Advanced Search

The Ordinance Of The Minister Of Internal Affairs And Administration Of 7 June 2010 On The Fire Protection Of Buildings, Other Buildings And Sites

Original Language Title: ROZPORZĄDZENIE MINISTRA SPRAW WEWNĘTRZNYCH I ADMINISTRACJI z dnia 7 czerwca 2010 r. w sprawie ochrony przeciwpożarowej budynków, innych obiektów budowlanych i terenów

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$40 per month.

ORDINANCE OF THE MINISTER OF THE INTERIOR AND ADMINISTRATION 1)

of 7 June 2010

on fire protection of buildings, other construction sites and areas

On the basis of art. 13 (1) 1 and 2 of the Act of 24 August 1991. on fire protection (Dz. U. 2009 r. No 178, pos. 1380 and 2010 No. 57, item. 353) shall be managed as follows:

Chapter 1

General provisions

§ 1. 1. The Regulation defines the ways and conditions for the fire protection of buildings, other construction sites and sites, hereinafter referred to as "facilities".

2. In cases of particularly justified local circumstances, indicated in the technical expertise of the expert on fire protection, may, in agreement with the competent local commander of the State Guard, be allowed to do so. Fire, use of replacement solutions in relation to those mentioned in § 19, § 23, § 24 and § 25 para. 1, 2, 5 and 6 and § 27 (1) 1 and 2, § 28 para. 1, § 29 para. 1 and § 38 (1) 1, which ensures a failure to deteriorate fire protection conditions of the facility.

§ 2. 1. Whenever there is a regulation in the regulation:

1. hazardous materials shall be understood by this means:

(a) flammable gases,

(b) flammable liquids having a flashpoint of less than 328,15 K (55 ° C),

(c) materials producing combustible gases in contact with water,

(d) self-igniting materials in the air,

(e) explosives and pyrotechnic articles,

(f) materials succumbing to a self-decomposing distribution or polymerisation,

(g) materials having a propensity for self-inflammation,

(h) materials other than those mentioned in (h) and -g, if the way in which they are stored, processed or otherwise used may result in a fire;

(2) the fire parcel-shall be understood by means of a system of trees of different widths subjected to special economic and ordinal treatments or areas of deforestation and purified into the mineral layer;

3) fire pump-shall be understood by this means the water pumping pumping system or the fire water supply network;

4) hazardous work in terms of fire-construction works related to the use of open fire, cutting with the manufacture of mechanical and mechanical engineering and welding, carried out inside or on the roofs of the objects, on the adjacent their areas and building sites, as well as repair and construction works carried out in areas at risk of explosion;

5) the landfill zone of the landfill-this shall be understood by the surface of the landfill separated from the buildings, other construction works and landfills, in the manner specified for the buildings in the regulations of the Regulation of the Minister of Infrastructure dated 12 April 2002 on the technical conditions to which the buildings should correspond and their location (Dz. U. Nr 75, poz. 690, with latt. 1. 2) ), hereinafter referred to as "technical-building provisions";

6. explosive danger zone-this shall be understood by the space in which the explosive mixture of flammable substances with air or other oxidising gases may occur, with a concentration between the lower and upper explosive limits;

7. the technical means of fire protection, which shall be understood by means of equipment, equipment, installations and construction solutions for the prevention and spread of fire;

(8) adjacent territory-this shall be understood by the belt of the site around the facility, with a width equal to the minimum permissible distance from the other objects due to fire safety requirements specified in the technical and construction regulations;

(9) fire-fighting devices-this shall be understood by means of equipment (fixed or semi-fixed, manually or manually operated) to prevent, detect, combat or reduce the effects of the fire and, in particular, the following: Semi-fixed fire extinguishing and safety equipment, inertising devices, devices of audible warning system and fire alarm system, including signalling and alarm equipment, fire alarm reception devices and fire alarm system, and fault signal reception devices, installations Evacuation lighting, internal hydrants and hydrant valves, external hydrants, fire pump pumps, fire-stop fire dams, smoke detectors, explosion protection devices and restraint systems its effects, smoke curtains and doors, fire gates and other fire closures, if equipped with control systems, fire-breakers and lifts for rescue crews;

10) protection against evacuation of escape routes-this shall be understood by means of protection against the maintenance of smoke evacuation roads in quantities which, due to the limitation of visibility, toxicity or temperature, would prevent safe evacuation;

11. explosion hazard-this shall be understood to mean the possibility of combustible gases, vapour or flammable solids, in different conditions, of mixtures with air which, under the influence of the trigger factor, ignite, That is, they are being burned rapidly with the pressure rise.

2. Whenever the regulation is used, the following terms are used:

(1) buildings-this shall be understood by the terms set out in paragraphs 4 to 6 and 8 and § 209 (1). 1,

2) production and warehouse buildings-it is to be understood by this term contained in § 209 (2). 1 point 2,

3) livestock buildings-this is understood by the term contained in § 209 (2). 1 point 3,

4) groups of heights-shall be understood by this term in § 8,

5) the danger category of people-it is necessary to understand the terms contained in § 209 (2). 2,

6) the floor-shall be understood by the terms of paragraph 3 (16-18),

7) fire zones-it is to be understood by this term contained in § 226 ust. 1 and 2

-technical and construction regulations;

8) the liquid fuel class III-shall be understood by this term contained in § 2 point 3 of the Ordinance of the Minister of Economy of 21 November 2005. on the technical conditions to be met by the bases and stations of liquid fuels, far-reaching pipelines for the transport of crude oil and petroleum products and their location (Dz. U. Nr 243, pos. 2063 and 2007 No. 240, pos. 1753).

§ 3. 1. Fire protection devices in the facility shall be carried out in accordance with the design agreed by the expert on fire protection matters, and the condition of admission to their use shall be carried out appropriate for the given device tests and tests, confirming the correctness of their operations.

2. Fire and portable fire extinguishers and transportable fire extinguishers, hereinafter referred to as "fire extinguishers", shall be subjected to technical inspections and maintenance operations, in accordance with the principles and in the manner specified in the Polish Standards of Equipment fire extinguishers and fire extinguishers, in the technical and movement documentation and in the service instructions, developed by their manufacturers.

3. Technical inspections and maintenance operations should be carried out within the periods set by the manufacturer, but not less frequently than once a year.

4. The hoses constituting the equipment of internal hydrants shall be subjected once every 5 years to a pressure test for maximum working pressure, in accordance with the Polish Norm on the maintenance of internal hydrants.

Chapter 2

Prohibited activities and obligations in the field of fire protection

§ 4. 1. The following operations, which may cause a fire, spread, impede the carrying out of a rescue operation or evacuation, shall be prohibited in the facilities and in adjacent areas:

1. use of open fire, smoking and other factors which may initiate the ignition of materials occurring:

(a) in the danger zone of explosion, with the exception of equipment intended for that purpose, meeting the requirements set out in the provisions of the Regulation of the Minister of Economy of 22 December 2005. on essential requirements for equipment and protective systems intended for use in potentially explosive atmospheres (Dz. U. No 263, pos. 2203),

(b) in the presence of hazardous materials in a fire;

(2) the use of non-technical installations, equipment and tools, or in a manner which is not in conformity with the intended purpose or conditions specified by the manufacturer or not subject to periodic inspections, of the scope and frequency of the provisions of law construction, if it can contribute to the emergence of fire, explosion or fire spreading;

3. garaging of motor vehicles in facilities and premises not intended for this purpose, if the fuel tank of the vehicle is not emptied and not detached on the fixed supply of the vehicle's battery;

4. warm-up by means of open fire of tar and other materials at a distance of less than 5 m from the object, the adjacent storage site or the component square with the combustible materials, and it is permissible to carry out those activities on the roofs of construction and non-flammable covering in the buildings being built and, in others, if appropriate, intended for this purpose heaters;

5) fire burning, the drying of hot ash and slag or the burning of the top layer of soil and grass, in a place which enables the inflammation of the combustible materials or of the adjacent objects;

6) storage outside the buildings at a distance of less than 4 m from the boundary of the plot of the adjacent combustment materials, including plant residues, branches and qualms;

7) the use of electric heating equipment set directly on a combusted basis, with the exception of equipment operated in accordance with the conditions specified by the manufacturer;

8. storage of combustble materials and the use of interior decoration and furnishing elements of combustble materials at a distance of less than 0,5 m from:

(a) equipment and installations the exterior surfaces of which may be heated to a temperature exceeding 373,15 K (100 ° C),

