for military uses are excluded from the scope of this regulation.
Equally, industrial activities and craft workshops and similar workshops whose fire load density, calculated in accordance with Annex I, does not exceed 10 Mcal/m2 (42) are excluded from the application of this regulation. MJ/m2), provided that its useful surface is less than or equal to 60 m2, except as specified in paragraphs 8 and 16 of Annex III.
Article 3. Regulatory compatibility.
1. Where, in the same building, other uses with different ownership coexist with the industrial activity, for which the basic building standard applies: fire protection conditions, NBE/CPI96, or equivalent regulations, The requirements to be met by non-industrial spaces shall be those required by such legislation.
2. Where, in an industrial establishment, other uses of the same ownership, for which the basic building standard applies: fire protection conditions, or equivalent rules, are co-exist with the industrial activity; the requirements to be met by non-industrial spaces shall be those required by that regulation when they exceed the limits set out below:
a) Trade zone: built surface greater than 250 m2.
b) Administrative zone: built surface greater than 250 m2.
c) Meeting rooms, conferences, projections: capacity exceeding 100 people seated.
d) Files: built surface greater than 250 m2 or volume greater than 750 m3.
e) Bar, cafeteria, dining room and kitchen: built area over 150 m2 or capacity to serve more than 100 diners simultaneously.
f) Library: built surface greater than 250 m2.
g) Personnel accommodation zones: capacity exceeding 15 beds.
The areas to which the requirements of the relevant regulations are applicable must constitute an independent fire sector.
CHAPTER II
Implementation, construction, and commissioning regime
Article 4. Construction and implementation projects.
1. Newly constructed industrial establishments and those which change or modify their activity, are moved, extended or reformed, in the part affected by the extension or reform, as set out in the single transitional arrangement, require the submission of a project, which may be integrated into the general project required by the legislation in force for obtaining the required permits and licenses, or be specific; in any case, it shall contain the documentation necessary to justify compliance with this regulation.
2. The project, which will be drafted and signed by a qualified technician and endorsed by its official college, should indicate, in accordance with the Regulation of fire protection facilities, approved by the Royal Decree 1942/1993 of 5 November 1998, and with the Order of 16 April 1998, the materials, equipment, equipment, systems or their components subject to a mark in accordance with rules included in the project.
The class or level of performance shall also be indicated in the light of the fire of the construction products that so require.
3. The project may be replaced by a technical memory signed by a qualified technician in the following cases:
a) Low intrinsic risk industrial facilities and useful surface less than 250 m2.
b) Industrial activities, craft workshops and similar with fire load equal to or less than 10 Mcal/m2 (42 MJ/m2) and a useful surface equal to or less than 60 m2.
c) Reforms that, as set out in the single transitional provision, do not require the application of this regulation.
Article 5. Setting up of the industrial establishment.
For the implementation of the industrial establishments referred to in the previous article, the presentation, before the competent authority of the autonomous community, of a certificate, issued by a technician, is required. (a) entitled 'competent' and 'endorsed' by the relevant official college, in which the adequacy of the facilities to the project is made clear and the compliance with the relevant regulatory technical requirements and requirements for the project; record the referred installation.
This certificate must also include the intrinsic risk level of the industrial establishment, the number of sectors and the intrinsic risk of each of them, as well as the constructive characteristics that justify the compliance with the provisions of Annex II; it shall also include a certificate of the authorised installing/s/s, signed by the appropriate competent technician, of the premises which, in accordance with Royal Decree 1942/1993, of 5 November, they need to be performed by an authorized installation company.
CHAPTER III
Periodic Inspections
Article 6. Inspections.
Regardless of the inspector's function assigned to the competent public administration in the field of industry of the Autonomous Community and the maintenance operations provided for in the Regulation of fire protection, approved by Royal Decree 1942/1993 of 5 November, the holders of the industrial establishments to which this regulation applies shall request a control body empowered for the application of this regulation the inspection of their facilities.
This inspection will check:
a) That no changes to the activity or extensions have occurred.
b) That the typology of the establishment, the sectors and/or areas of fire and the intrinsic risk of each one continue to be maintained.
(c) Fire protection systems are still required and maintenance operations are carried out in accordance with the requirements of Appendix 2 to the Fire Protection Facilities Regulation, approved by Royal Decree 1942/1993 of 5 November.
In establishments partially adapted to this regulation, the inspection will be performed only on the affected party.
Article 7. Periodicity.
1. The frequency with which such inspections shall be carried out shall not exceed:
a) Five years, for low-intrinsic risk establishments.
b) Three years, for medium intrinsic risk establishments.
c) Two years, for high intrinsic risk establishments.
2. A record shall be drawn up of those inspections, signed by the competent authority of the inspection body which has carried out the inspection and by the operator or technician of the industrial establishment who shall keep a copy.
Article 8. Special inspection programmes.
1. The management body responsible for industrial safety of the Ministry of Industry, Tourism and Trade may promote, after consultation with the Council for the coordination of industrial safety, special inspection programmes for industrial sectors or industries where it considers it necessary to contrast the degree of application and compliance with this regulation.
2. These inspections shall be carried out by the competent bodies of the autonomous communities or, if they so establish, by control bodies empowered to implement this Regulation.
Article 9. Corrective measures.
1. If, as a result of the inspections referred to in Articles 6 and 8, deficiencies are observed in compliance with the regulatory requirements, the time limit for the implementation of the appropriate corrective measures shall be indicated; Deficiencies are a serious and imminent risk, the control body shall communicate them to the competent body of the autonomous community for appropriate knowledge and effects.
2. In any industrial establishment there shall be documentary evidence of compliance with the preventive maintenance programmes of the existing fire protection means carried out in accordance with the provisions of Appendix 2 to the Regulation. of fire protection facilities, approved by Royal Decree 1942/1993 of 5 November 1993, of the deficiencies observed in their compliance, as well as of the inspections carried out in compliance with the provisions of this regulation.
CHAPTER IV
Take action in case of fire
Article 10. Fire communication.
The holder of the industrial establishment must inform the competent authority of the autonomous community, within the maximum period of 15 days, of any fire occurring in the industrial establishment in which it is located. less, one of the following circumstances:
a) That personal damages that require external medical attention occur.
b) Which causes a total cessation of industrial activity.
(c) A partial cessation of more than 14 days of industrial activity is caused.
d) resulting in material damage exceeding 30,000 euros.
Article 11. Fire investigation.
In all fires in which the circumstances provided for in paragraphs (a), (b) or (c) of the previous Article are present, the competent authority of the autonomous community shall carry out a detailed investigation in order to to ascertain its causes, and shall forward it to the competent industrial safety management body of the Ministry of Industry, Tourism and Trade.
In order to carry out such research, you may require the assistance of specialists such as the Fire Corps, competent organizations or technicians.
All this, without prejudice to the sanctioning dossier which may be initiated for alleged statutory infringements and the responsibilities which may arise if the conduct of the inspections is verified non-compliance regulatory requirements in Chapter III and/or the maintenance operations provided for in Appendix 2 to the Fire Protection Facilities Regulation, as approved by Royal Decree 1942/1993 of 5 November.
CHAPTER V
Conditions and requirements to be met by industrial establishments in relation to their fire safety
Article 12. Characterization.
The conditions and requirements to be met by industrial establishments, in relation to their fire safety, will be determined by their configuration and location in relation to their environment and their level of risk intrinsic, fixed as set out in Annex I.
Article 13. Construction conditions.
The constructive and building conditions and requirements to be met by industrial establishments, in relation to their fire safety, shall be as set out in Annex II, in accordance with the resulting from Article 12.
Article 14. Facility requirements.
1. All appliances, equipment, systems and components of fire protection facilities of industrial establishments, as well as the design, execution, commissioning and maintenance of their installations, shall comply with the requirements of this Directive. the provisions of the Regulation on fire protection installations, approved by Royal Decree 1942/1993 of 5 November 1993, and the Order of 16 April 1998, on rules of procedure and the development of that order.
Installers and maintainers of fire protection facilities, as referred to in the preceding paragraph, shall comply with the requirements laid down by the Fire Protection Facilities Regulation, approved by Royal Decree 1942/1993 of 5 November 1993 and the provisions which complement it.
2. The conditions and requirements to be met by the fire protection facilities of industrial establishments in relation to their fire safety shall be those laid down in Annex III, in accordance with the characterisation of the resulting from Article 12.
Article 15. Normalization.
1. Technical annexes refer to standards (UNE, EN or other standards), in whole or in part, to facilitate adaptation to the state of the art at any given time.
This reference is usually made without indicating the year of editing of the rule in question.
Annex IV lists all the rules cited in the text identified by their titles and numbering, which includes the year of editing.
When one or more rules vary in their year of editing, they must be updated in the list of rules, by means of an order from the Minister of Industry, Tourism and Trade, in which the date from which the use of the new edition of the standard will be valid and the date from which the use of the old edition of the standard will cease to be, for regulatory purposes.
In the absence of an express resolution, it will be understood that it also complies with the regulatory conditions for the edition of the standard after the one listed in the list of standards, provided that it does not modify basic criteria and is limited to update tests or increase the intrinsic safety of the material concerned.
2. For the purposes of this Regulation and the placing on the market of products within the framework of the Customs Union, subject to national industrial safety regulations, the competent public administration shall accept the validity of the certificates and marks in accordance with standard and the records or protocols of tests which are required by those regulations, issued by conformity assessment bodies officially recognised in those States, provided that they are recognizes, by the aforementioned competent public administration, that the aforementioned agents offer guarantees techniques, professionals and independence and impartiality equivalent to those required by Spanish legislation and that the legal provisions in force in the Member State in accordance with which conformity is assessed conduct a level of safety equivalent to that required by the corresponding Spanish provisions.
Construction products which are permanently incorporated into buildings, in accordance with their intended use, shall bear the CE marking provided that they have entered into force, all in accordance with the provisions of the Council Directive 89 /106/EEC of 21 December 1988 on the approximation of the laws, regulations and administrative provisions of the Member States relating to construction products, incorporated in our national legislation In the case of the Court of Law, the Court held that the Court of free movement of construction products pursuant to Directive 89 /106/EEC.
Article 16. Technical Guide.
The industry, tourism and commerce ministry's competent management centre will develop and keep up to date a non-binding technical guide for the practical application of the provisions of the the regulation and its technical annexes, which may provide for clarifications on general concepts.
CHAPTER VI
Liability and sanctions
Article 17. Non-compliance.
Failure to comply with this regulation will result in the responsibilities and penalties, if any, which correspond in accordance with the provisions of Title V of Law 21/1992 of 16 July 1992 on Industry, and in Chapter VI of Law 2/1985 of 21 January of Civil Protection and Section 2 of Chapter II of the recast of the Law on infringements and sanctions in the social order, approved by Royal Decree-Law 5/2000 of 4 August.
ANNEX I
Characterization of industrial establishments in relation to fire safety
1. Establishment.
The establishment of the building, building, area of the building, installation or open space of industrial use or warehouse, as provided for in Article 2, is intended to be used under an ownership differentiated and whose construction or reform project, as well as the start of the planned activity, is subject to administrative control.
Industrial establishments will be characterized by:
a) Your configuration and location in relation to your environment.
b) Your intrinsic risk level.
2. Characteristics of industrial establishments by their configuration and location in relation to their environment.
The many different configurations and locations that industrial establishments may have are considered to be reduced to:
2.1 Industrial establishments located in a building:
TYPE A: The industrial establishment partially occupies a building that has, in addition, other establishments, be they industrial use already of other uses.
TYPE B: the industrial establishment is fully occupied by a building which is attached to another building or other buildings, or at a distance of three metres from another or other buildings, from another establishment, whether these are for use industrial or other uses.
For industrial establishments that occupy a ship with a shared structure with the adjacent ones, which shall in any case have an independent cover, compliance with the requirements corresponding to the type shall be accepted. B, provided that it is technically justified that the possible collapse of the structure does not affect the adjacent ships.
TYPE C: the industrial establishment is fully occupied by a building, or several, if any, which is more than three metres away from the nearest building of other establishments. Such distance shall be free from combustible goods or intermediate elements liable to spread the fire.
2.2 Industrial establishments that develop their activity in open spaces that do not constitute a building:
TYPE D: The industrial establishment occupies an open space, which can be fully covered, some of whose facades are totally devoid of lateral enclosure.
TYPE E: The industrial establishment occupies an open space that may be partially covered (up to 50 percent of its surface), some of whose facades on the covered part are totally devoid of lateral enclosure.
TYPE A: common portant structure with other establishments
TYPE B
TYPE C
TIPOS D and E
2.3 Where the characterisation of an industrial establishment or part of an industrial establishment does not exactly match any of the rates defined in paragraphs 2.1 and 2.2, it shall be deemed to belong to the type with which it is best equating or justifiably assimilating.
In an industrial setting, different configurations can coexist, so the requirements of this regulation must be applied differently for each of them.
3. Characterization of industrial establishments by their intrinsic risk level.
Industrial establishments are classified according to their degree of intrinsic risk, taking into account the simplified criteria and according to the following procedures.
3.1 Industrial establishments, in general, will be made up of one or more configurations of types A, B, C, D and E. Each of these configurations will constitute one or more areas (sectors or areas of fire) of the industrial establishment.
1. For types A, B and C, the building space closed by fire-resistant elements during the time to be established in each case is considered to be 'fire sector'.
2. For types D and E, the surface they occupy is considered to be an open fire area, defined only by its perimeter.
3.2 The intrinsic risk level of each sector or area of fire will be assessed:
1. Calculating the following expression, which determines the density of fire load, weighted and corrected, of that sector or area of fire:
where:
Qs = fire load density, weighted and corrected, sector or fire area, in MJ/m2 or Mcal/m2.
Gi = mass, in kg, of each of the fuels (i) that exist in the sector or area of fire (including combustible building materials).
qi = calorific power, in MJ/kg or Mcal/kg, of each of the fuels (i) that exist in the fire sector.
Ci = dimensionless coefficient that weighs the degree of dangerousness (by the solubility) of each of the fuels (i) that exist in the fire sector.
Ra = dimensionless coefficient that corrects the degree of dangerousness (by activation) inherent in the industrial activity that develops in the fire, production, assembly, transformation, repair, storage, etc.
When there are several activities in the same sector, the risk factor for activation of the activity of higher activation risk is taken as a risk factor, provided that the activity occupies at least 10 percent of the surface area. of the fire sector or area.
A = built surface of the fire sector or busy area of the fire area, in m2.
The values of the hazard ratio by fuel, Ci, of each fuel can be deducted from Table 1.1, the CEA Catalogue of products and goods, or similar tables of recognized prestige whose use must be justified.
The values of the hazard ratio by activation, Ra, can be deducted from table 1.2.
The values of the calorific value qi, of each fuel, can be deducted from Table 1.4.
TABLE 1.1
Degree of hazardous fuels
Values of the hazard ratio by solubility, Ci
MEDIA | ||
---|---|---|
-Liquids classified as class A in the MIE-APQ1 ITC | -Liquids classified as subclass B2 in the MIE-APQ1. ITC | - Liquids classified as class D in ITC MIE-APQ1. |
-Classified liquids as subclass B1 in the MIE-APQ1. ITC | -Liquids classified as class C in ICE MIE-APQ1. |
|
-Solids capable of starting their combustion at a temperature of less than 100 ° C. | -Solids starting their ignition at a temperature between 100 ° C and 200 ° C. |
-Solids that begin their ignition at a temperature above 200 ° C |
-Products that can form explosive mixtures with air at room temperature. | -Solids that emit flammable gases. |
|
|
| |
i= 1.60 | Ci = 1.30 | Ci = 1.00 |
Note: ITC MIE-APQ1 of the Chemical Storage Regulation, approved by Royal Decree 379/2001 of 6 April.