(b) cable lines with a voltage greater than 1 kV, grounding conductors and piorunochronological and active switchgear of electric current, electric conductors and strength plugs with a voltage above 400 V;

9. use on the shielding of light material points of combusted materials, with the exception of flammable and non-inflammatory materials, if placed at a distance of at least 0,05 m from the bulb;

10) installation of luminaires and fixtures of electrical installations, such as switches, switches, plugs, directly on the ground floor, if their design does not protect the substrate from inflammation;

11. storage of combusting materials on general communication roads for the evacuation or placing of objects on these roads in such a way as to reduce their width or height below the required values specified in the regulations technical-construction;

12) storage of combustble materials in the technical premises, in the non-performance attic and loft and on the roads of general communication in basements;

13) the storage of full, incomplete and emptied cylinders intended for flammable gases in non-utilised attic and strychs and in basements;

14) closing the evacuation doors in such a way as to prevent them from being immediately used in the event of fire or any other threat causing the evacuation;

15) lock doors and fire gates in such a way as to prevent their automatic closure in the event of a fire;

16) localization of interior design elements, installations and devices in a way that reduces the dimensions of the evacuation road below the values required by the technical regulations;

(17) the use of an escape route from a spectacle or any other similar destination, where the public or users are simultaneously exchanged as a waiting room for entry into this room;

18) preventing or restricting access to:

a) Fire extinguishers and fire extinguishers,

(b) anti-explosive offload devices,

(c) water sources for fire-fighting purposes,

(d) equipment for actuating fire-extinguishing systems and controls such installations and other installations affecting the fire safety of the facility,

(e) evacuation exits or windows for rescue teams,

(f) circuit breakers and switchboards for electric current and shrinks of major gas installations,

(g) outer cranes and shutters which, in accordance with technical and construction regulations, should be opened from the inside of the apartment or room;

19) the filling of liquid gas cylinders at the stations of fuels, liquid gas stations and other facilities not intended for this purpose;

20) the distribution and transhipment of crude oil and petroleum products in facilities and in areas not intended for this purpose.

2. Owners, managers or users of buildings and building blocks and wiat, with the exception of single-family dwellings:

1) keep firefighting devices and fire extinguishers in a state of complete technical and functional efficiency;

2) equip the facilities with fire-breakers in accordance with the technical-construction regulations;

3) place in visible places instructions for fire handling together with a list of emergency telephones;

4) they label the signs according to Polish Norms:

(a) escape routes and exits excluding residential buildings and spaces in which at least 2 escape exits are required in accordance with the technical and construction regulations, in such a way as to ensure that the information necessary for the evacuation is provided. evacuation,

(b) location of fire protection and fire extinguishers,

(c) the location of the location of the fire control devices,

(d) the location of the location of the nasade enabling the supply of the fire water supply, the shrinks of major gas installations and the fire-hazardous materials,

(e) premises and areas with fire-risk materials,

f. evacuation ladder, rescue sleeves, escape-mask containers, evacuation collection sites, location of keys to escape exits,

(g) cranes for fire brigade,

(h) fire-fighting water reservoirs, technological tanks constituting a complementary source of water for fire-fighting purposes, water sampling points, water-draw stations,

(i) fire doors,

(j) fire routes,

(k) sites classified as an explosion hazard zone;

5) place, when entering garages closed with a floor below the ground level, clear information about the clearance or failure to park in these garages of cars fuelled with liquid propane-butane referred to in Technical and construction regulations.

3. Around the building blocks and landfills at the premises and the temporary facilities of the combusted structure must be preserved a protective belt with a minimum width of 2 m and a surface of non-combustble or ground-treated materials.

4. The storage of combustble materials under the walls of an object related to its function, with the exception of hazardous materials, shall be permitted provided:

1) not exceeding the maximum surface area of the fire zone specified for this facility;

2) the preservation of access to the facility in the event of rescue operations;

3) the inviting of minimum distance from the adjacent objects required for fire safety;

4) keep a minimum distance of 5 m from the fire road.

5. The owners, managers and users of the service stations shall place information on the failure of the cylinder on the gas meter of the gas.

6. Owners, managers and users of production and warehouse facilities carry out regular ordinal actions in places where there are combustible dust in layers, according to the rules laid down in the Polish Norms.

§ 5. The owners or managers of the land shall maintain the fire routes in which they are able to use these roads by vehicles of fire protection units in accordance with the regulations on fire protection of water supply and fire roads.

§ 6. 1. Owners, managers or users of facilities or parts thereof which are separate fire zones intended for the operation of public utilities, collective, productive, warehousing and inventory functions, shall provide and implement a fire safety statement containing:

1) the conditions of fire protection, resulting from the purpose, use of the way of use, the conducted technological process, storage (storage) and the technical conditions of the facility, including the threat of explosion;

2) determination of equipment in the required fire protection devices and fire extinguishers and the means of subjecting them to technical inspections and maintenance operations;

3) ways of dealing with fire and other hazards;

4) the means of securing the hazardous work in terms of fire, if such work is envisaged;

5) the conditions and organization of the evacuation of people and the practical ways of checking them;

6) ways of familiariying the users of the facility, including the employed workers, with the fire regulations and the content of the statement in question;

7) tasks and duties in the field of fire protection for persons who are their permanent users;

8. object plans, including their location, and adjacent terrain, taking into account graphic data concerning in particular:

(a) the area, height and number of floors of the building,

(b) distance from adjacent objects,

(c) fire parameters of existing flammable substances,

(d) the present density of the fire in the fire zone or in the fire zones.

(e) the risk category of humans, the estimated number of persons on each storey and in the individual premises,

(f) the location of premises and external spaces classified as explosion hazard zones,

(g) the division of the facility into fire zones,

(h) evacuation conditions, with indications of evacuation directions and exits,

(i) the location of fire fighting equipment and fire extinguishers, main gas installations, fire-hazardous materials and the location of fire control equipment,

(j) indications of lifts for rescue teams,

(k) external hydrants and other sources of water for fire protection purposes,

(i) fire roads and other access roads, with an indication of entry into the fenced area;

9) an indication of the persons or entities drawing up the statement.

2. Conditions of fire protection referred to in paragraph. 1 point 1, and the plans referred to in paragraph 1. 1 point 8, in relation to the facilities and areas referred to in § 28 (1) 1, shall be transferred to the local district commandant (urban) of the State Fire Service in order to use them for planning, organisation and carrying out rescue operations.

3. The way of storing the documents referred to in the paragraph. 2, should provide for the possibility of their immediate use for the purpose of carrying out rescue operations.

4. The district chief (city) of the State Fire Service may release the owner, the administrator or the user of the object from the transfer of the documents referred to in the paragraph. 2 if this does not result in failure to comply with the requirements referred to in paragraph 2. 3, and request to supplement them in justified cases.

5. The documents referred to in paragraph. 2, may be transmitted in electronic form.

6. The instruction referred to in paragraph. 1, may constitute in the production, storage and inventory facilities a part of the technological and movement instructions, and in facilities located in closed areas, for the defence of the State and facilities located in the premises of establishments criminal and arrest investigators part of the security plan or rescue operations.

7. The fire safety manual shall be periodically updated, at least once every 2 years, and after such changes in the use of the facility or the technological process, which affect the change of fire protection conditions.

8. The fire safety manual shall not be required for the objects or their parts referred to in paragraph. 1 if there is no danger zone in them, and in addition:

1) the gross cubature of the building or its part constituting a separate fire zone does not exceed 1 000 m 3 , subject to point 2;

2) gross cubature of the livestock building does not exceed 1 500 m 3 ;

3) the area of the fire zone of an object other than the building does not exceed 1 000 m 2 .

9. The fire safety manual shall be located in the places available to the rescue team.

Chapter 3

Fire hazardous materials

§ 7. 1. When using or storing hazardous materials, the fire shall be:

1) perform all activities related to the manufacture, processing, processing, transport or storage of hazardous materials in accordance with the conditions of fire protection specified in the fire safety instructions referred to in § 6, or in accordance with the conditions laid down by the manufacturer;

2. maintain the quantity of hazardous material at the workplace by no more than a daily requirement or a daily production, unless otherwise provided for in the special provisions;

3. store the supply of hazardous materials in excess of the size specified in point 2 in a separate warehouse adapted for such purpose;

4. store hazardous materials in such a way as to prevent the formation of a fire or explosion following the storage process or the interaction between them;

5. store liquids with a flashpoint of less than 328,15 K (55 ° C) only in containers, equipment and installations designed for this purpose, made of materials at least inflammable, discharging electrical charges static, sealed and protected against breakdows.

2. Non-hazardous materials shall not be stored in the pituionic rooms, the attic and the attic, within stairways and corridors, and in other areas generally available, as well as on terraces, balconies and loggias.

§ 8. 1. When storing liquids with a flash point of less than 328,15 K (55 ° C) in buildings, fire zones included in the hazard category of humans:

1. it is permissible to store in one fire zone qualified for the hazard category of people other than ZL IV and of a non-commercial purpose up to 10 dm 3 Liquids with flash point below 294,15 K (21 ° C) and up to 50 dm 3 of liquids with a flash point of 294,15 ÷328,15 K (21 ÷55 ° C), and in apartments up to 5 and up to 20 dm 3 liquids;

2. it is permissible to store liquids with a flash point of up to 328,15 K (55 ° C) in the commercial and service premises, in such a quantity that the density of the fire load created by these liquids does not exceed 500 MJ/m 2 ;

3. it is permissible to store in the commercial premises constituting a separate fire zone of flammable liquids in quantities greater than those referred to in point 2, provided that those premises satisfy the technical and construction requirements concerning production and warehouse fire zones;

4. in commercial and service premises, flammable liquids should be stored in sealed vessels, protected from breakage, and their sale should be carried out without spilting.

2. When storing liquids with a flash point of less than 373,15 K (100 ° C) in garages:

1) with an area of more than 100 m 2 it is permissible to store these liquids only if they are necessary for the operation of the vehicle and are stored in unit packages used in the retail trade;

2. it is not permissible to transfer fuel and to fill it with fuel tanks in vehicles;

3) free standing materials made of non-flammable materials with an area of up to 100 m 2 is acceptable storage up to 200 dm 3 a liquid with a flash point of less than 328,15 K (55 ° C);

4) with an area of up to 100 m 2 other than those mentioned in point 3. is allowed to be stored up to 20 dm 3 Liquids with flash point below 294,15 K (21 ° C) or up to 60 dm 3 Liquids with a flash point of 294,15 ÷373,15 K (21 ÷100 ° C);

5) liquids should be stored in metal vessels or other permitted for this purpose, with sealed closures.

§ 9. 1. The retail sale of pyrotechnic products in buildings shall only be carried out in positions which have been distinguished for this purpose without the possibility of self-service sales.

2. fireworks shall be stored in separate storerooms or premises, intended solely for that purpose, separated by internal walls and fire-resistance class strops of at least El 60 and REI 60 and closed doors with fire resistance class at least El 30.

3. Detailed requirements for the premises in which the products referred to in paragraph are traded. 2, specify the provisions issued on the basis of art. 24 ust. 2 and Art. 33 (1) 2 of the Act of 22 June 2001. on the performance of economic activities in the manufacture and marketing of explosives, weapons, ammunition and articles and technology for military or police purposes (Dz. U. No 67, pos. 679, of late. 1. 3) ) and the provisions of the Ordinance of the Minister of Economy, Labour and Social Policy of 9 July 2003. on safety and health at work in the production, intra-plant transport and on the circulation of explosives, including pyrotechnic articles (Dz. U. No 163, pos. 1577).

§ 10. 1. Requirements for the use of liquid gas cylinders for the power supply of the equipment and gas installations in the buildings shall be determined by the technical regulations.

2. In the fire zone, involving a temporary construction site or area, referred to as the fire zone of the landfill, the use and storage of no more than 2 cylinders with liquefied petroleum gas, with a gas content of up to 11 kg each, shall be permitted. In the case of a gas cylinder with a gas content of up to 5 kg, its total mass collected in cylinders shall not exceed 22 kg.

§ 11. 1. Storage of Class III liquid fuels may be stored for own user's own needs, in a two-cylinder terrestrial tank with a capacity of up to 5 m 3 .

2. Tank for storage of Class III liquid fuels for the user's own use referred to in paragraph. 1, should be placed at the following distances:

1) 10 m-from residential buildings and public buildings;

2) 5 m-from other construction sites and from the border of a neighbouring parcel.

3. The distances referred to in paragraph. 2, may be reduced by half, subject to the application between the building or the object and the tank of the fire separation wall with the fire resistance class at least REI 120 obscuring the container from the side of the building or the facility.

4. The execution of the external wall of the building or object from the side of the tank as the wall of the fire separation referred to in the paragraph shall be allowed. 3.

§ 12. 1. Storage spaces intended for the storage of flammable gases or carbide must meet the requirements laid down for the premises at risk of explosion.

2. The storage of storage cylinders with flammable gases shall be protected from heat to a temperature exceeding 308,15 K (35 ° C).

3. Situations outside the production and storage buildings are allowed, in a space encapsulated from three sides full of walls with a fire resistance class of at least REI 120, up to two cylinders of flammable gas, containing a maximum of 16 butli each, combined with a common manifold with expansion stations.

4. Butle referred to in paragraph. 3, containing liquid gas, shall be separated from the nearest wells or other cavities and holes to the premises with a floor situated below the adjacent area at least 3 m.

§ 13. 1. Butls designed for storing and transporting flammable gases means according to the Polish Norms.

2. Palm bottles should be stored in rooms dedicated exclusively to this purpose.

3. In one room can be stored:

1. cylinders with flammable gases and non-flammable gases, not excluding oxidising gases;

2) cylinders emptied with cylinders filled with flammable gas, provided that they are set separately.

4. Palm bottles, full or emptied, with feet, must be set in a vertical position by slicing them according to the contents.

5. The non-foot-gas cylinders shall be stored in wooden frames in a horizontal position; stacking cylinders of up to 1,5 m shall be permitted.

6. The bottles should be protected from falling, using barriers, septum or other protective measures, and cylinder valves to secure pins.

7. The detailed requirements for the storage and storage of cylinders with liquid gas determines the Ordinance of the Minister of Economy of 6 September 1999. on safety and health at work in the storage, filling and distribution of liquid gases (Dz. U. Nr 75, poz. 846, of 2000 Nr 29, pos. 366 and 2004 Nr 43, pos. 395).

§ 14. 1. In the sale points of gas utensils, liquid gas can be stored in cylinders with a total gas mass of up to 70 kg.

2. In commercial retail chains, outside of service stations, cylinders can be stored in containers with a cagerage structure. These containers, with a total gas mass in cylinders of up to 440 kg, should be set at a distance of at least:

1) 8 m-from public buildings, collective and residential buildings, and from other buildings, if their construction is made of combustble elements;

2) 3 m-from other buildings, from wells and other landings and from the border of the plot.

3. Butle can be stored in containers at the wall of the building with fire resistance class at least REI 120, at a distance of at least 2 m in the level and at least 9 m in the vertical from the contained window and door orifices.

4. Warehouses and spilles of liquefied gas and bases and stations of liquid fuels must be equipped with equipment and installations meeting the requirements set out in the provisions of the Regulation of the Minister of Economy of 21 November 2005. on the technical conditions to be met by the bases and stations of liquid fuels, far-reaching pipelines for the transport of crude oil and petroleum products and their location.

Chapter 4

Evacuation

§ 15. 1. Appropriate evacuation conditions shall be provided at any place in the facility, intended for human being, to permit the rapid and safe leaving of the zone at risk or the fire, adjusted to the number and status of the persons concerned. in the facility and its functions, constructions and dimensions, as well as the application of technical fire protection measures, consisting of:

1. providing sufficient numbers, heights and width of evacuation exits;

2) the maintenance of the permissible length, height and width of transitions and to be evacuated;

3. to provide safe fire in the housing and evacuation of evacuation roads and spaces;

4) protection against the smoke specified in the technical regulations of the evacuation roads, including: on the use of smoke-preventing devices or equipment and other technical-building solutions ensuring smoke removal;

5) providing emergency lighting (evacuation and backup) in the premises and on the evacuation roads mentioned in the technical regulations;

6) ensuring the possibility of broadcasting warning signals and voice messages by the audible warning system in the buildings for which it is required.

2. Appropriate evacuation conditions shall be defined in the technical regulations.

§ 16. 1. A user of an existing building shall be considered to be a life-threatening person, when the technical conditions in it do not provide for the possibility of evacuation of people.