2. As an alternative to the above formula the fire load density, weighted and corrected, Qs, can be evaluated from the fire sector by applying the following expressions.
a) For production, transformation, repair, or any other activities other than storage:
where:
Qs, Ci, Ra , and A have the same significance as in the previous section 3.2.1.
qyes = the fire load density of each zone with different processing according to the different processes that are performed in the fire sector (i), in MJ/m2 , or Mcal/m2.
Si = surface of each zone with different process and fire load density, qif different, in m2.
Average fire load density values, qyes, can be obtained from table 1.2.
Note: for the purposes of the calculation, the collection or storage of materials or products collected for the maintenance of the production processes of assembly, transformation or repair, or resulting thereof, is not accounted for. consumption or production is daily and constitute the so-called "day store". These materials or products shall be considered to be incorporated in the production process of assembly, processing, repair, etc., to which they are to be applied or from which they are carried out.
b) For storage activities:
where:
Qs, Ci, Ra , and A have the same significance as in the previous section 3.2.1.
qvi = fire load, contributed by each m3 of each zone with different type of storage (i) existing in the fire sector, in MJ/m3 or Mcal/m3.
hi = height of storage for each of the fuels, (i), in m.
si = floor space occupied by each zone with different type of storage (i) existing in the fire sector in m2.
The values of the fire load, per cubic meter qvi, contributed by each of the fuels, can be obtained from Table 1.2.
3.3 The intrinsic risk level of a building or a set of industries and/or fire areas of an industrial establishment, for the purposes of applying this regulation, will be assessed by calculating the following expression, which determines the density of fire load, weighted and corrected, Qe, of that industrial building.
where:
Qe = fire load density, weighted and corrected, of the industrial building, in MJ/m2 or Mcal/m2.
Qyes = fire load density, weighted and corrected, for each of the sectors or areas of fire, (i), which make up the industrial building, in MJ/m2 or Mcal/m2.
Ai = the constructed surface of each of the sectors or areas of fire, (i), which make up the industrial building, in m2.
3.4 For the purposes of this Regulation, the intrinsic risk level of an industrial establishment, when it develops its activity in more than one building, located in the same enclosure, shall be assessed by calculating the following expression, which determines the fire load, weighted and corrected, QE, of that industrial establishment:
where:
QE = fire load density, weighted and corrected, of the industrial establishment, in MJ/m2 or Mcal/m2.
Qei = the weighted and corrected fire load density of each of the industrial buildings, (i), which make up the industrial establishment in MJ/m2 or Mcal/m2.
Aei = constructed surface of each of the industrial buildings, (i), which make up the industrial establishment, in m2.
3.5 Devalued the weighted fire load density, and corrected for a fire sector or area, (Qs), an industrial building (Qe), or an industrial setting (QE), according to any of the the procedures set out in paragraphs 3.2, 3.3 and 3.4 respectively, the intrinsic risk level of the fire sector or area, of the industrial building, or of the industrial establishment, is deducted from Table 1.3.
3.6 For the intrinsic risk assessment, the use of recognised assessment methods can also be used; in this case, the method used should be justified in the project.
TABLE 1.2
Average fire load density settings for various industrial processes, product storage and associated activation risk, Ra
Activity | Manufacturing and Selling | Storage | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
s | Ra | qv | Ra | ||||||||
MJ/m2 | Mcal/m2 | MJ/m3 | Mcal/m3 | ||||||||
| 200 | 48 | 1.5 | 200 | 48 | ||||||
1,000 | 1,000 | 240 | 2.0 | 18,900 | 4.543 | 2.0 | |||||
edible oils, expedition | 900 | 216 | 1.5 | 18,900 | 4,543 | ||||||
Aceites: mineral, vegetable, and animal | 1,000 | 240 |
2.0 | 18,900 |
| ||||||
40 | 40 | 40 | 40 |
|
|
| |||||
Steel, needles | 200 | 48 | 1.0 |
|
|
| |||||
Acethylene, bottle filling | 700 | 168 |
|
|
| ||||||
40 | 40 | 10 |
|
|
|
| |||||
| 19 | 80 |
1.0 |
|
|
| |||||
| 96 | 1.5 | 800 | 192 | 1.5 | ||||||
Accumulators, Expedition | 800 | 192 | 1.5 |
|
|
| |||||
oxygenated Water | Special | Special | Special | Special |
|
|
|
| |||
| 72 | 1.0 | 300 | 1.0 |
| 240 | 240 | 2.0 |
|||
-isolated metal wire | 80 | 19 | 1.0 |
|
|
| |||||
Pottery | 200 | 48 |
|
|
|
| |||||
300 | 72 | 1.5 | 300 | 1.5 |
| 264 | 264 | 2.0 | |||
Cotton, warehouse of |
|
|
| 1,300 | 313 | 2.0 | |||||
800 | 192 | 1.5 | 800 | 192 | 1.5 | ||||||
| 240 | 2.0 |
|
|
| ||||||
, raw materials |
|
|
|
3,400 | 817 | 2.0 | |||||
Food, pre-cooked dishes | 200 | 48 |
|
|
|
| |||||
Workshops, etc. | 1,200 | 288 | 2.0 |
|
|
| |||||
Starch | 2,000 | 481 | 2.0 |
|
|
| |||||
|
|
| 3,400 | 817 | 2.0 | ||||||
Renting, products | 800 | 192 | 1.5 | 3,400 | 817 | 2.0 | |||||
ovens | 40 | 10 | 1.0 |
|
|
| |||||
40 | 10 | 1.0 |
|
|
| ||||||
, work from | 200 | 48 | 1.0 |
|
|
| |||||
Antiquities, Sale of | 700 | 168 | 1.5 |
|
|
| |||||
appliances, manufacturing | 300 | 72 | 1.0 | 200 | 48 | 1.0 | |||||
, Sale | 400 | 96 | 1.0 |
|
|
| |||||
Tv appliances | 300 | 72 | 1.0 | 200 | 48 | 1.0 | |||||
appliances | 300 | 72 |
1.0 | 200 | 48 | 1.0 | |||||
Appliances | 400 | 96 | 1.0 | 400 | 96 | 1.0 | |||||
appliances, repair | 500 | 120 | 1.0 |
|
|
| |||||
appliances | 400 | 96 | 1.0 | 400 | 96 | 1.0 | |||||
appliances, repair | 500 |
120 | 1.0 |
|
|
| |||||
Photo Appliances | 300 | 72 | 1.0 | 600 | 144 | 1.5 | |||||
appliances | 400 | 96 |
1.0 |
|
|
| |||||
appliances, build | 300 |
72 | 1.0 |
|
|
| |||||
Healthcare appliances, workshop | 100 | 24 | 1.0 |
|
|
| |||||
Appliances, expedition of | 700 | 168 | 2.0 |
|
|
| |||||
Appliances, test | 200 | 48 | 1.0 |
|
|
| |||||
Appliances, repair shops | 600 | 144 | 1.0 |
|
|
| |||||
, | 200 buildings | 48 | 1.5 |
|
|
| |||||
Purposes, Articles Manufacturing | 400 |
96 | 1.5 | 800 | 192 | ||||||
Files |
| 1.010 | 2.0 | 1,700 |
409 | 2.0 | |||||
1,000 | 240 | 2.0 | 300 |
72 | 1.0 | ||||||
| 300 | 72 | 1.0 |
|
|
| |||||
Items | 200 |
48 | 1.0 |
|
|
| |||||
80 | 80 | 19 |
|
|
|
|
| ||||
80 | 19 | 80 |
1.0 |
|
|
| |||||
Metal Items, Amolated | 80 | 19 | 1.0 |
|
|
| |||||
items, varnished | 300 | 72 |
|
|
|
| |||||
Items, locksmith | 200 | 48 |
1.0 |
|
|
| |||||
Metal Items, Chat | 80 | 19 | 1.0 |
|
|
| |||||
| 80 | 19 |
|
|
|
| |||||
100 | 100 | 24 |
1.0 |
|
|
| |||||
Metal Items, Forged | 80 | 19 | 1.0 |
|
|
| |||||
items, milling | 200 | 48 |
|
|
|
| |||||
40 | 10 |
1.0 |
|
|
| ||||||
Metal Items, Write | 200 | 48 | 1.0 |
|
|
| |||||
Items, Welding | 80 | 19 |
|
|
|
| |||||
|
72 | 72 |
1.0 |
|
|
| |||||
Special | Special | Special | Special | 2,000 | 481 | ||||||
Aserraders | 400 | 96 | 1.5 |
|
|
| |||||
Asmissing (bidons, blocks) |
|
|
| 3,400 | 817 | 2.0 | |||||
| 800 | 800 | 192 | 1.5 | 3,400 | 817 | |||||
Auto, coachwork | 200 | 48 |
|
|
|
| |||||
Automobiles, accessorial store |
|
|
| 800 | 192 | 1.5 | |||||
| 200 | 200 | 48 | 1.0 |
|
|
| ||||
Automobiles, garrison | 700 | 168 |
|
|
| ||||||
, Mount | 300 | 72 |
|
| |||||||
| 500 | 500 | 120 | 1.5 |
|
|
| ||||
, repair | 300 | 72 | 1.0 |
|
|
| |||||
Automobiles, accessorial sales | 300 | 72 |
1.0 |
|
|
| |||||
|
200 | 48 | 1.0 |
|
|
| |||||
Aircraft, hangars | 200 | 48 | 1.5 |
|
|
| |||||
Sugar |
|
|
|
2.019 | 2.0 | ||||||
800 | 192 | 1.5 | 800 | 192 | 1.5 | ||||||
Sulphur |
400 | 96 | 2.0 | 4,200 | 1,010 | 2.0 | |||||
Balances | 300 | 72 | 1.0 |
|
|
| |||||
600 | 600 | 600 | 144 | 1.5 |
|
|
| ||||
600 | 600 | 600 | 144 | 1.5 |
|
|
| ||||
Metal Boats | 200 | 48 | 1.0 |
|
|
| |||||
1.202 | 2.0 | 2,500 | 601 | ||||||||
2,000 | 2,000 | 481 | 2.0 | 5,000 | 1.202 | 2.0 | |||||
| 1,000 | 1,000 | 240 | 2.0 |
|
|
| ||||
Barnized | 80 | 19 | 1.5 |
|
|
| |||||
700 |
168 |
168 |
1.5 |
|
|
| |||||
Alcoholic Beverages, Sale | 500 | 120 | 1.5 | 800 | 192 | 1.5 | |||||
or no alcohol beverages | 80 | 19 | 1,0 | 125 | 30 | ||||||
not alcohol, expedition | 300 | 72 | 72 |
1.0 |
|
|
| ||||
Non-alcoholic beverages, fruit juices | 200 | 48 | 1.0 | 300 | 72 | 1.0 | |||||
Libraries | 2,000 | 481 | 1.0 |
2,000 | 481 | ||||||
Bicycles | 200 | 48 | 1,0 | 400 | 96 | 1.0 | |||||
Bodegas (wines) | 80 | 19 |
1.0 |
|
|
| |||||
| 96 | 1.5 |
264 | 264 | 2.0 | ||||||
|
|
|
|
|
| 240 |
240 | ||||
Cables | 300 | 72 | 1.0 | 600 | 144 | 1.5 | |||||
Cacao, products | 800 | 192 | 2.0 | 5,800 | 1,394 | 2.0 | |||||
coffee, unrefined |
|
|
| 2,900 |
697 | 2.0 | |||||
, extract | 300 | 72 | 1.0 | 4,500 | 1,082 | 2.0 | |||||
, Toaster | 400 | 96 | 1.5 |
|
|
| |||||
Boxes | 1,000 | 240 | 2.0 | 600 | 144 | 1.5 | |||||
| 80 | 19 | 1.0 |
|
|
| |||||
200 | 48 | 1.0 |
|
|
| ||||||
Calefactors | 300 | 72 | 1.0 |
|
|
| |||||
120 | 120 |
| 1.5 | 400 | 96 | 1.0 | |||||
footwear, accessorials |
|
|
| 800 | 192 | 1.5 | |||||
| 600 | 600 | 144 | 1.5 |
|
|
| ||||
Calzed, Sale | 500 | 120 | 1.0 |
|
|
| |||||
300 |
72 | 72 |
|
|
|
| |||||
| 96 | 96 |
| 1,0 | 1,500 | 361 | 2.0 | ||||
| 192 | 1.5 |
|
|
| ||||||
Coking coal |
|
|
| 10,500 | 2,524 | 2.0 | |||||
40 | 10 | 1.0 |
|
|
| ||||||
Carreteria, items of | 500 | 120 | 1.5 |
|
|
| |||||
| 72 | 1.5 | 300 |
| 1.010 | 1.5 | 1.5 | ||||
2,000 | 481 | 2.0 | 2,500 | 601 | 2.0 | ||||||
800 | 192 | 2.0 | 1,300 | 313 | 2.0 | ||||||
Carton stone | 300 | 72 | 1.5 | 2,500 | 601 | 1.5 | |||||
Cartonage | 800 | 192 | 1.5 | 2,500 | 601 | 1.5 | |||||
Cartonage, expedition of | 600 | 144 | 1.5 |
|
|
| |||||
|
|
|
| 28,600 |
|
|
2.0 | ||||
600 | 144 | 1.5 | 5,000 | 1.202 | 2.0 | ||||||
, sale of | items |
192 | 1.5 |
|
|
| |||||
Celuloid |
| 800 | 192 | 1.5 | 3,400 | 817 | 2.0 | ||||
| 40 | 10 | 1,0 |
|
|
| |||||
Central of Remote Heating | 200 |
48 | 1.0 |
|
|
| |||||
Hydraulic Central |
| 80 | 19 | 1.0 |
|
|
| ||||
power stations | 40 | 10 | 1.0 |
|
|
| |||||
200 | 200 | 200 | 200 | 48 | 1.0 |
|
|
| |||
Brushes and brushes | 700 | 168 | 1.5 | 800 | 192 | ||||||
|
|
| 3,400 | 817 | |||||||
Cera, items | 1,300 | 313 | 2.0 | 2,100 | 505 | 2.0 | |||||
| 2,100 | 2,100 | 505 | 2.0 |
|
|
| ||||
Ceramics, | 200 | 48 | 1.0 |
|
|
| |||||
200 | 48 | 48 |
|
|
|
|
| ||||
| 19 | 80 |
|
|
|
|
| ||||
| 96 | 1.5 | 200 | 48 | 1.0 | ||||||
|
72 | 72 | 1.0 | 200 | 48 | 1.0 | |||||
Chapa, items | 100 | 24 |
|
|
|
| |||||
| 48 | 48 | 48 | 1.0 |
|
|
| ||||
Chatarreria | 300 | 72 | 1.0 |
|
|
| |||||
Chocolate | Chocolate |
| 400 | 96 | 1.5 | 3,400 | 817 | 1.5 | |||
Chocolate, Packaging | 500 | 120 | 2.0 |
|
|
| |||||
Chocolate, manufacturing, mold room | 1,000 | 240 | 2.0 |
|
|
| |||||
Cines | 300 | 72 | 1.0 |
|
|
| |||||
Cochets | 300 | 72 | 1.0 | 800 | 192 | 1.5 | |||||
mattresses not synthetics | 500 | 120 | 1.5 | 5,000 |
1.202 | 2.0 | |||||
diluents and varnishes |
962 | 962 | 2.0 |
2,500 | 601 | 2.0 | |||||
and varnishes, manufactures of | 800 | 192 | 2.0 |
|
|
| |||||
| 2,0 | 2.0 | 2.0 | 2.0 | 2.0 |
|
|
| |||
and varnishes, sale |
1,000 | 240 |
|
|
|
| |||||
| 96 | 1.0 | 1,700 | 409 | 2.0 | ||||||
800 | 192 | 1.5 | 1.5 |
| 372 | 89 | 1.0 | ||||
Conservas | 40 | 10 | 1.0 | 372 | 89 | 1.0 | |||||
Corcho |
|
|
| 800 | 192 | 1.5 | |||||
Corcho, items from |
500 | 120 | 1.5 | 800 | 192 | 1.5 | |||||
Cordeleries | 300 | 72 | 1.5 | 600 | 144 | 1.5 | |||||
Cordeleries, Sale | 500 | 120 | 1.5 |
|
|
| |||||
Correas | 500 |
120 | 1.5 | 5,000 | 1.202 | ||||||
1,000 |
1,000 | 240 |
|
|
|
| |||||
Cosmetics | 300 | 72 | 1.5 | 500 | 120 | 1.5 | |||||
|
|
|
|
| 600 | 144 | 1.5 | ||||
| 24 | 1.0 |
|
|
| ||||||
|
|
|
|
409 | 409 |
1.5 | |||||
Leather |
240 | 240 | 1.5 | 1,700 | 409 | 1.5 | |||||
1.5 | |||||||||||
96 | 1.0 | 800 | 192 | 1.5 | |||||||
synthetic, trimming items from | 300 | 72 | 1.0 |
|
|
| |||||
, items from | 500 | 120 | 1.5 | 600 | 144 | 1.5 | |||||
, Cuts |
300 | 72 | 1.0 | 1.0 |
|
| |||||
, selling items from | 700 | 168 | 1.5 |
|
|
| |||||
Sports, selling items from | 800 | 192 | 1.5 |
|
|
| |||||
|
|
| 43,700 | 10.505 | 2.0 | ||||||
Deposits Merc. incomb. in wooden boxes |
|
|
| 200 |
48 | 1.0 | |||||
Deposits Merc. incomb. in plastic boxes |
|
|
| 200 | 48 | 1.0 | |||||
Deposits Merc. incomb. in wooden lockers |
|
|
| 100 | 24 | 2.0 | |||||
Deposits Merc. incomb. on wooden shelves |
|
|
| 100 | 24 | 1.0 | |||||
Deposits Merc. incomb. on metal shelves |
|
|
| 20 | 5 | 1.0 | |||||
Deposits Merc. incomb. on wooden pallets |
|
|
| 3,400 | 817 | 2.0 | |||||
Diluents |
|
|
|
3,400 | 817 | 2.0 | |||||
, compact disks, and the like |
600 | 144 | 1.5 | 3,400 | 817 | 1.5 | |||||
1,000 | 240 | 2.0 | 800 | 192 | 1.5 | ||||||
Fridges Buildings | 2,000 | 481 | 2.0 |
|
|
| |||||
Electricity, warehouse |
|
|
| 400 | materials |
96 | 1.0 | ||||
| 600 | 600 | 1.5 | 1.5 |
|
|
|
| |||
Material Packaging |
1,700 | 409 |
|
|
|
| |||||
| 144 | 1.5 | 1.5 |
|
|
|
|||||
Uncombustible Goods Packaging | 400 | 96 |
|
|
|
| |||||
Food Packaging | 800 | 192 |
1.5 |
|
|
| |||||
| 144 | 1.5 | 1.5 |
|
|
| |||||
Radio stations | 80 | 19 | 1.0 |
|
|
| |||||
Encuaderation |
240 | 240 | 2.0 |
|
|
| |||||
brooms | 700 | 168 | 1.5 | 400 | 96 | 1.0 | |||||
Sculptures | 40 | 10 | 1.0 |
|
|
| |||||
40 | 40 | 40 | 10 | 1.0 | 200 | 48 | 1.5 | ||||
3,000 | 721 | 1.5 | 2,500 | 601 | |||||||
synthetic, items | 600 | 144 | 1.5 | 800 | 192 | 1.5 | |||||
Skies | 400 | 96 | 1.5 | 1,700 |
409 | 2.0 | |||||
2.0 |
| 300 | 72 | 1,0 | 1,700 | 409 | 2.0 | ||||
Stamping synthetic | 400 | 96 | 1.0 |
|
|
| |||||
Stamping | 100 | 24 | 1.0 |
|
|
| |||||
| 200 | 48 | 1.0 |
|
|
| |||||
Tv Studies | 300 | 72 | 1.0 |
|
|
| |||||
stoves | 200 | 48 |
1.0 |
|
|
| |||||
Expedition of appliances, partially synthetic | 700 | 168 | 1.0 |
|
|
| |||||
Expedition, Fully synthetics | 1,000 | 240 | 1.0 |
|
|
| |||||
Item Expedition | 700 |
168 | 2.0 |
|
|
| |||||
200 | 48 | 1.0 |
|
|
| ||||||
| 409 | 2.0 | 1,700 | 2.0 |
|
|
|
| |||
Item Expedition |
1,000 | 240 |
|
|
|
| |||||
| 72 | 1.0 | 300 | 1.0 |
|
| |||||
| 144 | 1.5 | 600 |
|
|
|
| ||||
Waxes and varnishes Expedition |
1,300 | 313 |
|
|
|
| |||||
Furniture Expedition | 600 | 144 | 1.5 |
|
|
| |||||
Dispatching small wooden items | 600 | 144 | 1.5 |
|
|
| |||||
Expedition food | 1,000 | 240 |
|
|
|
| |||||
600 | 144 | 1.5 | 1.5 |
|
|
| |||||
Auto Expo | 200 | 48 | 1.0 |
|
|
| |||||
Exposition | 200 | 48 |
|
|
|
| |||||
| 19 | 19 | 1.0 |
|
|
| |||||
Furniture Exposition | 500 | 120 | 1.5 |
|
|
| |||||
Pharmacies (included stores) |
800 | 192 |
|
| |||||||
500 | 120 | 1.5 | 500 |
|
|
| |||||
Coconut Fibers |
|
|
|
2.019 | 2.019 | ||||||
| 600 | 144 | 1.5 | 800 | 192 | 1.5 | |||||
Fieltro, items | 500 | 120 | 1.5 |
|
|
| |||||
artificial | 300 | 72 | 1.5 | 200 |
48 | 1.5 | |||||
, selling | 80 | 19 | 1.0 |
|
|
| |||||
Plumbing | 200 |
48 | 1.0 |
|
|
| |||||
Forage | 2,000 | 481 | 2.0 | 3,300 | 793 | ||||||
Fosforum | 300 | 72 | 1.5 | 25,100 | 6.034 | ||||||
Fosforums | 300 | 72 | 1.5 | 800 | 192 | 2.0 | |||||
Photocopies, Workshops | 400 | 96 | 1.0 |
|
|
| |||||
Photography, labs | 100 | 24 | 1.0 |
|
|
|
|||||
, movies | 1,000 | 240 | 2.0 |
|
|
| |||||
, workshops |
300 | 72 |
|
|
|
| |||||
Photograph, store | 300 | 72 | 1.0 |
|
|
| |||||
| 19 | 1.0 |
|
|
| ||||||
Foundry | 40 | 10 | 1.0 |
|
|
| |||||
300 | 72 | 1.0 |
|
|
| ||||||
Galvanoplasty | 200 | 48 | 1.0 |
|
|
| |||||
Stations | Specific Regulations |
|
|
| |||||||
| 400 | 96 | 1.5 |
|
|
| |||||
Grains | 600 | 144 | 1.5 | 800 | 192 | 1.5 | |||||
1,000 | 240 | 2.0 | 18,000 | 4.327 | 2.0 | ||||||
Edible Fats | 1,000 | 240 | 2.0 | 18,900 | 4.543 | 2.0 | |||||
, expedition |
900 | 216 |
|
| |||||||
| 120 | 1.5 |
|
|
| ||||||
Garment, Wood Closets | 400 | 96 | 1.0 |
|
|
|
| 80 | 19 |
|
|
|
|
2,000 |
481 | 2.0 | 2.0 | 2.0 | 2.0 | 2.019 | 2.019 | 2.0 | |||
Harina, factory or store without warehouse | 1,700 | 409 | 2.0 | 13,000 | 3.125 | 2.0 | |||||
Heleria |
80 |
|
|
|
|
| |||||
| 0 |
| 0 |
240 |
240 | 2.0 | |||||
Tools | 200 | 48 | 1.0 |
|
|
| |||||
|
|
| 130,800 | 31,442 | 2.0 | ||||||
Hilados, carded | 300 | 72 | 2.0 |
|
|
| |||||
Hilados, Lock-winding | 600 | 144 | 1.5 |
|
|
| |||||
Hilados, hilature | 300 |
72 | 1.5 |
|
|
| |||||
Hilados, thread products |
|
|
| 1,700 | 409 | 2.0 | |||||
Hilados, wool products |
|
|
| 1,900 |
457 | 2.0 | |||||
Hilados, twisted | 300 |
72 | 1.5 |
|
|
| |||||
Hojalateries | 100 | 24 | 1.0 |
|
|
| |||||
, items from | 100 | 24 | 1.0 |
|
|
| |||||
200 | 200 | 48 | 1.0 |
|
|
| |||||
700 | 168 | 1.5 | 1,300 | 313 | |||||||
Hule, items | 700 |
168 | 1.5 | 2,100 | 505 | ||||||
|
|
| 8,000 | 1,923 |
| ||||||
2,000 | 2,000 | 481 |
|
|
|
| |||||
| 200 | 200 | 48 | 1.5 |
|
|
| ||||
, machine rooms | 400 | 96 |
|
|
| ||||||
300 | 72 |
1.5 |
|
|
| ||||||
| 200 | 200 | 48 | 1.0 |
|
|
| ||||
Electricist Installer | 200 | 48 |
|
|
|
| |||||
Installers, Workshops | 100 | 24 |
|
|
|
| |||||
| 600 | 600 | 144 | 1.5 |
|
|
| ||||
Instruments | 200 | 48 | 1.0 | 200 | 48 | 1,0 | |||||
Jabon | 200 | 48 | 1,0 | 4,200 | 1.010 | 1.5 | |||||
| 48 | 200 |
1.0 |
|
|
| |||||
| 72 | 1.0 |
|
|
| ||||||
| 120 | 1.5 | 500 |
| 800 | 192 | 1.5 | ||||
200 | 48 | 1.0 |
|
|
| ||||||
Laboratories | 200 | 48 | 1.0 |
|
|
| |||||
| 72 | 1.5 | 300 |
|
|
|
| ||||
Metallurgical Laboratories |
200 | 48 |
|
|
|
| |||||
| 72 | 1.0 |
|
|
| ||||||
Chemicals | 500 | 120 | 1.5 |
|
|
| |||||
Lamines | 40 | 10 | 1.0 |
|
|
| |||||
Lamparas incandescent | 40 | 10 | 1.0 |
|
|
| |||||
500 | 120 | 1.5 |
|
|
| ||||||
machines | 300 |
72 | 1.0 | 400 | 96 | 1.0 | |||||
Lavaneries | 200 | 48 | 1.0 |
|
|
| |||||
condensed milk |
200 | 48 | 1.0 | 9,000 |
| 1.0 | |||||
200 | 48 | 1.0 | 10,500 |
| 1.0 | ||||||
200 | 200 | 200 | 48 | 1.0 |
|
|
| ||||
Legacies | 1,000 | 240 | 2.0 | 400 | 96 | 1.5 | |||||
Lena |
|
|
| 2,500 | 601 | 2.0 | |||||
800 | 192 | 1.5 |
|
|
| ||||||
Bookshops | 1,000 | 240 | 1.5 |
|
|
| |||||
cleaning | 300 | 72 | 1.5 |
|
|
| |||||
Linoil | 500 | 120 | 1.5 | 5,000 | 1.202 | 2.0 | |||||
| 500 | 500 | 120 | 1.5 |
|
|
| ||||
Lupo |
|
|
|
1,700 | 409 | ||||||
Wood on logs |
|
|
| 6.300 | 1.514 | 1.5 | |||||
Madera, barnized items | 500 | 120 | 1.5 |
|
|
| |||||
, items, carpentry | 700 | 168 | 1.5 |
|
|
| |||||
, ebeanisteria articles | 700 | 168 | 1.5 |
|
|
| |||||
Wood, Items, Expedition | 600 | 144 | 1.5 |
|
|
| |||||
, articles, impregnation | 3,000 | 721 |
|
|
|
| |||||
, items, marquetry | 500 | 120 | 1.5 |
|
|
| |||||
Madera, items from, polished | 200 | 48 | 1.0 |
|
|
| |||||
, items, drying | 800 | 192 |
|
|
| ||||||
400 | 96 |
1.5 |
|
|
| ||||||
Wood, Items, carved | 600 | 144 | 1.5 |
|
|
| |||||
, items, turning | 500 | 120 |
|
|
| ||||||
, items, die-cut | 700 | 168 |
1.5 |
|
|
| |||||
| 800 | 192 | 1.5 | 4.200 | 1,010 | ||||||
Wood, Remains |
|
|
| 2,500 | 601 | ||||||
, beams, and tables |
|
|
| 4,200 | 1.5 | 1.5 | |||||
Madera, paths |
|
|
| 2,100 | 505 | ||||||
Malta |
|
|
| 13,400 | 3.221 | ||||||
Butter | 700 | 168 |
|
| |||||||
| 48 | 48 |
|
|
|
|
| ||||
| 72 | 1.0 |
|
|
| ||||||
Office Machines | 300 | 72 | 1.0 |
|
|
| |||||
Mark | 300 | 72 | 1.0 |
|
|
| |||||
Marble, items | 40 | 10 | 1.0 |
|
|
| |||||
Matches |
40 | 10 | 1.0 |
|
|
| |||||
Material | 700 | 168 | 1.5 | 1,300 | 313 | 2.0 | |||||
Materials, Warehouse |
|
|
| 800 | 192 | ||||||
Materials | 2,000 | 481 | 2.0 | 5,900 |
| 2.0 |
| ||||
800 |
192 | 1.5 | 3,400 | 817 | 2.0 | ||||||
injected synthetic materials |
500 | 120 | 1.5 |
|
|
| |||||
| 600 | 144 | 1.5 | 800 | 192 | 1.5 | |||||
materials, stamped |
400 | 96 |
|
|
|
| |||||
| 240 | 240 | 2.0 |
|
|
|
|||||
materials, parts welding | 700 | 168 |
|
| |||||||
Precision Mechanics, Workshop | 200 | 48 |
|
|
|
| |||||
| 48 | 1.0 |
|
|
| ||||||
| 300 | 72 | 1.0 | 800 | 192 | 1.5 | |||||
, sales | 800 | 192 | 1.5 |
| 0 |
| |||||
Melaza |
|
|
| 5,000 | 1.202 | 2.0 | |||||
Merceria, sale | 700 | 168 | 1.5 | 1,400 | 337 | 2.0 | |||||
800 | 192 | 1.5 |
|
|
| ||||||
200 | 200 | 48 | 1.0 |
|
|
| |||||
, manufacturing in general | 200 | 48 | 1.0 |
|
|
| |||||
, large constructs | 80 | 19 | 1.0 |
|
|
| |||||
| 40 |
|
|
|
| ||||||
Mostaza | 400 | 96 | 1.0 |
|
|
| |||||
Motorcycles | 300 | 72 | 1.0 |
|
|
| |||||
300 | 300 | 72 |
|
|
|
| |||||
| 72 | 300 | 1.0 |
|
|
| |||||
500 | 120 | 1.5 | 1.5 |
| 800 | 192 | 1.5 | ||||
Wood furniture, varnished | 500 | 120 | 1.5 |
|
|
| |||||
, varnishing of | 200 | 48 |
|
| |||||||
| 600 | 144 | 1.5 |
|
|
| |||||
Furniture, upholstered without synthetic foam | 500 | 120 | 1.5 |
400 | 96 | 1.0 | |||||
, sale | 400 | 96 |
|
| |||||||
| 192 | 1.5 | 800 | 1.5 |
|
| |||||
Munitions | Special | Special | Special |
4,500 | 1,082 | 2.0 | |||||
Museums | 300 | 72 |
|
|
|
| |||||
300 | 300 | 1.0 |
|
|
| ||||||
|
|
|
|
|
|
| 12,600 | 3.029 | 2.0 | ||
Tyres | 700 | 168 | 1.5 |
1,800 | 433 | 2.0 | |||||
tires | 700 | 168 | 1.5 | 1,500 | 361 | 2.0 | |||||
|
Special | Special | Special | Special | Special | Special | 264 | 264 | 2.0 | ||
Offices | 800 | 192 |
|
| |||||||
| 96 | 1.0 |
|
|
| ||||||
| 144 | 1.0 |
|
|
| ||||||
Orgage | 200 | 48 | 1.0 |
|
|
| |||||
Oxygen | Oxygen | Oxygen | Special | Special | Special | Special |
|
|
| ||
Paja pressed |
|
|
| 800 |
192 | 1.5 | |||||
Paja, items from | 400 | 96 | 1.5 |
|
|
| |||||
Paja, packaging of | 400 | 96 | 1.5 |
|
|
| |||||
Palettes | 1,000 | 240 | 2.0 | 1,300 |
313 | 2.0 | |||||
500 | 120 | 1.5 |
|
|
| ||||||
| 1,000 | 240 | 1.5 |
|
|
| |||||
Panaderies, warehouses | 300 | 72 | 1.0 |
|
|
| |||||
Panaderies, labs, and ovens | 200 | 48 | 1.0 |
|
|
| |||||
panels | 500 | 120 | 1.5 |
|
|
| |||||
agglomerated wood panels | 300 | 72 | 1.5 | 6,700 | 1,611 | 2.0 | |||||
panels | 800 | 192 | 1.5 | 6,700 | 1,611 | 2.0 | |||||
| 200 |
48 | 1.0 | 10,000 | 2.404 | ||||||
Role, learn | 500 | 120 | 1.5 |
|
|
| |||||
, varnish of | 80 | 19 | 1.5 |
|
|
| |||||
, pressed waste |
|
|
| 2,100 | 505 | ||||||
Role, treat. of wood and cellulosic materials | 80 | 19 | 1.5 |
|
|
| |||||
, treatment-manufacturing | 700 | 168 | 1.5 |
|
|
| |||||
, old or bulk |
|
|
| 8,400 | 2.019 | 2.0 | |||||
Papeleria | 800 | 192 | 1.5 | 1,100 |