2. The basis for determining that the building contains the technical conditions referred to in the paragraph. 1, subject to § 45, may be:

1) the breadth of the passage, the outlet or the escape exit, or the escape or the spoon of the staircase to be evacuated, less by more than one third from the specified technical and construction regulations;

2) the length of the passage or evacuation order greater by more than 100% from the specified in the technical and construction regulations;

3. occurrence in the fire zone room classified in the hazard category of the people ZL I, ZL II or ZL V or by an evacuation route:

(a) ceiling or suspended ceiling linings made of material which is easily inflamed or capsized under the influence of fire, or floor coverings of easily ignited material,

(b) wall cladding of material which is easily inflamed by an evacuation, unless two directions are provided for evacuation;

4) non-evacuation of the stairway of the building of a high other than residential or high-altitude building, in the manner specified in the technical regulations;

5) failure to prevent the evacuation of escape routes specified in the technical regulations, in the manner specified therein;

6. lack of required emergency lighting in relation to the fire zone qualified for the hazard category of the people of ZL I, ZL II or ZL V or on the escape route leading from this zone outside the building.

3. The owner or manager of the building referred to in paragraph. 1, it is obliged to apply solutions ensuring the fulfilment of fire safety requirements in the manner specified in the technical-building regulations.

§ 17. 1. The owner or manager of the facility intended for more than 50 persons who are his permanent users, who are not classified in the category of threat to the ZL IV, shall carry out a practical check of the organisation at least once every 2 years, and evacuation conditions from the entire facility.

2. In the case of objects in which a group of more than 50 users changes simultaneously, in particular: schools, kindergartens, internships, student houses, practical organisation checks and evacuation conditions should be made-co at least once a year, but within a period of not more than 3 months from the date when the use of the facility by new users is started.

3. In the case of an object containing a fire zone qualified for the threat category of the people of ZL II and in the buildings of the inmates located in the areas of the penal facilities and the arrests of investigators, the scope and area of the building covered the practical examination of the organisation and evacuation conditions must be agreed with the local district commander of the State Fire Service (municipal).

4. The owner or the manager of the facility shall notify the local district commander of the (municipal) State Fire Service of the date of carrying out the activities referred to in paragraph. 1, not later than one week before they are carried out.

Chapter 5

Fire-Suppression Water Installation

§ 18. 1. In buildings, the following types of water collection points are used for fire fighting purposes:

1. indoor hydrants with semi-rigid hose with a nominal hose diameter of 25 mm and 33 mm, hereinafter referred to as "hydrant 25" and "hydrant 33" respectively;

2. an internal hydrant with a flat hose made of a nominal hose diameter of 52 mm, hereinafter referred to as "hydrant 52";

3) a hydrant valve, hereinafter referred to as the "valve 52", without the equipment in the fire hose.

2. Internal Hydrants must meet the requirements of the Polish Standards for these devices.

3. The valves 52 must meet the requirements of the Polish Standards for these devices.

4. The power supply of indoor hydrants must be provided for at least 1 hour.

§ 19. 1. Hydrants 25 must be used in fire zones qualified for the hazard category of the ZL people:

1) on each floor of the high and high-altitude building, except for the floor covering only the fire zone qualified for the hazard category of the people of ZL IV;

2) on any floor of a building other than a temporary, low-and medium-size building:

(a) in a fire zone with an area exceeding 200 m 2 , qualified for the hazard category of people ZL I, ZL II or ZL V,

(b) in the fire zone qualified for the hazard category of the people of ZL III:

-of a surface exceeding 200 m 2 in a semi-averages building, where this is a fire zone with only the first floor, and only ZL IV fire zones are above it, only if the area of that fire area exceeds 1 000 m 2 ,

-with an area exceeding 1 000 m 2 in a low building.

2. Hydrants 33 must be used in the garage:

1. single-storey closed by more than 10 parking spaces;

2) multistorey.

3. Hydrants 52 must be used:

1) in the production and warehouse fire zone with a density of more than 500 MJ/m 2 and of a surface exceeding 200 m 2 ;

2) in the production and warehouse fire zone with a density of fire load not exceeding 500 MJ/m 2 In which there is a room with a surface exceeding 100 m 2 and the density of the fire load exceeding 1 000 MJ/m 2 ;

3) at the entrance to storage or technical premises with a surface exceeding 200 m 2 And fire density exceeding 500 MJ/m 2 , situated in a fire zone classified in the hazard category of people ZL I, ZL II, ZL III or ZL V, located in a low or semi-averages building.

4. In the fire zones referred to in paragraph. 3 (1), and at the entrance to the storage or technical premises referred to in paragraph 1. 3, paragraph 3, shall be permitted to use hydrants 33 if the density of the fire load in these areas and those of the storage or technical units does not exceed 1 000 MJ/m 2 .

5. The requirements referred to in paragraph. 2, they do not concern the slow-standing garages in the closed areas of the subordinate Ministries of National Defence.

§ 20. 1. The internal Hydrants and the valves 52 shall be placed on the roads of general communication, in particular:

1) at the entrances to the building and staircases on each floor of the building, with the location of the valve 52 in the fire-fighting vestibule in the high and high buildings, and it allows the staircases to be located;

2) in the crossings and in the corridors, including in the hall and in the corridors of individual floors of high and high-altitude buildings;

3) at the entrants to the attic;

4) at the exits to the open space or at the evacuation exits from the production and storage premises, in particular at risk of explosion.

2. The internal Hydrants and the valves 52 must be on each floor, where the high and high buildings are to be used for two 52 valves per vertical on the ground floor and on a floor above 25 m and after one valve 52 on each vertical on the remaining floors.

3. The range of indoor hydrants shall cover the entire surface of the protected building, fire zone or room, taking into account:

1) the length of the hose section of the internal hydrant determined in the standards referred to in § 18 paragraph. 2;

2. effective range of extinguishing currents of extinguishing currents:

(a) 3 m in fire zones falling within the risk category of the ZL, situated in buildings with more than one filing floor-adopted for tapered currents,

(b) 10 m-in other buildings.

4. In the case of rooms and fire zones of production and storage, to secure the places from which the distance to the nearest evacuation exit or other output to the open space exceeds 30 m, in order to meet the requirements of which Paragraph 1. 3, the hydrant 52 is permitted to be equipped with an additional hose.

§ 21. 1. The valves 52 and the shut-off valves for internal hydrants shall be placed at a height of 1.35 ± 0,1 m from the floor level.

2. The valves 52 and the shut-off valves in the hydrants 52 shall be fitted to the bottom, situated together with the valve knob relative to the wall or housing in a way that enables easy connection of the piston hose and the opening and closing of the valve valve.

3. The valves 52 localised in places where they can be exposed to damage or devastation shall be placed in metal protective cabinets complying with the requirements of the Polish Standards, with a lock conforming to the Polish Norms opening the topork head fire.

4. Before the internal hydrant or valve 52, sufficient space for extinguishing the fire extinguishing line shall be provided.

§ 22. 1. The minimum efficiency of the collection of water measured at the outlet of the generator shall be:

1) for hydrants 25-1.0 dm 3 /s;

2) for hydrants 33-1.5 dm 3 /s;

3) for hydrants 52-2,5 dm 3 /s;

4) for valve 52-2,5 dm 3 Second.

2. Pressure on the internal hydrant shut-off valve shall provide the performance as defined in paragraph 1. 1 for a given type of internal hydrant, taking into account the used diameter of the nozzle of the generator, and be not less than 0,2 MPa.

3. Pressure on the valve 52, which is the most disadvantaged due to the height and hydraulic resistance, for the efficiency specified in the mouth. 1 point 4, shall not be less than 0,2 MPa.

4. The maximum working pressure in the fire water system on the shut-off valve shall not exceed 1,2 MPa, with the valve 52 and the hydrant shut-off valves 33 and the hydrants 52 shall not exceed 0,7 MPa.

§ 23. The installation of fire-fighting water supply should provide the possibility of simultaneous collection of water on one floor of the building or in one fire zone with:

1) one internal hydrant-in a low or medium building, if the area of the fire area does not exceed 500 m 2 ;

2) two adjacent internal hydrants or two adjacent valves 52-in buildings not listed in points 1 and 3 and in a high building with one staircase;

3) four neighboring hydrants or 52 valves:

a) in the high and high-altitude building on the floors and floors of the post-bed floors above 25 m,

(b) in the production and warehouse fire area with a load density of more than 500 MJ/m 2 and of an area exceeding 3 000 m 2 .

§ 24. 1. The installation of the fire-fighting water supply must be supplied from the external fire water supply network or from tanks with adequate water supply for fire purposes, either directly or by means of a fire pump, in the way ensuring that the requirements laid down in paragraphs 22 and 23 are met.

2. The water supply of the fire water supply in the high and high buildings should be provided the supply of water collected with a total capacity of not less than 100 m 3 in one or more tanks intended solely for this purpose.

3. Acceptable:

1) reduction of the capacity of the tanks referred to in paragraph. 2, up to 50 m 3 , in the case of high and high-altitude buildings up to 100 m high:

(a) containing more than 12 metres in height only of fire zones falling within the hazard category of the people of ZL IV, irrespective of their area, or

(b) not containing fire zones with a surface area exceeding 750 m 2 ;

2) use of one common tank with a capacity of at least 100 m 3 for a group of high and height buildings erected side by side, if the container is not more than 100 m away from any of the buildings;

3. the use of tanks with a capacity reduced than those mentioned in:

(a) paragraphs 2 and paragraph 3 points 2-up to 50 m 3 in the case of providing the supply of these tanks with water from the external fire-fighting water network with a capacity of not less than 10 dm 3 Second,

(b) paragraphs 2 and paragraph 3 points 2-to 25 m 3 in the case of providing the supply of these tanks with water from the external fire-fighting water network with a capacity of not less than 15 dm 3 Second,

(c) paragraphs 3 points 1-up to 6 m 3 in the case of providing the supply of these tanks with water from the external fire-fighting water network with a capacity of not less than 10 dm 3 Second.

4. For high buildings qualified for the hazard category of the people of ZL IV it is permissible to power the installation of the fire water supply directly from the external fire-fighting water network with a capacity of not less than 10 dm 3 /s, without the need to provide the tanks referred to in paragraph. 2 and 3.

5. The application of the admissibility referred to in paragraph 5. 3 points 3 and 3 4, is the exit in the facades of the building, from the side of the fire road, additional rainfall of the diameter of 75 mm, enabling the supply of the fire water supply system with the fire extinguishing cars.

§ 25. 1. The power supply of the fire pipe system shall be carried out:

1) as pions in staircases or stairways;

2. as distribution cables in single-storey buildings and, where appropriate, on the floors of multi-storey buildings.

2. In tall and high buildings with two or more staircases, the hydrated foils shall be connected to each other on the highest floor of the wire with a nominal diameter (DN) at least DN 80.

3. The installation flow from which water to extinguish the fire, made of combusted materials, shall be encapsulated on all sides of the fire resistance class of at least El 60. This condition does not apply to pions kept in staircases separated by walls and closed doors with a fire resistance class of at least El 30.

4. The nominal diameter of the supply lines, in millimetres, on which the internal hydrants and valves are installed 52 shall be at least:

1) DN 25-for hydrants 25;

2. DN 50-for hydrants 33 and 52;

3) DN 80-for valves 52 on hydrated pawns in high and high-altitude buildings.

5. In unheated buildings or in their parts, the wiring of the fire pipe system shall be protected against the possibility of freezing. In this case, the dry installation may be used, provided that the solutions are used to enable it to be irrigated in a manual and/or automatic manner.

6. The supply of water supply systems shall be carried out as a circumferential water supply to ensure that the water supply is at least two sides, where:

1) the number of pions in the building, powered from one cable, is greater than 3;

2. more than 5 internal hydrants have been installed on the redistribution lines.

7. It shall be possible to disconnect the valves or valves of these parts of the power supply lines of the fire water supply which are between the supply referred to in paragraph (s). 6.

8. The connection to the power lines of the fire water installation of sanitary ware shall be allowed, provided that in the event of their failure, this will not result in an uncontrolled outflow of water from the installation.

9. The possibility of collecting water for fire purposes with the required parameters of pressure and performance in the building must be ensured regardless of the state of work of other systems or devices.

§ 26. The detailed requirements for the fire pump shall be determined by the provisions of the Regulation of the Minister of Internal Affairs and Administration of 24 July 2009. on fire protection of water and fire roads (Dz. U. Nr 124, pos. 1030).

Chapter 6

Use of fixed fire extinguishing systems, fire alarm systems, audible warning systems and fire extinguishers

§ 27. 1. The use of fixed fixed fire-extinguishing devices with an object, containing a supply of extinguishing agent and activated automatically in the early stages of fire development, shall be required in:

1) the archives designated by the Supreme Director of State Archives;

2) museums and construction monuments, designated by the General Conservator of the Monuments in agreement with the Commander of the Main State Fire Service;

3) electronic data processing centres of national importance.

2. The use of fixed self-active water extinguishing devices is required in:

1. commercial or exhibition buildings:

a) single-storey, in the fire zone qualified for the risk category of the people of ZL I with an area of more than 8,000 m 2 ,

(b) multistorey, in the fire zone qualified for the risk category of the people of ZL I with an area greater than 5 000 m 2 ;

2) in buildings with a number of places serving gastronomic purposes above 600;

3) high-altitude public buildings;

4) buildings of collective high-altitude residence.

3. In fire zones and spaces equipped with fixed gas fire-extinguishing equipment or with another extinguishing agent capable of affecting human health, safety conditions shall be ensured for persons staying in those premises, in accordance with Polish Standards for these devices.

§ 28. 1. Use of fire alarm system, including signalling and alarm equipment, for the automatic detection and transmission of fire information, as well as reception facilities for fire alarms and signal reception devices Damage is required in:

1. commercial or exhibition buildings:

a) single-storey with area of fire zone above 5 000 m 2 ,

(b) multi-storey areas with a fire area above 2 500 m 2 ;

2) theatres with a number of seats over 300;

3) cinemas having a number of seats over 600;

4) buildings with a number of places serving gastronomic purposes above 300;

5. spectacle and sporting halls having a number of seats above 1 500;

6) hospitals, except psychiatric wards, and in sanatorias-with a number of beds over 200 in the building;

7) psychiatric hospitals with a number of beds over 100 in the building;

8) the homes of social assistance and rehabilitation centres for persons with disabilities with a number of beds over 100 in the building;

9) workplaces employing more than 100 people with disabilities in the building;

10) public buildings of high and high altitude;

11. buildings of collective residence in which the expected period of residence of the same persons exceeds three days, having a number of accommodation units above 200;

(12) buildings of collective residence not mentioned in point 11, with a number of accommodation units exceeding 50;

13) archives designated by the Supreme Director of State Archives;

14) museums and construction monuments, designated by the General Conservator of the Monuments in agreement with the Commander of the Main State Fire Service;

15) electronic data-processing centres with national, provincial and government data processing offices;

16. telephone centres with a capacity of more than 10 000 telephone numbers and telephone exchanges with a capacity of 5 000-10 000 numbers, of local or regional importance;

17) underground garages, in which the fire zone exceeds 1 500 m 2 or involving more than one underground store;

18) subway stations and underground railways;

19) railway stations and ports, which are intended to be more than 500 persons at the same time;

20) banks in which the fire zone containing the operating room has a surface exceeding 500 m 2 ;

21) libraries, whose collections in whole or in part constitute a national library resource.

2. Requirements referred to in paragraph. Points 4 and 11 do not apply to buildings which are located in closed areas for defence of the State, and of the buildings of the inmates, which are located in the area of detention facilities and the detention of investigators.

§ 29. 1. The use of a audible warning system enabling the broadcast of warning signals and voice messages for the safety of persons present in the facility, transmitted automatically upon receipt of a signal from the system the fire alarm, as well as by the operator, is required in:

1. commercial or exhibition buildings:

a) single-storey, containing a fire zone qualified for the hazard category of people ZL I with an area of more than 8,000 m 2 ,

(b) multistorey, containing a fire zone classified in the risk category of the people of ZL I with a surface area greater than 5 000 m 2 ;

2. spectacle and sporting halls having a number of seats above 1 500;

3) cinemas and theatres with a number of seats over 600;

4) hospitals and sanatoriums with a number of beds over 200 in the building, excluding the premises of intensive medical care, operating rooms and halls with the sick;

5) high and high-altitude public buildings;

6) buildings of collective high and high-altitude residency or with a number of accommodation units above 200;

7) subway stations and underground railways;

8) stations and ports, which are intended to be at the same time above 500 people.

2. In facilities where the audible warning system is used, no other fire alarm devices shall be used for alerting the occupants of that object, except for the services of the supervision or protection.