264 | 2.0 | |||||
700 | 168 | 1.5 |
|
|
| ||||||
Parwaters | 300 | 72 | 1.0 | 400 | 96 | 1.0 | |||||
Parwaters, sale | 300 |
72 | 1.0 |
|
|
| |||||
Parquets | 2,000 | 481 | 2.0 | 1,200 | 288 | ||||||
1,300 |
313 | 313 | 2.0 | 1,700 | 409 | 1.5 | |||||
| 1,000 | 1,000 | 240 | 2.0 |
|
|
| ||||
Fuels | 1,000 | 240 |
| 3,400 | 817 | ||||||
800 |
192 | 192 | 1.5 | 3,400 | 2.0 | 2.0 | |||||
| 500 | 500 | 120 | 1.5 | 1,200 | 288 |
| ||||
200 | 200 | 48 |
|
|
|
| |||||
, Copies | 600 | 144 |
|
| |||||||
300 | 300 | 72 | 1.5 |
|
|
| |||||
Perfumery, items from | 300 | 72 | 1.0 | 500 | 120 | 1.5 | |||||
Perfuming, selling items from | 400 | 96 |
|
| 0 |
| |||||
800 | 800 | 192 | 1.5 | 300 | 72 | 1.0 | |||||
40 |
40 | 10 | 1.0 |
|
|
| |||||
Sharp stones | 80 | 19 | 1.0 |
|
|
| |||||
stones, carved |
80 | 19 | 1.0 |
|
|
| |||||
stones, items | 200 | 48 | 1.0 |
|
|
| |||||
| 0 |
| 0 | 0 | 0 | 1,200 | 288 | 1.5 | |||
Stack | 400 | 96 | 1.0 | 600 | 144 | 1.5 | |||||
brushes | 700 | 168 | 1.5 |
|
|
| |||||
Fiber Plates | 300 | 72 | 1.0 | 800 | 192 | 1.5 | |||||
resin plates | 300 | 72 | 1.0 | 4,200 | 1,010 | 1.5 | |||||
Planers | 600 |
144 | 1.5 |
|
|
| |||||
Porcelain |
| 200 | 48 | 1.0 |
|
|
| ||||
500 |
120 | 120 |
1.5 | 400 | 96 | 1.0 | |||||
dress, Sale | 600 | 144 | 1.5 |
|
|
| |||||
processing, computer room | 400 | 96 | 1.5 |
|
|
| |||||
product (raw material bleach) |
|
|
| 500 |
120 | 1.5 | |||||
Asbestos products | 80 |
19 | 1.0 |
|
|
| |||||
Carnage Products | 40 | 10 | 1.0 |
|
|
| |||||
products (bleach) | 300 | 72 | 1.0 | 200 | 48 | 1.0 | |||||
footwear repair products | 800 |
192 | 1.5 | 2,100 | 505 | ||||||
| 200 | 48 | 1.5 |
|
|
| |||||
Products | 200 | 48 |
1.0 |
|
|
| |||||
products except sheet and wire | 100 | 24 | 1.0 |
|
|
| |||||
Chemicals | 300 | 72 | 2.0 | 1,000 | 240 | 2.0 | |||||
Doors | 800 | 192 |
1.5 | 1,800 | 433 | 2.0 | |||||
700 | 168 | 1.5 | 4.200 | 1,010 | |||||||
Quesos | 100 | 24 | 1.5 | 2,500 | 601 | ||||||
1,300 |
313 | 313 |
| 2.0 |
|
|
| ||||
, cabinet of | 200 | 48 | 1.0 |
|
|
| |||||
Oil Refineries | Regulatory specifies |
|
|
| |||||||
| 1,000 | 2.0 | 2.0 | 300 | 72 | 1.0 | |||||
| 96 | 1.0 |
| 1,300 | 313 | 2.0 | |||||
Watches | 300 | 72 | 1.0 |
400 | 96 | 1.0 | |||||
Watches, Repair |
300 | 72 | 1.0 |
|
|
| |||||
300 | 72 | 1.0 |
|
|
| ||||||
| 3,300 |
| 793 | 2.0 |
|
|
| ||||
Resins | 3,400 | 817 | 2.0 | 4,200 | 1,010 | ||||||
Synthetic Resins, |
| 800 | 192 | 1.5 | 3,400 | 817 | 2.0 | ||||
| 300 | 72 |
1.0 |
|
|
| |||||
500 |
120 | 1.5 | 6,000 | 1,442 | |||||||
Combustible Floor Coverings, selling | 1,000 | 240 | 2.0 |
|
|
| |||||
bearings or bearings | 200 |
48 | 1.0 |
|
|
| |||||
Sacks | 800 | 192 | 1.5 | 12,600 |
2.0 | 2.0 | |||||
Sacks | 600 | 144 | 2.0 | 25,200 |
| ||||||
500 | 500 | 2.0 | 120 | 1.5 | 800 |
192 | 1.5 | ||||
Salinas, products from | 80 |
19 | 1.0 |
|
|
| |||||
Services | 200 | 48 | 1.0 |
|
|
| |||||
Silos |
|
|
| According to stored material | |||||||
Shadows | 500 | 120 | 1.5 |
|
|
| |||||
| 40 | 10 | 1.0 |
|
|
| |||||
Sotanos, home holds residential | 900 | 216 | 1.0 |
|
|
| |||||
|
|
|
409 | 409 | 2.0 | ||||||
Tabacos, items | 200 | 48 | 1.5 |
2,100 | 505 | 2.0 | |||||
Tabacos, sale of items | 500 | 120 | 1.5 |
|
|
| |||||
40 | 40 | 1.0 |
|
|
| ||||||
Talker | 40 |
10 | 1.0 |
|
|
| |||||
Workshops | 800 | 192 | 1.5 | 2,900 | 697 | 1.5 | |||||
Workshops garnitionery | 300 | 72 | 1.0 |
|
0 |
| |||||
Workshops | 500 | 120 | 1.5 |
|
|
| |||||
workshops | 400 | 96 | 1.0 |
|
|
| |||||
Workshops electrical | 600 | 144 | 1.5 |
|
|
| |||||
Workshops | 200 | 48 | 1.0 |
|
|
| |||||
Tapias | 800 |
192 | 1.5 |
|
|
| |||||
Tapiceries, items | 300 | 72 | 1.5 | 1,000 | 240 | 2.0 | |||||
Tapices | 600 | 144 | 1.5 | 1,700 | 409 | 2.0 | |||||
Tapes, tincture | 500 | 120 | 1.5 |
|
|
| |||||
Tapes, sale | 800 | 192 | 1.5 |
|
|
| |||||
Theatres | 300 | 72 |
|
|
|
| |||||
Theatres, racks |
|
|
| 1,100 | 264 | 2.0 | |||||
40 | 40 | 40 | 1.0 |
|
|
| |||||
Wovens, drying ovens and wooden shelving | 1,000 | 240 | 1.5 |
|
|
| |||||
200 | 200 | 48 |
|
|
|
| |||||
Fabric, clay preparation | 40 |
|
|
|
| ||||||
, Secadero, Wood Shelves | 400 | 96 | 1,0 |
|
|
| |||||
, Secadero, Metal Shelves | 40 |
|
|
|
| ||||||
, jute, linen |
|
|
| 1,300 | 313 | ||||||
400 | 96 | 96 |
|
|
| ||||||
Fabric in general, warehouse |
|
|
| 2,000 | 481 | 2.0 | |||||
| 300 | 300 | 72 | 1.5 | 1,300 | 313 | |||||
Fabric, Cotton Bullet Repository |
|
|
| 1,300 | 313 | 2.0 | |||||
, artificial silk | 300 | 72 | 1.5 | 1,000 | 240 | 2.0 | |||||
| 400 | 96 | 1.5 | 200 | 48 | 2.0 | |||||
| 80 | 19 | 1.5 |
|
|
| |||||
Textiles |
|
|
| 1,000 | 240 | 2.0 | |||||
Textiles, learn | 300 | 72 |
1.0 | 1,100 | 264 | 2.0 | |||||
|
|
|
|
|
| 600 | 144 | 1.5 | |||
Textiles, undergarments | 300 | 72 | 1.0 |
1,000 | 240 | 1.5 | |||||
Textiles, whitened | 500 | 120 |
|
| |||||||
| 72 | 1.0 | 1,300 | 313 | 2.0 | ||||||
Textiles, calendaring | 500 | 120 | 1.5 |
|
|
| |||||
300 | 72 | 1.0 |
|
|
| ||||||
Textiles, cut | 500 | 120 | 1.5 |
|
|
| |||||
Textiles, linen |
|
|
| 1,300 | 313 | 2.0 | |||||
Textiles, jute | 400 | 96 | 1.0 | 1,300 | 313 | 2.0 | |||||
Textiles, Packing | 600 | 144 | 1.6 |
|
|
| |||||
Textiles, lace |
|
|
| 600 | 144 | 1.5 | |||||
Textiles, stamping | 700 | 168 | 1.5 |
|
|
| |||||
600 | 144 | 1.5 |
|
|
| ||||||
Textiles, liners | 700 | 168 | 1.5 |
|
|
| |||||
| 500 | 120 | 1.5 | 600 | 144 |
2.0 | |||||
Textiles, blankets | 500 | 120 |
|
457 | 2.0 | ||||||
2.0 | |||||||||||
Textiles, Garments | 500 | 120 | 1.5 | 400 | 96 | 2.0 | |||||
Textiles, preparation | 300 | 72 | 1.5 |
|
|
| |||||
Textiles, bedding | 500 | 120 |
|
| |||||||
Textiles, fabrics (manufacturing) | 300 | 72 | 1.5 |
|
|
| |||||
Textiles, dyed | 500 | 120 | 1.5 |
|
|
| |||||
| 72 | 72 | 1,0 | 1,300 | 313 | 2.0 | |||||
| 600 | 600 | 144 | 1.5 |
|
|
| ||||
Tintas | 200 | 48 | 1.0 |
|
|
| |||||
700 |
168 | 168 |
|
721 | 2.0 | ||||||
| 120 | 1.5 |
|
|
| ||||||
Toldos or tarps | 300 | 72 | 1.0 |
240 | 240 | 1.0 | |||||
Tonels | 1,000 | 240 | 1.5 | 800 | 192 | 1.5 | |||||
Tonels | 600 | 144 | 1.5 | 800 | 192 | 1.5 | |||||
| 72 | 1.0 | 300 | 1.0 |
|
|
|
||||
| 300 | 72 | 1.5 |
|
|
| |||||
, winding |
600 | 144 |
|
| |||||||
| 72 | 1.5 | 300 |
|
|
| |||||
fluorescent tubes | 300 | 72 | 1.0 |
|
|
| |||||
Wagon, Manufacturing | 200 | 48 |
|
|
|
| |||||
| 72 | 1.5 | 1.5 |
|
|
| |||||
| 96 | 1.5 | 1.5 |
|
|
|
| ||||
Windows | 800 | 192 |
|
| |||||||
| 144 | 1.5 | 600 |
|
|
| |||||
| 19 | 1.0 |
|
|
| ||||||
, items from | 200 | 48 | 1.5 |
|
|
| |||||
, expedition | 700 | 168 | 1.0 |
|
|
| |||||
, plane, factory of | 700 | 168 | 1.0 |
|
|
| |||||
, blowing workshops | 200 |
48 | 1.5 |
|
|
| |||||
, tincture of | 300 | 72 | 1.5 |
|
|
| |||||
Glass, Treatment | 200 | 48 | 1.5 |
|
|
| |||||
, sale of | 200 | 48 | 1.0 |
|
|
| |||||
, Production | 80 | 19 | 1.0 | 100 | 24 | 1.0 | |||||
Vulcanization | 1,000 | 240 | 2.0 |
|
|
| |||||
Yeso | 80 | 19 |
|
|
|
| |||||
1,000 | 240 | 2.0 | 1,300 | 313 | 2.0 |
TABLE 1.3
Weighted And Corrected Fire Load Density | |||
---|---|---|---|
Mcal/m2 | MJ/m2 | ||
UNDER | 1 |
s ≤ 100 | Qs ≤ 425 |
2 | 100 < Qs ≤ 200 | 425 < Qs ≤ 850 | |
| 3 | 200 < Qs ≤ 300 |
850 < Qs ≤ 1,275 |
4 | 300 < Qs ≤400 | 1.275 < Qs ≤ 1,700 | |
5 | 400 < Qs ≤ 800 | 1,700 < Qs ≤ 3,400 | |
HIGH | 6 | 800 < Qs ≤ 1,600 | 3,400 < Qs ≤ 6,800 |
7 | 1,600 < Qs ≤ 3,200 | 6,800 < Qs ≤ 13,600 | |
8 | 3,200 < Qs | 13600 < Qs |
TABLE 1.4
Calorific Power (q) of Various Substances
Product | MJ/kg | Mcal/kg | Product | MJ/kg | Mcal/kg | Product | MJ/kg |
Mcal/kg | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Oil | 37.2 | 9 | 9 | 31.4 | 7.5 | Powdered Milk | 16.7 | 4 | ||||||
Creosote Oil | 37.2 | 9 | Carbon | 33.5 | 8 |
16.7 | 4 | 4 | ||||||
| 9 | Carton |
16.7 | 4 | Linoleum | 2.1 | ||||||||
Oil | 42 | 10 |
| 21 | 21 | 5 | Wood | 4 | 4 | |||||
| 10 | Cell | 42 | 42 |
| 16,7 | 4 | Magnesium | 25.1 | 6 | ||||
paraffin oil | 42 | 10 | Cell | 16.7 | 4 | Malta | 16.7 | |||||||
Acetaldehyde | 25,1 | 6 |
16.7 | 4 | 4 | Butter |
| 9 | ||||||
5 | 5 | 5 |
| Metano | 50.2 | 6 | 6 | |||||||
amyl acetate | 33.5 | 8 | 46 | 46 | 11 | Carbon Monoxide | 8.4 | 2 | ||||||
| 21 | 21 | 5 | Ciclohexane | 46 | 11 | 29.3 | 7 | ||||||
Acetone |
7 | 7 |
46 | 11 | Nitrocellulose | 46 | 46 | 8.4 | 2 | |||||
50.2 | 12 | Ciclopropane | 50.2 | 12 | Octane | 46 | 11 | |||||||
Disdissolved Acethylene | 16.7 | 4 |
| 21 | 21 | 5 | Paper | 4 | 4 | |||||
16,7 | 4 | cellulosic Queue |
| 9 | 9 | 11 | 11 |
11 | ||||||
| 6 | 6 | 29.3 | 7 | Pentano | 50.2 | 12 | |||||||
Acrolein | 29.3 | 7 | Leather | 21 | 5 |
| Oil | 42 | 10 | |||||
Needles | 42 | 10 | Diethylamine | 42 | 10 | Polyamide | 29.3 | |||||||
|
Diethylketone | 33.5 | 8 | Polycarbonate | 29.3 | 7 | ||||||||
Alcanfor | 37.2 | 9 | Diethyl ether | 37.2 | 9 |
25,1 | 6 |
| ||||||
allyl alcohol | 33.5 | 8 |
42 | 10 | POLYSTYRENE | 42 | 10 | |||||||
42 | 42 | 10 | Dynamite (75%) | 4.2 | 1 | 42 | 42 | |||||||
33.5 | 8 |
| 46 | 46 | 11 | Polyisobutylene | 46 | 11 | ||||||
42 | 10 | Ebonita | 42 |
| 33.5 | 8 |
4.2 | 1 | ||||||
ethyl alcohol | ||||||||||||||
25,1 | 6 | Etane | 50.2 | 12 | Polyurethane |
| ||||||||
| 21 | 21 |
5 | 42 | 42 | 10 |
46 | 46 | 11 | |||||
Starch | 16.7 | 4 | Ethyl Ether | 33.5 | 8 | Rayon | 16.7 | |||||||
acetic anhydride |
4 | 4 | 4 | 25,1 | 6 | pine resin | 42 | 10 | ||||||
37.2 | 9 | Fenol | 33.5 | 8 | phenol resin |
25,1 | 6 | |||||||
Antraceno | 42 | 10 | Fosforum |
|
urea Resin | 21 | 5 | |||||||
Antracita | 33.5 | 8 | 25.1 | 6 | 6 |
Silk | 21 | 5 | ||||||
Sugar |
4 |
4 | 4 | 42 | 10 | Sisal | 16.7 |
4 | ||||||
| 8.4 | 2 | 16,7 | 4 | Sodium | 4 | 4.2 | |||||||
33.5 | 8 | Grases | 33.5 |
| 42 | 10 | Carbon Sulfide | 12.5 | ||||||
Bentina | 42 | 10 | 46 | 46 | 11 | Tobacco | 16.7 | 4 | ||||||
42 | 10 | 10 | 10 Wheat table_izq"> Wheat Harina | 16.7 | 4 | Te | 16,7 | 4 | ||||||
33.8 | 8 | Heptano | 46 |
11 | Tetralin | 46 | 11 | |||||||
46 | 11 | Hexamethylene | 46 | 46 | 46 | 11 | Toluol | 42 | 10 | |||||
powder | 16.7 | 4 | Hexano | 46 | 11 |
16.7 | 16.7 |
| ||||||
Coffee | 16.7 | 4 |
142 | 34 | Turba |
| 33.5 | 8 | ||||||
21 | 5 | Magnesium hydride | 16.7 |
4 | Urea | 8.4 | 2 | |||||||
4.2 | 4.2 | 1 | Sodium hydride | 8.4 | 2 |
16.7 | 4 | 4 | ||||||
42 | 10 | Lana |
21 | 5 |
|
|
|
ANNEX II
Constructive requirements for industrial establishments based on their intrinsic configuration, location and level of risk
Definitions.
This fire safety regulation uses terms that may be subject to different interpretations.
In order to avoid different interpretations, which may even become contradictory or to be set against the spirit of the text of the regulation, the following definitions are laid down for some of the terms included in the the.
A. Accessible facades.
Both urban planning and the conditions of design and construction of the buildings, in particular the immediate environment, their access, their holes in front, etc., must enable and facilitate the intervention of the fire extinguishing services.