3. The requirement referred to in paragraph 1. Article 1 (6) does not apply to buildings located in closed areas for the defence of the State and of the buildings of the inmates, which are located in the area of detention facilities and of the detention facilities.

§ 30. 1. Objects equipped with fixed fire extinguishing devices may not be equipped with fire alarm system.

2. Paragraph Recipe 1 does not apply to objects in which the fire alarm system is necessary to run the devices intended for operation during fire.

§ 31. The owner, manager or user of the object referred to in Article 5 of the Act of 24 August 1991. on fire protection, agree with the local district commandant (city) of the State Fire Service to connect signalling and fire alarm system equipment with the command of the State Fire Service, or The object specified by this command.

§ 32. 1. The objects must be equipped with fire extinguishers, meeting the requirements of the Polish Standards for fire extinguishers.

2. The type of extinguishers shall be adapted to extinguish these groups of fires, which may occur in the facility:

1) A-solid materials, usually of organic origin, of which the normal combustion takes place with the formation of carbon-producing fissors;

2) B-liquids and solid materials melting;

3) C-gases;

4) D-metals;

5) F-fats and oils in kitchen appliances.

3. One unit weight of extinguishing agent 2 kg (or 3 dm) 3 ) the fire extinguishers contained in the fire extinguishers shall be, except as provided for in specific

1) for every 100 m 2 the area of the fire area in the building, unprotected by a fixed fire-extinguishing device:

(a) qualified for the hazard category of people ZL I, ZL II, ZL III or ZL V,

(b) production and storage of more than 500 MJ/m of fire load density 2 ,

(c) containing a room at risk of explosion;

2) for every 300 m 2 the area of the fire zone not mentioned in point 1, except as regards the risk category of the ZL IV people.

4. Equipment in the fire extinguishers of warehouses in which the cylinders of liquefied gas are stored, and the liquid fuel stations shall be determined by the Regulation of the Minister of Economy of 21 November 2005. on the technical conditions to be met by the bases and stations of liquid fuels, far-reaching pipelines for the transport of crude oil and petroleum products and their location.

5. The place of the ohms, regardless of the required fire extinguishers, must be equipped with a water container with a volume of at least 200 dm 3 , prepared for use for extinguishing purposes by means of buckets or other equivalent ways.

§ 33. 1. Gaśnice in the premises must be arranged:

1. in places which are easily accessible and visible, and in particular:

(a) at the entrants to the buildings,

(b) in staircases,

(c) in corridors,

(d) at exits from outside rooms;

2) in places not arable to mechanical damage and the operation of heat sources (furnaces, radiators);

3) in multi-storey facilities-in the same places on each floor, if existing conditions permit.

2. The following conditions shall be met when the fire extinguishers are deployed:

1. the distance from any place in the facility where the person may be present to the nearest fire extinguisher shall not be greater than 30 m;

2. access to fire extinguishers shall be provided at least 1 m wide access.

Chapter 7

Installations and technical equipment

§ 34. 1. In the facilities or parts thereof where the combustion of solid, liquid or gaseous fuels is carried out, the pollutants from the smoke and exhaust pipes shall be removed during the period of their use:

1) from the pallets of mass caterers and catering services-at least once a month, if the local regulations do not stipulate otherwise;

2. from solid fuel burners not listed in point 1-at least once every 3 months;

3. from smokies fired liquid and gaseous fuel not listed in point 1-at least once every 6 months.

2. In the objects or their parts referred to in the paragraph. 1, the pollutants from the ventilation ducts shall be removed at least once a year, if the higher frequency does not result from the conditions of use.

3. The activities referred to in paragraph 1. 1 and 2, they perform a person with a cominiary qualification.

4. The provision of the paragraph. 3 shall not be used for the removal of impurities from the smoke, exhaust and ventilation ducts of single-family dwellings and construction and holiday building facilities.

§ 35. 1. The temperature of the external surface of the equipment and the installation of the power supply, excluding electrical installations, and the temperature inserted into the air space should not exceed depending on the type occurring in the The following material objects:

1) for gases and vapour vapour 2/3 of the maximum surface temperature expressed in degrees Celsius (° C), defined by the Polish Standard concerning electrical equipment in potentially explosive atmospheres for individual temperature classes of gases and liquid vapour;

2. in the case of dusts and fibres:

(a) at least 70 degrees Celsius (° C) below the temperature of the inclination of 5 mm of the dust layer for horizontal heating surfaces or inclined to 60 ° in relation to the level,

(b) 2/3 of the self-ignition temperature expressed in degrees Celsius (° C), mixtures of dusts or fibres with air for surfaces with a gradient greater than 60 ° in relation to the level and for those surfaces on which the accumulation of dust is prevented and fibres,

(c) 2/3 of the temperature of the self-ignition, expressed in degrees Celsius (° C), mixtures of dusts or fibres with air for non-smoked dusts or fibres, irrespective of the degree of inclination of the surface of the heaters;

3) in cases of other solids easily inflamed 2/3 of the temperature of the self-ignition, expressed in degrees Celsius (° C).

2. The permissible operating temperatures of the electrical equipment and the rules for the classification of gases and vapour vapour to the temperature classes shall be determined by the Polish Standards for electrical equipment in potentially explosive atmospheres.

3. When establishing the permissible temperatures, it shall be taken as the basis of the combustible material contained in the room, which has the lowest self-ignition temperature and for the oxygen to be the lowest temperature of the weaving.

4. In heating and ventilation systems, air recirculation shall not be permitted if it could cause an increase in explosion hazard.

5. The use of central air heating systems in all facilities and facilities shall be allowed, provided that the use of self-active equipment (thermoregulators) to prevent exceeding permissible temperatures in the case of an air flow failure and a blockage preventing the integration of heating elements prior to the start of the air supply.

6. Central water and steam heating systems shall not be used in facilities where there are materials producing in reaction with water or vapour water vapour, if such reactions are not provided for in the technological process.

7. The surfaces of the hoses and heating devices and their insulation within the spaces in which the combustible dust and fibres can be secreted shall be smooth, easy to clean and fire non-flammable.

8. Technical and technological installations and devices in which, during operation, the loads of static electricity with a potential sufficient potential for inflammations of flammable materials may be produced, and shall be equipped with appropriate measures. protection, in accordance with the Polish Standards for Protection against Static Electricity.

Chapter 8

Fire-hazardous work and explosion hazard assessment

§ 36. 1. Before the start of hazardous fire work, which may cause a direct danger of fire or explosion, owner, administrator or operator of the facility:

1) assess the fire risk in the place where the work will be carried out;

2. establish the nature of the projects to prevent the emergence and spread of fire or explosion;

3) indicate the persons responsible for the appropriate preparation of the workplace, for the course and securing of the place after the work is completed;

4) ensure that the work is carried out only by the persons authorised to do so, with the appropriate qualifications;

5. acquaints persons carrying out the work with fire hazards occurring in the area of work, and with undertakings designed to prevent a fire or explosion.

2. In carrying out the work referred to in paragraph. 1, it shall be:

1) protect against inflammation of the combustible materials occurring at the place of execution of works and in adjacent areas, including elements of the structure of the building and the technical installations in it;

2) carry out hazardous work in terms of fire in the premises or with devices at risk of explosion or in premises where other works related to the use of flammable liquids or flammable gases have been previously performed, only then, where the concentration of vapour or gas vapour in the mixture with the air at the place of work does not exceed 10% of their lower limit of explosion;

3) have at the place of execution of the work equipment enabling the elimination of any fire source;

4) upon completion of the works, submit to the inspection the place where the work was carried out, and the adjacent divisions;

5. use only technically and protected equipment to carry out the work before the fire is capable of being called.

§ 37. 1. In facilities and adjacent areas where technological processes are carried out with materials capable of creating explosive mixtures or in which such materials are stored, risk assessment shall be carried out.

2. The explosion hazard assessment shall include an indication of the premises at risk of explosion, the designation in the premises and external spaces of the relevant explosion hazard zones, together with the development of the graphical classification documentation and an indication of the the factors that may initiate the ignition in them.

3. Graphical classification documentation contains situational plans depicting the type and extent of the danger zones of the explosion and the location and identification of emission sources, in accordance with the principles set out in the Polish Norms.

4. The explosion hazard assessment shall be carried out by: the investor, the designer or the user who decides on the technological process.

5. An explosion hazard assessment may be part of an explosion risk assessment, referred to in the provisions of the Regulation of the Minister of Economy, Labour and Social Policy of 29 May 2003. on the minimum health and safety requirements for the work of workers employed at work stations on which an explosive atmosphere may occur (Dz. U. Nr. 107, pos. 1004 and 2006 Nr 121, pos. 836).

6. Classification of danger zones of an explosion shall be defined by the Polish Standard concerning the prevention of explosion and protection against the explosion.

7. A room capable of producing an explosive mixture formed from the discharge of such amounts of combustible gases, vapour, mists or dusts, the explosion of which could result in a pressure rise in this room exceeding 5 kPa, shall be determined as a room at risk of exploding.

8. Guidelines for determining the pressure increase in the room that could be caused by an explosion shall be specified in the Annex to the Regulation.

9. In the room, a danger zone should be determined if there is a mixture of explosive mixture with a volume of at least 0,01 m 3 in a compact space.

Chapter 9

Forest fire protection

§ 38. 1. Forests located at facilities which may present a fire risk to the forest shall be separated from those facilities by fire-belts, maintained in a state that ensures their usefulness throughout the year.

2. Types and ways of carrying out fire belts by entities designated as competent for their execution and maintenance in: Act of 28 September 1991 r. in the forest (Dz. U. of 2005 Nr 45, poz. 435, with late. 1. 4) ), the Act of 28 March 2003. o Rail transport (Dz. U. 2007 No 16, pos. 94, z późn. 1. 5) ) and the Act of 24 August 1991. the fire protection shall be determined by:

1) Regulation of the Minister of the Environment of 22 March 2006. on the detailed rules for the protection of forest fire protection (Dz. U. Nr. 58, pos. 405 and Nr 82, pos. 573);

2) the Ordinance of the Minister of Infrastructure dated 7 August 2008. on the requirements for distance and conditions allowing the location of trees and shrubs, elements of acoustic protection and the execution of earthworks in the vicinity of the railway line, as well as the way of arranging and maintaining the snow veil, and fire-belts (Dz. U. No. 153, pos. 955).

3. Paragraph Recipe 2 not applicable:

1. forests classified in the category III fire hazard category;

2. trees for more than 30 years old on public roads and in car parks and stands situated on unpaved roads, except in the case of polygonal and inter-polygon roads;

3) forests with a width of less than 200 m.

4. The alienation of forest areas to the category of fire hazard is carried out in the forest device plans, simplified forest device plans and plans for the protection of national parks.

§ 39. 1. At a distance of less than 30 m from the edge of the railway track or public road, with the exception of the road with an unpaved surface, leaving in particular branches, crunch, uncaged beetle of trees and post-operative waste is prohibited.

2. Owners, stewards or users of forests whose forests are self-formed or jointly form a forest complex with an area of more than 300 ha:

1) organize the observation and patrol of forests for the detection of fires and alarm about their insurrection, in accordance with the provisions on fire protection of forests;

2) provide and maintain water sources for fire prevention purposes;

3) keep the fire commute designated in the forest device plan in accordance with the provisions on the rules on the protection of forest fire protection;

4) means the positions of water draw with the marks in accordance with the Polish Standards concerning the signs of safety;

5) arrange and maintain in the places designated, in agreement with the local district commanders (urban) of the State Fire Service, the equipment base for the extinguishing of forest fires, in accordance with the regulations on fire protection of forests;

6) agree on the project of the forest device plan, draft of the simplified plan of the forest device and draft protection plan of the national park, in the part concerning fire protection, with the appropriate local commandant of the State Fire Service, for forests I and II of the fire hazard category.

3. The source of water for fire prevention in the forests should provide the possibility of obtaining water from a depth of not more than 4 m, counting between the water's mirror and the level of the water draw position, and be equipped with a position of drawing water along with the commusion.

4. The sources of water for fire protection in forests which spontaneously or jointly form a complex with an area of more than 300 ha, shall be provided in the form of no more than 2 tanks within the protected area containing a total of at least 50 m 3 water, external hydrants and/or watercourse with a fixed water flow of not less than 10 dm 3 Second, with the lowest water status, providing the nearest water draw in the area with a radius of:

1) not exceeding 3 km in the forest and fire hazard category;

2) not exceeding 5 km in the forest of the second category of fire hazard;

3) agreed with the local district commandant (city) of the State Fire Service in the third category of fire hazard category.

5. The owner or the owner of the forest shall place the information and warning boards on the protection of the fire in the forest at the entry into the forest and in the forest parks, in agreement with the local district commandant (urban) State Fire Service.

6. The fire-driving licences referred to in paragraph. Article 2 (3), and the bases of the equipment referred to in paragraph 2 (3). 2 point 5, specifies the Ordinance of the Minister of the Environment of 22 March 2006. on the detailed rules for the protection of forest fire prevention.

§ 40. 1. In the forests and in the forests, in the area of meadows, peat bogs and heaths, as well as in the distance of up to 100 m from the border of the forests, it is not permissible to carry out activities likely to cause danger of fire, in particular:

1) the unfire of fire outside the places designated for that purpose by the owner or the forest manager;

2) smoking tobacco, with the exception of places on hardened roads and places designated for the stay of people.

2. Paragraph Recipe 1 point 1 does not apply to forest management activities and the execution of works and operation of the mine in agreement with the owner or management of the forest.

Chapter 10

Fire protection of harvesting, transport and storage of agricultural agricultural foetal

§ 41. 1. During the harvesting, transport and storage of agricultural crops, the following shall be:

1) use the indications given in the operating instructions for the operation of the agricultural machinery and other with the drive;

2. use electric motors with an appropriate level of protection to the working conditions; the minimum distance of the propulsion system from the rudin, stogs and buildings with a combustible structure shall be 5 m;

3) set internal combustion engines on a non-combustible substrate, at a distance of at least 10 m from the rudders, stogs or buildings with a combustible structure;

4) secure exhaust devices of internal combustion engines prior to the departure of the sparks;

5) ensure the possibility of evacuation of people and equipment;

6. store the necessary propellant materials, in a quantity not exceeding good demand, in closed non-shellfish vessels, at least 10 m from the point of omnicity and the places of occurrence of combustents of agricultural crops;

7. equip halting, control and harvester spaces in fire extinguishers and, if necessary, equipment used for the execution of belts limiting the spread of fire.

2. Smoking on the use of equipment, machinery and vehicles during the harvest of agricultural crops and their transport shall be prohibited.

3. Use of open fire and smoking of tobacco at a distance of less than 10 m from the site of the halls and the places of occurrence of combustents of agricultural crops is prohibited.

§ 42. 1. The fire zone of the heap, the stogu or the broth with roasted plant products does not exceed the area of 1 000 m 2 or a cubature 5 000 m 3 .

2. At least the following distances shall be maintained when setting the rudders, stogs and brogs:

1) from buildings made of materials:

a) flammable-30 m,

(b) non-combustble and with a covering at least inflammable-20 m;

2) from public roads and railway tracks-30 m;

3) from the internal roads and from the boundary of the parcel-10 m;

4) from electrical power lines and cables of high voltage-30 m;

5) from forests and forested land-100 m;

6) between the rudders, the stogs and the brogels constituting separate fire zones-30 m.

3. Around the rudders, stogs and brogs should be performed and maintained to a surface of at least 2 m width at a distance of 3 m from their contour devoid of combustible materials.

4. Plant products shall be stored in such a way that their spondylitis cannot be used. In the event of the need to store the underserved products, the temperature should be checked periodically.

§ 43. The firing of straw and plant residues in the fields is prohibited.

Chapter 11

Transitional and final provisions

§ 44. In relation to objects erected before the date of entry into force of the Regulation:

1) the requirements laid down in § 27 ust. 1 and 2 shall not apply to premises erected before 17 January 1993;

2) the requirements laid down in § 18 (1) 2 and in Paragraph 19 (1) of the 1 in the case of buildings equipped with hydrants 52, shall be valid for the reconstruction and extension of the fire water system, as well as for the reconstruction, expansion, reconstruction and alteration of the use of the facility;

3) the requirements laid down in § 19 (1) 2 shall not apply if they have been equipped with hydrants 52 in accordance with the provisions of the Ordinance of the Minister of Internal Affairs and Administration of 21 April 2006. on fire protection of buildings, other construction sites and areas (Dz. U. Nr 80, poz. 563);

4) the requirements laid down in § 27 (1) 2 points 1 and § 29 (1) 1 point 1 shall not apply to commercial and exhibition buildings:

a) single-storey, containing a fire zone qualified for the hazard category of people ZL I with an area of more than 8,000 m 2 , but not more than 10 000 m 2 ,

(b) multistorey, containing a fire zone classified in the risk category of the people of ZL I with a surface area greater than 5 000 m 2 , but not more than 8,000 m 2 ;

5) the requirements set out in § 6 paragraph. 1 points 7 and 8 and paragraph 8 2 and 3 shall be met during the periodic update of the fire safety instructions referred to in paragraph 6 (1). 7.