Local authorities will be able to regulate the conditions they deem necessary to comply with the above; in the absence of regulatory regulation by the local authorities, the recommendations indicated to continuation.
They are considered to be accessible facades of a building, or industrial establishment, those that have gaps that allow access from outside to the fire extinguishing service personnel.
Facade gaps must meet the following conditions:
a) Facilitate access to each of the floors of the building, so that the height of the sill with respect to the level of the plant at which it accesses is no greater than 1.20 m.
b) Its horizontal and vertical dimensions must be at least 0.80 m and 1,20 m, respectively. The maximum distance between the vertical axes of two consecutive voids must not exceed 25 m, measured on the facade.
(c) No elements should be installed in front of elements that prevent or hinder the accessibility of the building through such holes, except for the safety elements in the holes of the plants whose height of Evacuation does not exceed nine m.
In addition, in order to consider the accessible facade as defined, the conditions of the building environment and the conditions of approach to this building must be met:
A. 1. Conditions of the building environment.
(a) Buildings with a descending discharge height greater than nine m must have a space for manoeuvre suitable for the passage of vehicles, which meets the following conditions along the accessible facades:
1. Minimum free width: six m.
2. Free Height: the building.
3. th Maximum building separation: 10 m.
4. th Maximum distance to any main access to the building: 30 m.
5. Top Pending: 10 percent.
6. Ground Port Capacity: 2000 kp/m2.
7. Ground punching resistance: 10 t on 20 cm Ø.
The condition referred to the punching must be met in the recording caps of the public service channels, if the dimensions are greater than 0.15 m × 0.15 m, and must be closed to the specifications of the UNE-EN 124:1995 standard.
The wiggle room should be kept free of urban furniture, trees, gardens, mojones, or other obstacles.
In buildings in closed block, the only access and void of which are open exclusively to patios or inner squares, there shall be an access to these for the vehicles of the fire extinguishing service. Both the places or the yards and the accesses mentioned above shall comply with the provisions of paragraph A. 2 above.
(b) In built-up areas bordering or inland to forest areas, the conditions set out in paragraph 10 of this Appendix must be met.
A. 2. Conditions for the approximation of buildings.
The approach vials up to the accessible facades of the industrial establishments, as well as the manoeuvring spaces referred to in the previous paragraph, must meet the following conditions:
1. Minimum free width: five m.
2. Minimum free height or galibo: 4.50 m.
3. Vial Bearing Capacity: 2000 kp/m2.
In the curved sections, the tread must be delimited by the trace of a circular crown whose minimum radii must be 5.30 m and 12, 50 m, with a free width for circulation of 7.20 m.
B. Portant structure.
A building structure shall be understood as the building structure consisting of the following elements: forged, beams, supports and main and secondary deck structure.
C. Cover main structure and its supports.
The main cover structure and its supports shall be the cover structure of the cover structure itself (lintel, cercha) and the supports which have as its sole function to support it, including those which, in its Case, also support a crane.
For these purposes, the secondary structural elements, for example, cover straps, shall not be considered a constituent part of the main deck structure.
D. Lightweight cover.
Any cover whose own weight does not exceed 100 kg/m2shall be qualified as lightweight.
E. Permanent load.
To be interpreted as a permanent load, to the rating effects of a cover as light, the result of taking into account the set formed by the main structure of cover porches, plus the straps and materials coverage.
In the case of the existence of cranes, account must also be taken, in addition, for the computation of the permanent load, the weight of the rail beam itself, as well as the structure of the crane on which the hoist is moved.
1. Non-permitted locations of fire sectors with industrial activity.
The location of fire sectors with the industrial activities included in Article 2 is not permitted:
a) High intrinsic risk, in type A configurations, as shown in Annex I.
(b) Average intrinsic risk, in floor level, in type A configurations, as set out in Annex I.
c) An intrinsic, average risk, in type A configurations, when the length of its accessible facade is less than five m.
(d) Medium or low intrinsic risk, in plant on scraper with an evacuation height of more than 15 m, in type A configurations, as set out in Annex I.
e) High intrinsic risk, when the discharge height of the downstream sector is greater than 15 m, in type B configuration, as set out in Annex I.
f) Medium or high intrinsic risk, in type B configurations, when the length of its accessible facade is less than five m.
g) Of any risk, on the second floor of the floor in type A, type B and type C configurations, as set out in Annex I.
h) High intrinsic risk A-8, in type B configurations, according to Annex I.
i) Medium or high intrinsic risk, less than 25 m of forest mass, with permanently free perimeter strip of low bushland vegetation.
2. Sectorisation of industrial establishments.
Any industrial establishment shall, at least, constitute a fire sector when it adopts type A, type B or type C configurations, or it shall constitute a fire area when it adopts type D or type E configurations, Annex I.
2.1. The maximum permissible constructed surface of each fire sector shall be as shown in Table 2.1.
TABLE 2.1
Maximum allowable built surface for each fire sector
Setting up the | |||||
---|---|---|---|---|---|
TYPE A (m2) | TYPE B (m2) | TYPE C (m2 | |||
UNDER | (1)-(2)-(3) |
| (3) (4) | ||
1 | 2000 | 6000 | WITHOUT LIMIT | ||
1000 | 4000 | 6000 | |||
MEDIUM | (2)-(3) | (2) (3) | (3) (4) | ||
|
3500 | 5000 | 5000 | ||
4 | 400 | 3000 | 4000 | ||
5 | 300 | 2500 | 3500 | ||
NO SUPPORTED | (3) | 6 | |||
3000 | |||||
7 | 1500 | 2500 | |||
8 | UNSUPPORTED | 2000 |
NOTES TO TABLE 2.1
(1) If the fire sector is located at first low street level, the maximum allowable built surface is 400 m2, which can be increased by application of the notes (2) and (3).
(2) If the accessible facade of the industrial establishment is greater than 50 percent of its perimeter, the maximum permissible constructed surfaces, as indicated in Table 2.1, can be multiplied by 1.25.
(3) Where automatic water sprinkler systems which are not required by this Regulation (Annex III) are installed, the maximum permissible constructed surfaces indicated in Table 2.1 may be multiplied by 2.
(Notes (2) and (3) can be applied simultaneously).
(4) In type C configurations, if the activity requires it, the fire sector can have any surface, provided the entire sector has an automatic fixed installation of extinction and the distance to the limits of plots capable of building on them is greater than 10 m.
(5) For industrial establishments of type B, of intrinsic risk under 1, the only activity of which is the storage of Class A materials and in which the construction materials used, including the coatings, are Class A as a whole, the maximum permitted area of the fire sector may be increased up to 10,000 m2.
2.2. The distribution of combustible materials in fire areas in type D and type E configurations shall meet the following requirements:
1. Maximum maximum surface of each stack: 500 m2.
2. ° Maximum volume of each stack: 3500 m3.
3. Maximum maximum height of each stack: 15 m.
4. ° Maximum length of each stack: 45 m if the corridor between piles is ≥ 2.5 m; 20 m if the corridor between piles is ≥ 1,5 m.
3. Materials.
The requirements for fire performance of construction products are defined by determining the class to be achieved, according to the UNE-EN 13501-1 standard for those materials for which there is a harmonised standard and already in The CE marking is effective.
The fire reaction conditions applicable to the building elements shall be justified:
a) By means of the class in each case, first, according to the new European classification.
b) By means of the class that is in second place in parentheses, according to the classification established by the standard UNE-23727.
Construction products whose classification according to standard UNE 23727:1990 is valid for these applications may continue to be used after the end of their coexistence period, until a new regulation of fire reaction for such applications based on their specific risk scenarios. In order to be eligible for this possibility, the products must prove their reaction to the fire in accordance with regulation 23727:1990 by means of a conformity assessment system equivalent to that of the CE marking which is applicable.
3.1 Coating products: Products used as coating or surface finish must be:
In soils: CFL-s1 (M2) or more favorable.
On walls and ceilings: C-s3 d0 (M2), or more favorable.
Non-continuous or smoke removal facilities to be installed on the decks shall be at least Class D-s2d0 (M3) or more favourable.
The materials of the continuous lumen on deck will be B-s1d0 (M1) or more favorable.
The exterior cladding materials of facades will be C-s3d0 (M2) or more favorable.
3.2 Products included in walls and enclosures.
When a product constituting a layer contained in a floor, wall or roof is of a more unfavourable class than that required of the corresponding coating, according to paragraph 3.1, the layer and its coating, as a whole, be at least 30 (RF-30).
This requirement shall not be required in the case of products used in industrial sectors classified according to Annex I as being of low intrinsic risk, located in type B or type C buildings for which the classification Ds3 d0 (M3) or more favourable for the constituent elements of the products used for walls or enclosures.
3.3 Other products: products located inside false ceilings or raised floors, whether or not they are used for thermal insulation and for sound conditioning, such as those which are or are in the form of air ducts air conditioning or ventilation, etc., must be of class C-s3 d0 (M1) or more favourable. The cables shall be non-fire spreaders and with smoke emission and reduced opacity.
3.4 The justification that a building product reaches the required fire reaction class shall be accredited by type or certificate test in accordance with UNE standards, issued by a control body that complies with the requirements of this Regulation. requirements set out in Royal Decree 2200/1995 of 28 December.
According to the different products, the CE marking must be mandatory, the test methods applicable in each case shall be those defined in the UNE-EN and UNE-EN ISO standards. The classification shall be in accordance with UNE-EN 13501-1.
3.5 Petreous, ceramic and metal construction products, as well as glass, mortar, concrete or sand, shall be considered as Class A1 (M0).