§ 45. In relation to buildings erected in accordance with the Act of 7 July 1994. -Building law (Dz. U. 2006 r. Nr 156, pos. 1118, as of late. 1. 6) ) and implementing acts issued on the basis of that Law do not apply the criteria set out in § 16 (1). 2.

§ 46. The Regulation of the Minister of Internal Affairs and Administration of 21 April 2006 shall be repealed. on fire protection of buildings, other construction sites and areas (Dz. U. Nr 80, poz. 563).

§ 47. The Regulation shall enter into force after 7 days from the date of the announcement.

Minister of Internal Affairs and Administration: J. Miller

1) The Minister of the Interior and Administration heads the government administration-internal affairs, pursuant to § 1 paragraph. 2 point 3 of the Regulation of the Prime Minister of 16 November 2007. on the detailed scope of the action of the Minister of Internal Affairs and Administration (Dz. U. No 216, item. 1604).

2) Amendments to that Regulation have been announced in the Official Journal of the European U. 2003 r. Nr 33, pos. 270, of 2004. No. 109, pos. 1156, 2008 Nr 201, pos. 1238 and 2009 Nr 56, pos. 461.

3) The amendments to the said Act were announced in Dz. U. of 2002. No. 74, item. 676 and No. 117, pos. 1007, 2003 No. 210, item. 2036, 2004 Nr 96, pos. 959, Nr 116, poz. 1203, Nr 173, pos. 1808 i Nr 222, poz. 2249, of 2005. Nr 94, pos. 788 and No. 184, pos. 1539, 2006 No. 133, item. 935 i No 235, pos. 1700, of 2008 No. 180, pos. 1112 and No. 214, pos. 1347, of 2009 Nr 18, pos. 97 i No 125, pos. 1036 and 2010 Nr 47, poz. 278.

4) Amendments to the text of the single law have been announced in the Dz. U. of 2005 Nr 157, poz. 1315, No 167, pos. 1399 and No. 175, pos. 1460 and 1462, of 2006 No. 227, pos. 1658 and Nr 245, poz. 1775, 2007 Nr 59, pos. 405, No 64, pos. 427 and No 181, pos. 1286, 2008 No. 163, pos. 1011 and No. 199, pos. 1227, of 2009 Nr 18, pos. 97, Nr 42, poz. 340, No. 69, pos. 595, Nr 92, pos. 753 and No. 157, pos. 1241 and 2010 Nr 96, pos. 620.

5) Amendments to the text of the single law have been announced in the Dz. U. 2007 No 176, item. 1238 and No. 191, pos. 1374, of 2008 Nr 59, pos. 359, No 144, pos. 902, Nr 206, poz. 1289 and No. 227, pos. 1505 and 2009 No. 1, pos. 3, Nr 18, poz. 97, Nr 19, poz. 100, Nr. 98, pos. 817, Nr 115, poz. 966, Nr 157, pos. 1241 and No. 214, pos. 1658.

6) Amendments to the text of the single law have been announced in the Dz. U. 2006 r. No. 170, pos. 1217, 2007 Nr. 88, pos. 587, Nr 99, poz. 665, Nr 127, poz. 880, Nr 191, poz. 1373 and Nr. 247, pos. 1844, 2008 Nr 145, pos. 914, Nr 199, pos. 1227, Nr 206, poz. 1287, Nr 210, pos. 1321 i Nr 227, poz. 1505, of 2009 Nr 18, pos. 97, Nr 31, poz. 206, Nr 160, pos. 1276 and No. 161, pos. 1279 and 2010 Nr 75, poz. 474 and No. 106, pos. 675.

Annex 1. [ GUIDELINES FOR DETERMINING THE PRESSURE INCREASE IN THE ROOM THAT COULD BE CAUSED BY AN EXPLOSION]

Annex to the Regulation of the Minister of Internal Affairs and Administration
of 7 June 2010 (pos. 719)

GUIDELINES FOR DETERMINING THE PRESSURE INCREASE IN THE ROOM THAT COULD BE CAUSED BY THE EXPLOSION

1. When assessing the risk of an explosion of premises, account shall be taken of the most unfavourable consequences of the explosion of a situation which may arise in the process of their operation, taking into account the most dangerous situation, the nature of the substance and the greatest amount of substance that could be involved in the explosion response.

2. The pressure increase in the ΔP room (in Pa) caused by the explosion involving homogeneous flammable gases or vapours with molecules built from the atoms of carbon, hydrogen, oxygen, nitrogen and halogenates shall be determined by the equation:

infoRgrafika

where:

mmax

-the maximum mass of flammable substances forming a mixture of explosive which can be separated in the room in question (kg);

ΔPmax

-maximum pressure increase at stoichiometric explosion of a gas-or vapour-air mixture in a closed chamber (Pa);

In

-the rate of explosion response, which takes into account the incapability of the room, the non-admissibility of the explosion reaction, and the fact that there is less than 0,17 for combustible gas and vapour that would have been separated in the room. gases and 0,1 for flammable vapor;

V

-the volume of the airspace of the space, which is the difference between the volume and the volume of the installation, equipment, closed packaging, etc. (m 3 );

Cst-volumetric stoichiometric concentration of flammable gases or vapour:

infoRgrafika

b-stoichiometric oxygen factor in the explosion reaction:

infoRgrafika

nC, nH, nCl, nO-the quantities of carbon, hydrogen, halogenates and oxygen atoms in the gas or vapour molecule;

ρ-dense-dense gases or vapour at room temperature under normal operating conditions (kg * m -3 ).

3. The pressure increase in the room ∆P (in Pa), caused by an explosion involving the combustble substances not listed in point 2, is determined by the equation:

infoRgrafika

where:

qsp-combustion heat (J kg -1 );

After-atmospheric pressure normal, equal to 101 325 Pa;

Ρp-air density at T temperature (kg m -3 );

cp-air-correct heat equal to 1,01 10 3 J kg -1 K -1 ;

T -temperature of the room under normal operating conditions (K);

W = 0,17 for combustible gases and raised pale dust;

W = 0,1 for flammable vapour and mist;

other-as in the formula [ 1].

4. The mass of combustble pairs of m (in kg), secreted in the room due to the evaporation of liquid from the open surface, shall be determined by the equation:

infoRgrafika

where:

F -liquid evaporation area (m 2 ) -for each dm 3 of the liquid splated on the concrete floor shall be taken to be F = 0,5 m 2 for solutions containing not more than 70% of the mass contribution of the solvent and F = 1 m 2 for other liquids;

t-estimated maximum time of separation of pairs (s);

K-the evaporation factor specified in the table;

Ps-the vapour pressure of the saturated steam at the temperature of the t-room at ° C (Pa):

infoRgrafika

A, B, CA-Antoine equation coefficients for a given liquid;

M-molecular weight of liquid (kg kmol -1 ).

Table

Evaporation factor K values

Airflow rate above the evaporation surface (m s -1 )

Room temperature in ° C

10

15

20

30

35

0

1.0

1.0

1.0

1.0

1.0

0.1

3.0

2.6

2.4

1.8

1.6

0.2

4.6

3.8

3.5

2.4

2.3

0.5

6.6

5.7

5.4

3.6

3.2

1.0

10.0

8.7

7.7

5.6

4.6

5. In the event of an emergency ventilation being activated in the room for the determination of the mmax for flammable gases or vapour, it shall be permitted to take into account its operation if the air lifts are in the vicinity of the target area. the secretion of gases or vapour. The maximum mass of flammable substances used for the calculation of ΔP may then be reduced 'k' times, with:

infoRgrafika

where:

n-the amount of air exchange in the room at the operation of the emergency ventilation (s) -1 );

t-predicted time of secretion of gases or vapour (s).

6. The calculation of the expected pressure increase in the room is not required if without its investor, the design unit or the user deciding on the technological process considers the room to be at risk of explosion.