4. Fire stability of the supporting building elements.
The requirements for behaviour in relation to the fire of a constructive element are defined by the time in minutes, during which the element must maintain the mechanical stability (or carrying capacity) in the test (a) standard in accordance with the standard corresponding to those included in Commission Decision 2000 /367/EC of 3 May 2000 as amended by Commission Decision 2003 /629/EC.
Fire stability, which is required for building construction elements in the fire sectors of an industrial establishment, can be determined:
1. The adoption of the values set out in this Annex II, paragraph 4.1 or more favourable.
2. º By means of calculation, analytical or numerical, of recognized solvency or justified validity.
4.1 The fire stability of the structural elements with a bearing function and ladders that are route of evacuation shall not be less than the value indicated in Table 2.2.
TABLE 2.2
Stability to the fire of supporting structural elements
intrinsic risk level | TYPE A | TYPE B | TYPE C | |||||
---|---|---|---|---|---|---|---|---|
Basement Plant | Plant on Raking | basement floor | Plant over scratch | R | ||||
| 120 |
LOW | R 120 | R 90 | R 90 | R 60 | R 60 | R 30 |
(EF -120) |
| (EF-90) | (EF-60) | (EF-60) |
| |||
| NOT SUPPORTED | R 120 | R 120 | R 90 | R 90 | R 60 | ||
(EF-120) | (EF-120) | (EF-90) | (EF-90) | (EF-60) | ||||
HIGH | NOT SUPPORTED | 180 | R 120 | R 120 | R 120 | R 120 R 90 | ||
(EF -120) | (EF -120) |
(EF-90) |
Regardless of the fire stability required in Table 2.2, for industrial establishments located in buildings with other uses, the value required of their structural elements shall not be less than that required by the the building as a whole in application of the rules that apply.
4.2 For the main structure of light covers and their supports in plants on scraping, not intended to be used in the evacuation of occupants, provided that it is justified that their failure cannot cause serious damage to the buildings or establishments nearby, do not compromise the stability of other plants or the sectorisation of implanted fires and, if their intrinsic risk is medium or high, have a system for the extraction of smoke, may be adopted the following values:
TABLE 2.3
Type B | Type C | |
---|---|---|
Raking | Raking | |
Risk | R15 (EF-15) | NOT |
Risk | R 30 (EF-30) | R15 (EF-15) |
Riego | R 60 (EF-60) | R30 (EF-30) |
Specific typologies.
4.2.1 Light covers in type A location
Building at height
The 'Type C, scraping' column in Table 2.3 shall also apply to the main structure of light decks in exempted buildings and to a distance greater than three m from the adjacent parcel limit, in Type A configuration
4.2.2 Industrial Naves in Ground Floor.
Table 2.3 will also apply to the main structures of light decks and their supports in ground floor buildings.
4.2.3 Industrial Naves with Enterplant
Table 2.3 will also apply to both the main structure of light covers and to the supports that support a plant, in industrial buildings of type B and C, provided that 90% of the the surface of the establishment, at least, is in the ground floor, and 10 per cent, in the ground floor, and is justified by calculations that the plant can withstand the failure of the cover, and that the evacuation routes, from any industrial establishment point to a plant or building exit, do not exceed 25 meters.
For activities classified as low-intrinsic risk, the plant may be up to 20 percent of the total surface area, and the evacuation routes up to an exit of the building, 50 m, provided the number of occupants are less than 25 people.
4.2.4 Industrial Naves with Crane Bridges.
Table 2.3 will also apply to the main light deck structures which, if any, also bear a crane (e.g. boom crane or crane bridge), which is considered unladen.
4.2.5 Type A industrial birds with medianeries (ground floor building).
For light covers of type A industrial buildings with medianeries, the provisions of paragraph 5.4. shall apply.
The main structure of the cover can adopt the fire stability values of table 2.3 corresponding to the type B setting values.
This condition will not be applicable when the cover is shared by two or more distinct industrial establishments.
4.3 In single-floor buildings with light cover, when the total area of the fire sector is protected by an installation of automatic water sprinklers and a smoke evacuation system, the values of the The following values may be adopted by the fire stability of the supporting structures:
TABLE 2.4
Single-site | |||
---|---|---|---|
Type A | Type B | Type C | |
Risk | R 60 (EF-60) | NOT REQUIRED |
R 90 (EF-15) |
| 15 (EF-15) |
NOT | |||
Risk | NOT SUPPORTED | R 30 (EF-30) | R15 (EF-15) |
Note: When, according to Table 2.3 or Table 2.4, it is permissible not to justify the stability of the structure fire, it shall be marked in the main access of the building for the staff of the services of extinction is aware of this particularity.
In single-plant industrial establishments, or with administrative areas in more than one plant but compartmentalized from industrial use according to their specific regulations, located in C-type buildings, separated at least 10 m of the boundaries of plots with the possibility of building on them, it will not be necessary to justify the stability to the fire of the structure.
4.4 The justification that a supporting constructive element reaches the required fire stability value shall be demonstrated:
(a) By contrast to the values set out in Appendix 1 of the Basic Building Standard: fire protection conditions in buildings, if any.
b) By means of conformity marking, with UNE standards or certificate of conformity, with the technical specifications indicated in this Regulation.
Conformity marks, certificates of conformity and type tests shall be issued by a control body which complies with the requirements of Royal Decree 2200/1995 of 28 December.
c) By application of a theoretical-experimental calculation method of recognized prestige.
5. Fire resistance of building construction elements.
The requirements of behavior in the fire of a building element of enclosure (or delimiter) are defined by the times during which the element must maintain the following conditions, during the test normalised in accordance with the standard corresponding to those contained in Commission Decision 2000 /367/EC of 3 May 2000 as amended by Commission Decision 2003 /629/EC:
a) R. portant capacity
b) Integrity in the way of flames and hot gases E.
c) Thermal insulation I.
These three assumptions are considered equivalent in those specified in UNE 23093.
a) Mechanical stability (or carrying capacity).
b) Stay at the pace of flames or hot gases.
c) Non-emission of flammable gases in the face not exposed to fire.
d) Thermal insulation sufficient to prevent the non-fire-exposed face from exceeding the temperatures set by the corresponding standard.
5.1 The fire resistance of the building blocks of a fire sector with respect to other elements shall not be less than the fire stability required in Table 2.2 for constructive elements with a function carrier in that fire sector.
5.2 Fire resistance of any medianery or wall adjacent to another establishment shall be at least
| No portant function | With portant |
---|---|---|
Risk | The 120 | REI 120 (RF-120) |
Risk medium | The 180 | REI 180 (RF-180) |
High Risk | The 240 | REI 240 (RF-240) |
5.3 When a medium, a forged or a wall that compartmentalized fire sectors to a facade, the fire resistance of this shall be, at least, equal to half of the required to that constructive element, in a a strip whose width shall be at least one m.
When the building element is involved in a quiebrum of the facade and the angle formed by the two outer planes of the facade is less than 135th the width of the strip shall be at least two m.
The width of this strip must be measured on the plane of the facade and, if there are projections in it that prevent the passage of the flames, the width may be reduced in the dimension of the said projection.
5.4 When a medianery or a constructive element of compartmentalization in fire sectors takes on the cover, the fire resistance of this shall be at least equal to half of the required to that constructive element, in a strip whose width is equal to one m. This strip may be found:
a) Integrated into the cover itself, provided that the remaining strip is justified after the collapse of the parts of the non-resistant cover.
b) Fixed in the structure of the cover, when the cover has at least the same stability to the fire as the resistance required of the strip.
(c) Formed by a barrier of a m wide that justifies the required fire resistance and is below the cover fixed to the medianery. The barrier shall in no case be installed at a distance greater than 40 cm from the bottom of the deck.
The justification for the fire resistance of such strip shall be carried out by type test. This test shall be carried out in the final conditions of use, including the support or restraint systems.
However, if the medianery or the compartmentator element is prolonged one m above the cover, at least, it is not necessary for the cover to meet the above condition.
5.5 The minimum distance, measured in horizontal projection, between a window and a hollow, or a lusirarium, of a cover shall be greater than 2,50 m when such holes and windows belong to different fire sectors and distance vertical, including less than five m.
5.6 The doors of passage between two fire sectors shall have a fire resistance, at least equal to half of that required for the element separating both fire sectors, or for the fourth part of the fire when the step is taken. perform through a previous lobby.
Mobile compartmentators shall not be assimilated to passage doors for the purpose of reducing their fire resistance.
5.7 All voids, horizontal or vertical, that communicate a fire sector with an outer space to it must be sealed so that they maintain a fire resistance that will not be less than:
(a) Fire resistance in the fire sector, in the case of floodgates of air canalisations of ventilation, heating or air conditioning.
(b) Fire resistance in the fire sector, in the case of sealing of stroke holes or trays of electrical cables.
(c) A means of fire resistance in the fire sector, in the case of sealing of non-flammable and non-combustible liquid canalisations passing holes.
(d) Fire resistance in the fire sector, in the case of sealed passage holes for flammable liquids or fuels.
e) A means of fire resistance in the fire sector, in the case of record-setting caps on facilities.
f) Fire resistance in the fire sector, in the case of practicable closures of service galleries communicated with the fire sector.
g) Fire resistance in the fire sector, in the case of gates or automatic closing screens of vertical hollows of maintenance, discharge of hoppers or vertical communication of other use.
When pipes that pass through a fire sector are made of combustible or fusible material, the sealing system must ensure that the internal space that leaves the pipe to melt or burn is also sealed.
Systems including conduits, both vertical and horizontal, that pass through compartmentalization elements and whose function does not allow the use of gates (smoke extraction, ventilation of escape routes, etc.), be resistant to fire or be adequately protected throughout its journey with the same degree of fire resistance as the elements crossed, and tested in accordance with the applicable UNE-EN standards.
It will not be necessary to comply with these requirements if the communication of the fire sector through the hole is to the outer space of the building, nor in the case of pressure water pipes, provided that the gap of passage is adjusted to them.
5.8 The fire resistance of the enclosure that delimits a type D establishment (except those at risk under 1), with respect to the limits of plots with the possibility of building in them, must be at least 120, unless the an activity is carried out at a distance equal to or greater than five m from that or the applicable urban planning guarantees such distance between the fire area and the line.
5.9 The justification for a building construction element to reach the required fire resistance value shall be demonstrated:
(a) By contrast to the values set out in Appendix 1 of the Basic Building Standard: fire protection conditions in buildings, or in the implementing rules where applicable.
b) By means of a mark in accordance with UNE standards or certificate of conformity or type test with the technical standards and specifications set out in Annex IV to this Regulation.
Conformity marks, certificates of conformity and type tests shall be issued by a control body which complies with the requirements of Royal Decree 2200/1995 of 28 December.
6. Evacuation of industrial establishments.
6.1 For the application of the requirements regarding the evacuation of industrial establishments, their occupation, P, will be determined, deduced from the following expressions:
P = 1.10 p, when p < 100.
P = 110 + 1.05 (p -100), when 100 < p < 200.
P = 215 + 1.03 (p-200), when 200 < p < 500.
P = 524 + 1.01 (p-500), when 500 < p.
Where p represents the number of people in the fire sector, according to the labor documentation that legalizes the operation of the activity.
The values obtained for P, according to the above expressions, will be rounded to the immediately top integer.
6.2 When in a building of type A co-exist industrial and non-industrial activities, the evacuation of spaces occupied by all uses that is carried out through the common elements must satisfy the conditions laid down in the basic building standard: fire protection conditions in buildings or equivalent standards which are applicable, or in paragraph 6.3, in the case where all establishments are used industrial.
The evacuation of the industrial establishment may be carried out by common elements of the building, provided that access to them is carried out through a previous lobby.
If the number of employees in the industrial establishment is more than 50 people, you must have an independent exit from the rest of the building.
6.3 The evacuation of industrial establishments located in type B buildings (as shown in Annex 1) must satisfy the conditions set out below. The reference in his case to the articles cited in the basic building standard: fire protection conditions in buildings shall be understood as the effects of definitions, general characteristics, calculation, etc., when they do not specify specific values or conditions.
1. Elements of the evacuation: evacuation source, evacuation routes, evacuation height, ramps, lifts, escalators, ramps and mobile corridors and exits are defined in accordance with Article 7 of the NBE-CPI/96, paragraph 7.1, subsections 7.1.1, 7.1.2, 7.1.3, 7.1.4, 7.1.5 and 7.1.6, respectively.
2. Number and layout of the exits: in addition to taking into account the provisions of Article 7 of the NBE-CPI/96, paragraph 7.2, the following shall be extended:
Industrial establishments classified in accordance with Annex 1 to this Regulation as being of high intrinsic risk should have two alternative outlets.
Average intrinsic risk should have two outputs when their number of employees is more than 50 people.
Maximum distances from the evacuation routes of fire sectors in industrial establishments shall not exceed the values indicated in the table below and shall prevail over those set out in Article 7.2 of the NBE/CPI/96:
Length of evacuation path based on number of outputs
Risk | 1 single travel output | 2 alternative |
---|---|---|
(*) | 35 m (**) | 50 m |
| 25 m (***) | 50 m |
High | - | 25 m |
(*) For production or storage activities classified as low-level risk 1, where it is justified that the materials involved are exclusively of Class A and the construction products, including Coatings, as well as Class A, may be increased by the maximum distance of evacuation routes up to 100 m.
(**) The distance may be increased to 50 m if the occupancy is less than 25 people.
(***) Distance may be increased to 35 m if occupancy is less than 25 people.
In areas of sectors whose activity prevents the presence of personnel (e.g. automatic operating warehouses), evacuation requirements will apply to maintenance areas. This particularity must be justified.
3. Provision of stairs and lifting devices: in accordance with Article 7 of the NBE-CPI/96, paragraph 7.3, sub-paragraphs 7.3.1, paragraphs a) and c), 7.3.2, and 7.3.3.
The stairs to be provided for descending evacuation shall be protected, in accordance with paragraph 10.1 of the NBE/CPI/96, when used for the evacuation of industrial establishments which, depending on their level of risk intrinsic, exceed the following evacuation height:
High risk: 10 m.
Average risk: 15 m.
Risk under: 20 m.
Ascending evacuation ladders will always be protected.
4. Sizing of exits, corridors and stairways: in accordance with Article 7 of the NBE-CPI/96, paragraph 7.4, sub-paragraphs 7.4.1, 7.4.2 and 7.4.3.
5. Characteristics of the doors: in accordance with Article 8 of the NBE-CPI/96, paragraph 8.1.
These conditions will not apply to the doors of the cold chambers.
6. Characteristics of the corridors: in accordance with Article 8 of the NBE-CPI/96, paragraph 8.2.b).
7. Characteristics of the stairs: in accordance with Article 9 of the NBE-CPI/96, paragraphs (a), (b), (c), (d) and (e)
8. Characteristics of the corridors and of the protected staircases and of the previous vestibule: in accordance with Article 10 of the NBE-CPI/96, paragraphs 10.1, 10.2 and 10.3.
9. Signalling and lighting: in accordance with Article 12 of the NBE-CPI/96, paragraphs 12.1, 12.2 and 12.3; in addition, they shall comply with the provisions of Royal Decree 485/1997 of 14 April.
6.4 The evacuation of industrial establishments located in C-type buildings (as shown in Annex 1) must satisfy the following conditions:
1. Evacuation elements: are defined as in paragraph 6.3.1 of this Annex.
2. Number and layout of the exits: as in paragraph 6.3.2 of this Annex.
3. Provision of stairs and lifting devices: as in paragraph 6.3.3 of this Annex.
4. Sizing of exits, corridors and stairways: as in paragraph 6.3.4 of this annex.
5. Door characteristics: as in paragraph 6.3.5 of this annex, except that sliding, or sliding, manually operable sliding doors are permitted as exit doors.
6. Characteristics of the corridors: as in paragraph 6.3.6 of this Annex.
7. Characteristics of the stairs: as in paragraph 6.3.7 of this Annex.
8. Characteristics of the corridors and of the protected staircases and of the previous vestibule: as in paragraph 6.3.8 of this annex.
9. Signalling and lighting: as in paragraph 6.3.9 of this Annex.
6.5 The provisions on evacuation and signalling in industrial establishments which are located in type D and E configurations shall be in accordance with the provisions of Royal Decree 485/1997 of 14 April 1997 and in Royal Decree 486/1997 of 14 April 1997 and shall also comply with the following requirements:
Width of the perimeter strip: the height of the stack and at least 5 m.
Width for emergency access paths: 4.5 m.
Maximum separation between emergency paths: 65 m.
Minimal width of aisles between stacks: 1.5 m.
7. Ventilation and removal of fumes and gases from combustion in industrial buildings.
The elimination of the fumes and gases of combustion, and, with them, of the heat generated, of the spaces occupied by sectors of fire of industrial establishments must be carried out according to the typology of the building in relationship to the characteristics that determine the movement of the smoke.
7.1 Smoke Evacuation System will be available:
a) Sectors with production activities:
1. Medium intrinsic risk and built surface ≥ 2000 m2.
2. High intrinsic risk and built surface ≥1000 m2.
b) Sectors with storage activities:
1. Medium intrinsic risk and built surface ≥ 1000 m2.
2. High intrinsic risk and built surface ≥ 800 m2.
For smaller surface ships, the following minimum values of the aerodynamic smoke evacuation surface may be applied.
a) Fire sectors with production, assembly, transformation, repair and other activities other than storage if:
1. º They are located in the ground floor and their intrinsic risk level is high or medium, at the rate of a minimum aerodynamic surface of 0.5 m2/150 m2 or fraction.
2. º They are located in any plant on a scraper and its intrinsic risk level is high or medium, at the rate of a minimum aerodynamic surface of 0.5 m2 /200 m2 or fraction.
b) Fire sectors with storage activities if:
1. º They are located in the ground floor and their intrinsic risk level is high or medium, at the rate of a minimum aerodynamic surface of 0.5 m2/100 m2 or fraction.
2. º They are located in any plant on a scraper and its intrinsic risk level is high or medium, at the rate of a minimum aerodynamic surface of 0.5 m2/150 m2 or fraction.
Ventilation will be natural unless the location of the sector prevents it; in such a case, it may be forced.
Gaps will be evenly spread across the upper part of the sector, either in high-facing or covered areas.
Gaps must be manually or automatically practicable.
In addition, there should be gaps for air intake in the lower part of the sector, in the same proportion of the required area for the exit of the smoke, and the gaps in the doors of access to the sector may be computed.
7.2 The design and execution of the smoke and heat control systems will be performed according to the UNE-23 585 standard. In duly justified cases other recognised international standards may be used.
8. Storage.
The storage systems are characterized by storage systems, when they are performed on metal shelves. They are classified as self-supporting or independent, which, in both cases, may be automatic and manual.
1. Self-supporting storage system. They support, in addition to the stored merchandise, the facade enclosures and the cover, and act as a cover structure.
2. Independent storage system. They only support the stored merchandise and are detachable and independent structural elements of the cover structure.
3. Automatic storage system. The load units that are stored are transported and raised by an automatic operation, without the presence of people in the warehouse.
4. Manual storage system. The load units that are stored are transported and raised through manual operation, with the presence of people in the warehouse.
8.1 Metal shelving storage system. Requirements.
1. The materials of racks, stringers, metal panels, latches, beams, metal floors and other metal elements and accessories that make up the system must be of steel of Class A1 (M0) (see paragraph 3 of this Annex).
2. Painted coatings with thicknesses less than 100 μ must be of class Bs3d0 (M1). This coating must be a non-flammable material, duly accredited by an approved laboratory by means of tests according to standard.
3. Linings with thicknesses less than 100μ must be of the class Bs3d0 (M1).
4. The following values may be adopted for the main structure of storage systems with metal shelving on scraping or low-level scraping systems:
Independent or self-supporting storage system manually | ||||||
---|---|---|---|---|---|---|
A | Type B | Type C | ||||
Automatic Water Rocers | Automatic Water Rocers | Automatic Water Rocers | ||||
| YES | NO | YES | NO | ||
Low Risk | R30 (EF-30) | R15 (EF-15) | R15 (EF-15) | Not required | Not required | Do not know |
Risk | R60 (EF-60) | R30 (EF-30) | R30 (EF-30) | R15 (EF-15) | R15 (EF-15) | Not |
Risk |
|
| R60 (EF-60) | R30 (EF-30) | R30 (EF-30) | R15 (EF-15) |
Independent or self-supporting storage system automatically | ||||||
---|---|---|---|---|---|---|
Type A | Type B | Type C | ||||
Automatic Water Rocers | Automatic Water Rocers | Automatic Water Rocers | ||||
| YES | NO | YES | NO | ||
Low Risk | R15 (EF-15) | Not requires | Not required | Not required | Not required | Do not |
Risk | R30 (EF-30) | R15 (EF-15) | R15 (EF-15) | Not Required | Not requires | Not |
Risk |
|
| R30 (EF-30) | R15 (EF-15) | R15 (EF-15) | Not required |
5. The evacuation in industrial establishments with separate storage systems or manually operated self-carriers shall be the same as that specified in the following paragraph 6 and sub-sections of this Annex.
6. The evacuation in industrial establishments with self-operated independent storage systems or self-supporting storage systems shall be the same as that specified in the following paragraph 6 and sub-sections of this Annex and applicable only in the case of: areas intended for maintenance which is the only area where there can be a presence of people.
8.2 The storage systems on manually operated metal shelves must meet the following requirements:
(a) In the case of automatic sprinkler system, respect the holguras for the proper functioning of the extinction system.
b) The dimensions of the shelves will have no more limitation than the one corresponding to the designed storage system.
c) Longitudinal steps and evacuation paths shall have a free width equal to or greater than m.
d) Cross-shelving steps must be spaced apart from each other in maximum lengths of 10 m for manual storage and 20 m for machined storage, which can be doubled if the occupancy in the storage is less than 25 people. The width of the steps shall be equal to the width specified in paragraph (c).
8.3 The storage systems on metal shelves operated automatically must comply with paragraphs (a) and (b) of the previous paragraph, in addition to the following requirements:
a) Be solidly anchored to the ground.
b) Dispose of land take.
(c) From the top of the stored goods there shall be a minimum free gap to the roof of a m.
Note: The building requirements of the systems are complemented by the other parts of this annex.
9. Technical facilities for the services of industrial establishments.
Electrical services installations (including own generation, distribution, taking, disposal and consumption of electrical energy), thermal energy installations from solid, liquid or gaseous fuels (including storage and distribution of fuel, equipment or equipment for consumption and thermal conditioning), refrigeration facilities, mechanical energy use facilities (including generation, storage, distribution, etc.). compressed air consumption equipment or equipment) and the facilities of movement of materials, maintenance and elevators of industrial establishments will meet the requirements established by the regulations in force that specifically affect them.
In existing industrial establishments, these facilities may continue according to the regulations applicable at the time of their implementation, as long as they are covered by it.
In the event that electrical cables power equipment that must remain in operation during a fire, they must be protected to maintain the electrical current for the time required for the structure of the ship. in that you are.
10. Forest fire risk.
The location of industries on land adjacent to the forest causes fire risk in a double direction: danger to the industry, since a forest fire can affect it, and danger of a fire in an industry may cause a forest fire.
The built-up or built-up area should preferably have two alternative paths of access, each of which must meet the conditions of approach to buildings (see paragraph A. 2.).
When the two alternative paths are not available, the single access must end in a circular-shaped bag of 12.5 m radius.
High and medium-risk industrial establishments located near a forest mass must maintain a 25 m wide perimeter strip permanently free of low and bushy vegetation with the clarified forest mass and the low branches pruned.
In places of strong wind and close forest mass the distance established by 100 percent, at least in the directions of the prevailing winds, must be increased.
ANNEX III
Requirements of fire protection facilities of industrial establishments
1. All appliances, equipment, systems and components of fire protection facilities of industrial establishments, as well as the design, execution, commissioning and maintenance of their installations, shall comply with the requirements of this Directive. the provisions of the Regulation on fire protection installations, approved by Royal Decree 1942/1993 of 5 November 1993, and the Order of 16 April 1998, on rules of procedure and the development of that order.
2. The installers and maintainers of the fire protection facilities referred to in the previous paragraph shall comply with the requirements laid down by the Regulation on fire protection facilities approved by the Commission. Royal Decree 1942/1993 of 5 November 1993 and provisions supplementing it.
3. Automatic fire detection systems.
3.1 Automatic fire detection systems shall be installed in the fire sectors of industrial establishments when they are developed:
a) Production, mount, transform, repair, or other activities other than storage if:
1. º They are located in type A buildings and their total built surface is 300 m2 or higher.
2. º They are located in B-type buildings, their intrinsic risk level is medium and their total built surface is 2,000 m2 or higher.
3. º They are located in B-type buildings, their intrinsic risk level is high and their total built surface is 1,000 m2 or higher.
4. º They are located in C-type buildings, their intrinsic risk level is medium and their total built surface is 3,000 m2 or higher.
5. º They are located in C-type buildings, their intrinsic risk level is high and their total built surface is 2,000 m2 or higher.
b) Storage activities if:
1. º They are located in type A buildings and their total built area is 150 m2 or higher.
2. º They are located in B-type buildings, their intrinsic risk level is medium and their total built surface is 1,000 m2 or higher.
3. º They are located in B-type buildings, their intrinsic risk level is high and their total built area is 500 m2 or higher.
4. º They are located in C-type buildings, their intrinsic risk level is medium and their total built surface is 1,500 m2 or higher.
5. º They are located in C-type buildings, their intrinsic risk level is high and their total built surface is 800 m2 or higher.
NOTE: Where the installation of an automatic fire detection system is required and the design conditions (paragraph 1 of this Annex) result in the use of thermal detectors, it may be replaced by an installation. of automatic water sprinklers.
4. Manual fire alarm systems.
4.1 Manual fire alarm systems shall be installed in the fire sectors of industrial establishments when they are developed:
a) Production, assembly, transformation, repair, or other activities other than storage, if:
1. º Your total built surface is 1,000 m2 or higher, or
2. The installation of automatic fire detection systems is not required, according to section 3.1 of this annex.
b) Storage activities, if:
1. Your total built surface is 800 m2 or higher, or
2. The installation of automatic fire detection systems is not required, according to section 3.1 of this annex.
4.2 Where the installation of a manual fire alarm system is required, a pulsator shall be placed, in any case, together with each evacuation exit from the fire sector, and the maximum distance to be travelled from any point to reach a push button must not exceed 25 m.
5. Alarm communication systems.
5.1 Alarm communication systems will be installed in all sectors of fire in industrial establishments, if the sum of the built area of all the fire sectors of the industrial establishment is 10,000 m2 or higher.
5.2 The acoustic signal transmitted by the fire alarm communication system will make it possible to differentiate whether it is an alarm for "partial emergency" or "general emergency", and the use of a system of public address.
6. Fire water supply systems.
6.1 A fire water supply system ("fire water network") shall be installed if:
is required by existing provisions governing industry or sector specific industrial activities in accordance with Article 1 of this Regulation.
(b) Where necessary to provide service, in the calculated flow, pressure and reserve conditions, to one or more fire fighting systems, such as
Equipped Fire Hydrants Network (BIE).
External hydrant network.
Automatic sprinklers.
Spray water.
Foam.
When in an industrial establishment installation there are several of these systems, the water flow and reserve will be calculated by considering the minimum operation concurrency that is then established, and which is summarizes in the attached table.
BIE and hydrant systems:
[1] + [2] case (a) Buildings with plants at scratch level only:
Water flow required by the hydrant system (QH).
Water reserve required for the hydrant system (RH).
[1] + [2] case (b) Buildings with plants on scratch:
Sum of flows required for BIE (QB) and for hydrants (QH).
Water reserve sum required for BIE (RB) and for hydrants (RH).
BIE and automatic sprinkler systems [1] + [3]:
Water flow required for automatic sprayers (QRA).
Water reserve required for automatic sprayers (RRA).
BIE, hydrant and automatic sprinkler systems [1] + [2] + [3]:
50 per cent flow rate required for hydrants (0.5 QH) as per table in section 7.2, and the required for automatic sprinklers (QRA).
Sum of 50 percent of water reserve required for hydrants (0.5 RH) and required for automatic sprinklers (RRA).
Automatic sprinkler and hydrant systems [2] + [3]:
The minimum required flow rate will be the one required for the system that requires the highest flow rate.
The minimum required reserve will be required for the installation of the system that requires the largest water reserve.
Hydrant and Sprayed Water Systems [2] + [4]:
The minimum required flow rate will be the one required for the installation of the system that requires the highest flow rate.
The minimum required reserve will be required for the installation of the system that requires the largest water reserve.
Water and foam systems [2] + [5]:
The minimum required flow rate will be the one required for the installation of the system that requires the highest flow rate.
The minimum required reserve will be required for the installation of the system that requires the largest water reserve.
Water, pulverized water and foam systems [2] + [4] + [5]:
Sum of required flow rates for pulverized water (QAP) and for foam (QE), and in any case, at least, the flow of hydrants.
Sum of water reserves required for pulverized water (RAP) and for foam (RE), which, in any case, will be the required reserve for the hydrant system.
Automatic sprinkler and spray water systems [3] + [4]:
The minimum required flow rate will be the one required for the system that requires the highest flow rate.
The minimum required reserve will be required for the installation of the system that requires the largest water reserve.
Automatic and foam sprinkler systems [3] + [5]:
The minimum required flow rate will be the one required for the installation of the system that requires greater flow.
The minimum required reserve will be required for the installation of the system that requires the largest water reserve.
Spray and foam water systems [4] + [5]:
Sum of required flow rates for spray water (QAP) and for foam (QE).
Sum of water reserves required for pulverized water (RAP) and for foam (RE).
SUMMARY TABLE FOR FLOW CALCULATION (Q) AND WATER RESERVE (R) WHEN MULTIPLE EXTINCTION SYSTEMS COEXIST IN AN INSTALLATION
INSTALLATION TYPE | BIE [1] | HIDDEN [2] | AUTOMATIC SPRAYERS [3] | SPRAYED water [4] | FOAM [5] | ||
---|---|---|---|---|---|---|---|
[1] BIE | B/RB | (a) QH/RH) (b) QB+ QH/RB+ RH) | QRA/RRA | ||||
0.5 QH + QRA 0.5 RH + RRA | |||||||
HIDRBEFORE | (a) QH/RH (b) QB + QH/RB + RH | 0.5 QH + QRA 0.5 RH + RRA | QH/RH | Q major R major QH | QAP/ Q major, R major (one installation) | ||
AP + QE RAP + RE | |||||||
3] ROCIATORS AUTOMATIC | QRA/RRa | Q major R major (one instance.) | QRA/RRA | Q major, R major (one installation) | Q major, R major (one installation) | ||
sprayed water [4] | 0.5 QH + QAP/0.5 RH + RAP | QAP + QE RAP + RE | Q major, R major (one installing) | QAP/RAP | QAP + QE RAP + RE |
||
FOAM [5] | Q major R major (one instance.) | Q major, R major (one installation) | QAP + QE RAP + RE | QE/RE |
SOURCING CATEGORY (as standard UNE 23,500)
It will be adopted according to the installed extinction systems:
BIE: Category III.
hydrants: Category II.
Spray water: Category I.
Foam: Category I.
Automatic sprinklers (according to UNE-EN 12845).
7. External hydrant systems.
7.1 Needs.
An external hydrant system will be installed if:
(a) The provisions in force governing sectoral or specific industrial activities are required in accordance with Article 1 of this Regulation.
b) Concurren the circumstances that are reflected in the following table:
TABLE 3.1
External hydrants depending on the configuration of the zone, its built surface, and its intrinsic risk level
Area of the sector or area of fire (m2) | Intrinsic | ||||
---|---|---|---|---|---|
| Medium |
|
|||
A | ≥ 300 ≥ 1000 | NO S* | YES YES |
| |
B | ≥ 1000 ≥ 2500 ≥ 3500 | NO NO YES | NO YES YES | YES | |
≥ 2000 ≥ 3500 | NO NO | NO YES | YES
| ||
D or E |
≥ 5000 ≥ 15000 | YES YES | YES YES |
Note: When a hydrant system is required, the installation must protect all fire zones that constitute the industrial establishment.
* Not required when the risk is low 1 (table 1.3).
7.2 Deployment.
The number of external hydrants to install will be determined by having the following conditions met:
a) The protected zone for each of them is the cover for a radius of 40 m, measured horizontally from the site of the hydrant.
b) At least one of the hydrants (located, if possible, at the entrance) must have a 100 mm output.
c) The distance between the site of each hydrant and the outer boundary of the protected building or zone, measured perpendicularly to the facade, must be at least five m.
If there are vials that make it difficult to meet these distances, they will be justified.
(d) Where, for reasons of location, local conditions do not allow the installation of external hydrants to be justified, reasoned and substantiated.
7.3 Required Flow and Autonomy.
Water needs to protect each of the areas (areas or sectors of fire) that require a hydrant system will be made according to the values of the following table.
WATER NEEDS FOR EXTERNAL HYDRANTS
intrinsic risk | ||||||||
---|---|---|---|---|---|---|---|---|
| Medium | High | ||||||
Type | Flow (L/Min.) | Auton. (Min) | CauDal (L/Min.) | Auton. (Min) | Flow (L/Min.) | Auton. (Min) | ||
A | 500 | 30 | 1000 |
60 | - | - | ||
B | 500 | 30 | 1000 | 60 | 1000 | 90 | ||
500 | 30 | 1500 | 500 | 500 | 60 | 2000 | 90 | |
D and E | 1000 | 30 | 2000 | 60 | 3000 | 90 |
NOTES:
1) When in an industrial establishment, consisting of type C, D or E configurations, there are fuel storage in the exterior, the flow rates indicated in the table will be increased by 500 l/min.
2) The minimum pressure in the hydrants ' outlet mouths shall be five bar when the indicated flow rates are being discharged.
3) For establishments for which the non-performance of a specific installation is justified by reason of its location, if there is a public network of hydrants, the situation of the nearest hydrant and the situation of the hydrant shall be indicated in the project. guaranteed minimum pressure.
8. Fire extinguishers.
8.1 Portable fire extinguishers will be installed in all fire sectors of industrial establishments.
Note: In the areas of automatically operated storage, where activity prevents people from accessing, the non-installation of fire extinguishers can be justified
The extinguishing agent used shall be selected according to Table I-1 of Appendix 1 to the Fire Protection Facilities Regulation, approved by Royal Decree 1942/1993 of 5 November.
Where fuels of Class A and Class B are co-exist in the fire sector, the fire class of the fire sector shall be considered to be A or B when the fire load contributed by class A or class B fuels, respectively, be at least 90 percent of the sector's fire load. In another case, the fire class of the fire sector shall be considered A-B.
8.2 If the fire class of the fire sector is A or B, the fire extinguishing envelope shall be determined in accordance with Table 3.1 or Table 3.2, respectively.
If the fire class of the fire sector is A-B, the envelope of fire extinguishers shall be determined by adding those necessary for each class of fire (A and B), independently assessed, according to Table 3.1 and Table 1. 3.2, respectively.
When in the fire sector there are class C fuels that can provide a fire load that is at least 90 percent of the sector's fire load, the allocation of fire extinguishers will be determined according to the specific sectoral regulations affecting them. In another case, the allocation of fire extinguishers shall not be increased if those required by the presence of other fuels (A and/or B) are suitable for class C fires.
When in the fire sector there are class D fuels, extinguishing agents of specific characteristics suitable for the nature of the fuel, which may be projected on fire with fire extinguishers, or means shall be used. manuals, in accordance with the situation and the particular recommendations of the manufacturer of the extinguishing agent.
TABLE 3.1
Determination of the provision of portable fire extinguishers in fire-load sectors contributed by class A fuels
Minimum efficiency of the fire extinguisher | Maximum fire sector protected | |
---|---|---|
| 21A | Up to 600 m2 (one more extinguisher per 200 m2, or fraction, in excess) |
21A | Up to 400 m2 (one more extinguisher per 200 m2, or fraction, in excess) | |
High | 34A | Up to 300 m2 (one more extinguisher per 200 m2, or fraction, in excess). |
TABLE 3.2
Determination of the envelope of portable fire extinguishers in fire-load sectors contributed by class B fuels
MAXIMUM VOLUME, V (1), OF LIQUID FUELS IN THE FIRE SECTOR (1) (2) | ||||||
---|---|---|---|---|---|---|
V≤20 | 2 | 50 | 100 | |||
B | 113 B | 113 B | 113 B | 144 B | 233 B |
NOTES:
(1) When more than 50 percent of the volume of liquid fuels, V, is contained in perfectly closed metal containers, the minimum efficiency of the extinguisher can be reduced to the immediately preceding class B, according to the UNE-EN 3-7 standard.
(2) When the volume of liquid fuels in the fire sector, V, exceeds 200 l, the envelope of portable fire extinguishers with movable extinguishers on wheels, of 50 kg of dust BC, or ABC, shall be increased at the rate of:
A fire extinguisher, if:
200 l < V ≤ 750 l.
Two extinguishers, if:
750 l < V ≤ 2000 l.
If the volume of class B fuels exceeds 2000 l, the protection of the fire sector shall be determined in accordance with the specific sectoral regulations affecting it.
8.3 The use of fire extinguishing agents on fires which are developed in the presence of electrical appliances, frames, conductors and other elements under electrical voltage exceeding 24 V is not permitted. of these shall be made with carbon dioxide extinguishers, or BC or ABC dry powder, the load of which shall be determined according to the size of the protected object with a minimum value of five kg of carbon dioxide and six kg of dry BC or ABC powder.
8.4 The location of portable fire extinguishers will allow them to be easily visible and accessible, located close to the points where the fire and its distribution are most likely to start. it shall be such that the maximum horizontal travel, from any point in the fire sector to the fire extinguisher, does not exceed 15 m.
8.5 Portable fire extinguishers shall be installed in all fire areas of industrial establishments (type D and type E), except in areas where the intrinsic risk level is low 1.
The envelope shall be in accordance with the above paragraphs, except the maximum journey to one of them, which may be extended to 25 m.
9. Fire hydrant systems equipped.
9.1 Fire hydrant systems equipped in the fire sectors of industrial establishments shall be installed if:
a) They are located in type A buildings and their total built surface is 300 m2 or higher.
b) They are located in B-type buildings, their intrinsic risk level is medium and their total built area is 500 m2 or higher.
c) They are located in B-type buildings, their intrinsic risk level is high and their total built surface is 200 m2 or higher.
d) They are located in C-type buildings, their intrinsic risk level is medium and their total built surface is 1,000 m2 or higher.
e) They are located in C-type buildings, their intrinsic risk level is high and their total built surface is 500 m2 or higher.
f) They are establishments of type D or E configurations, their intrinsic risk level is high and the occupied surface is 5,000 m2 or higher.
Note: In the areas of automatically operated storage, where the activity prevents people from accessing, the non-installation of fire hydrants may be justified.
9.2 Type of BIE and water needs.
In addition to the requirements laid down in the Fire Protection Facilities Regulation, the following hydraulic conditions shall be met for their disposal and characteristics:
establishment intrinsic risk level | BIE TYPE | CONCURRENCY | AUTONOMY | |
---|---|---|---|---|
| DN 25 mm |
2 | 60 min | |
MEDIUM | DN 45 mm * | 2 | 60 min | |
HIGH | DN 45 mm * | 3 | 90 min |
* BIE 25 mm shall be admitted as an additional take of 45mm, and shall be considered, for hydraulic calculation purposes, as BIE of 45 mm.
The unit flow rate shall be that corresponding to the dynamic pressure available at the entry of the BIE, when the indicated BIE number, the "K" factor of the set, provided by the manufacturer, works at the same time. of the equipment. The minimum equivalent diameters shall be 10 mm for BIE of 25 and 13 mm for BIE of 45 mm.
The pressure on the nozzle must be checked not to be less than two bar and not more than five bar, and pressure reducing devices shall be provided if necessary.
10. Dry column systems.
10.1 Dry column systems shall be installed in industrial establishments if they are medium or high intrinsic risk and their evacuation height is 15 m or greater.
10.2 The exit mouths of the dry column shall be located in staircases or in vestibulos prior to them.
11. Automatic water sprinkler systems.
Automatic water sprinkler systems shall be installed in the fire sectors of industrial establishments when they are developed:
a) Production, mount, transform, repair, or other activities other than storage if:
1. º They are located in type A buildings, their intrinsic risk level is medium and their total built surface is 500 m2 or higher.
2. º They are located in B-type buildings, their intrinsic risk level is medium and their total built surface is 2500 m2 or higher.
3. º They are located in B-type buildings, their intrinsic risk level is high and their total built surface is 1000 m2 or higher.
4. º They are located in C-type buildings, their intrinsic risk level is medium and their total built surface is 3500 m2 or higher.
5. º They are located in C-type buildings, their intrinsic risk level is high and their total built surface is 2000 m2 or higher.
b) Storage activities if:
1. º They are located in type A buildings, their intrinsic risk level is medium and their total built surface is 300 m2 or higher.
2. º They are located in B-type buildings, their intrinsic risk level is medium and their total constructed surface is 1500 m2 or higher.
3. º They are located in B-type buildings, their intrinsic risk level is high and their total built surface is 800 m2 or higher.
4. º They are located in C-type buildings, their intrinsic risk level is medium and their total built surface is 2000 m2 or higher.
5. º They are located in C-type buildings, their intrinsic risk level is high and their total built surface is 1000 m2 or higher.
NOTE:
When installing a system of automatic water sprinklers, concurrently with that of an automatic fire detection system employing thermal detectors according to the design conditions (paragraph 1 of this Annex) the requirement of the detection system shall be cancelled.
12. Pulverized water systems.
Sprayed water systems will be installed when the configuration, content, process and location of the risk require cooling parts of the risk to ensure the stability of its structure, and to avoid the effects of heat. of radiation emitted from another nearby risk.
And in those areas of fire and fire areas where installation is required in accordance with the existing provisions governing fire protection in specific or sectoral industrial activities. (Article 1 of this Regulation).
13. Physical foam systems.
Physical foam systems will be installed in those areas of fire and fire areas where their installation is required in accordance with the existing provisions governing fire protection in activities industrial, sectoral or specific (Article 1 of this regulation) and, in general, where there are areas of a fire sector in which flammable liquids are handled which, in the event of fires, can spread to other sectors.
14. Extinguishing systems by dust.
Dust-extinguishing systems will be installed in those fire sectors where their installation is required in accordance with the existing provisions governing fire protection in industrial activities. sectoral or specific (Article 1 of this Regulation).
15. Extinguishing systems by gaseous extinguishing agents.
15.1 Extinction systems will be installed by gaseous extinguishing agents in the fire sectors of industrial establishments when:
(a) Be required to be installed in accordance with the existing provisions governing fire protection in industry or sector specific industrial activities (Article 1 of this Regulation).
(b) Constituency where electronic equipment, calculation centres, data banks, control or measurement centres and analogues are located and protection with water systems may damage such equipment.
16. Emergency lighting systems.
16.1 Contain with an emergency lighting installation of the evacuation routes the fire sectors of the industrial buildings when:
a) Be located at ground floor.
(b) Be located in any plant on the ground, when the occupation, P, is equal to or greater than 10 persons and are of medium or high intrinsic risk.
c) In any case, when the occupation, P, is equal to or greater than 25 people.
16.2 Contain with an emergency lighting installation:
(a) The premises or spaces where tables, control centres or controls of the technical facilities of services are installed (referred to in Annex II.8 of this Regulation) or of the processes which are carried out in the establishment industrial.
(b) The premises or spaces where the central equipment or control tables of fire protection systems are installed.
16.3 The installation of the emergency lighting systems will meet the following conditions:
(a) It shall be fixed, provided with its own power source and shall automatically enter into operation upon failure of 70 per cent of its rated voltage of service.
b) Maintain service conditions for at least one hour from the time the failure occurs.
c) Provide an illuminance of at least one lx at the ground level in the evacuation paths.
d) The illuminance shall be at least five lx in the spaces defined in paragraph 16.2 of this Annex.
e) The uniformity of the illumination provided at the various points in each zone shall be such that the ratio between the maximum and the minimum illuminance is less than 40.
f) The levels of illumination established should be obtained by considering the reflection factor of walls and ceilings and contemplating a maintenance factor that includes the reduction of the luminous performance due to the ageing of the lamps and the dirt of the luminaries.
17. Signage.
The signs of the usual or emergency use-outs, as well as the means of fire protection for manual use, shall be made when they are not easily located from some point in the area protected, taking into account the provisions of the Regulation on the Signalling of Work Centres, approved by Royal Decree 485/1997 of 14 April 1997 on minimum requirements for the provision of safety and health signs at work.
ANNEX IV
Relationship of UNE Standards of Obligation to the Application of the Fire Safety Regulation in Industrial Establishments
23093-1: 1998. | Fire resistance tests. Part I. General requirements |
23093-2: 1998. | Fire resistance tests. Part II. Alternative and additional procedures |
UNE-EN 1363-1:2000 | Fire resistance tests. Part 1. General requirements | ||
UNE-EN 1363-2:2000 | Fire resistance tests. Part 2. Alternative and additional procedures | ||
UNE-EN 13501-1:2002 | Classification based on the fire performance of the construction products and building elements. Part 1: Classification from data obtained in reaction to fire testing | ||
UNE-EN 13501-2:2004 | Classification of products building and building elements according to their behaviour in the face of fire. Part 2: Classification from data obtained in fire resistance tests excluding ventilation facilities | ||
UNE-EN 3-7:2004 | Portable fire extintors. Part 7. Features, operating requirements, and test methods | ||
UNE-EN 12845:2004 | Fixed fire fighting systems. Automatic sprinkler systems. Design, installation, and maintenance. |
23500: 1990. | Systems fire water supply |
23585:2004 | Fire safety. Temperature control and smoke evacuation systems (SCTEH). Requirements and methods of calculation and design for projector a temperature control and smoke evacuation system in case of fire | ||
23727: 1990. | Reaction-to-fire test of building materials. Classification of materials used in construction |