Advanced Search

Calculation Of The Energy Performance Of The Building Method

Original Language Title: Ēkas energoefektivitātes aprēķina metode

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$40 per month.
Cabinet of Ministers Regulations No. 348 in Riga on 25 June 2013 (pr. 27. § 36) building energy efficiency calculation method is Issued in accordance with the law of the energy performance of buildings article fifth 1. General questions 1. determines the calculation of the energy performance of the building method. Method used when drawing up the energy balance of the building level. If you draw up the energy balance of the building engineering systems level or if the building calculated energy required for heating of less than 50 kWh to calculate the area of a square metre a year, carried out a detailed calculation in accordance with the standard EN ISO 13790:2009 EN L "energy performance of buildings. Space heating and cooling energy calculation "(hereinafter referred to as the standard LVS EN ISO 13790:2009 L). 2. The terms used in the following terms: 2.1 heating and cooling energy needs – the calculated energy heating or cooling system to be delivered in an air-conditioned room or output to maintain the desired temperature in a given period of time, not taking into account the building engineering systems; 2.2. the heating or cooling season-period of the year when heating or cooling is used to a certain amount of power; 2.3. building calculated energy efficiency energy efficiency assessment-assessment, obtained on the basis of calculations of the energy consumption of building heating, cooling, ventilation, hot water and lighting needs; 2.4. building measurement model, mathematical model of the building used for the calculation of energy consumption; 2.5. the exported energy – energy, expressed in energonesējo, which supplies the building through a system border and used beyond the boundaries of a system; 2.6. energonesēj-substance or natural phenomenon, used for the production of heat and mechanical work, physical or chemical process; 2.7. internal heat losses and gains heat by building – creates the building's occupants (metabolic heat) and a device (for example, lighting, household appliances, Office equipment); 2.8. building the measured energy efficiency energy efficiency assessment-assessment, obtained on the basis of energy delivered and exported quantities measured; 2.9. conditioned space-part of a building that is blazing or chilled; 2.10. the conditioned area, air-conditioned rooms with a particular set of temperature controlled heating system, cooling or ventilation system; 2.11. carbon dioxide (CO2) emission factor, carbon dioxide (CO2) that is output into the atmosphere per unit of energy delivered. Carbon dioxide (CO2) emission factor including all carbon dioxide (CO2) emissions, which are linked to the building's primary energy consumed. Carbon dioxide (CO2) emissions factors defined in annex 1 of these rules; 2.12. additional energy — electricity, used for heating, hot water supply, air-conditioning, ventilation and lighting systems to produce and transform the energy supplied useful energy (such as fans, pumps, electronics). The energy that is produced, there is no additional energy; 2.13. the delivered energy, total energy, expressed energonesējo that is delivered to the building engineering systems through the boundary of the system, to ensure the necessary energy (such as heating, hot water, cooling, ventilation, lighting, devices) or to generate electricity. Energy supplied according to specific energy use can be calculated or measured; 2.14. primary energy – energy from renewable and non-renewable sources of energy that are not processed or transformed; 2.15. heat gain-heat, which occurs in the conditioned space inside or is forced into it from another heat source and is the energy used for heating, cooling or centralised preparation of hot water. Heat gains include internal heat gain and solar heat gain; 2.16. system boundary-boundary, which includes all the building-related areas (inside and outside of the building), where the energy is consumed or produced; 2.17. system heat loss-heat loss from buildings civil engineering system that does not participate in the life of the system return. System losses may become the building's internal heat gains, if they are recoverable. The heat recovered, no heat loss, but the benefits of thermal energy; 2.18. solar heat gains, heat, solar radiation, entering the building through Windows directly or indirectly (by absorption of building elements) through solid walls and roofs or passive solar construction of use (for example, winter gardens, translucent insulation). The use of active solar devices (for example, solar collectors) are building engineering systems; 2.19. space heating-heat delivery process to ensure thermal comfort; 2.20. cooling-heat discharge process to ensure thermal comfort; 2.21. the installed temperature-control system to maintain the normal arrangements for the indoor minimum temperature the heating period or the maximum temperature inside the cooling period. 2. assessment of the energy performance of the building required in building engineering systems 2.1. Basic conditions of building energy efficiency 3 assessment, the setting of annual energy consumption of building engineering systems, which provide: 3.1 heating; 3.2. the cooling (air and sausināšan); 3.3 ventilation (and air humidification); 3.4. the hot water supply; 3.5. lighting. 4. other energy consuming system built into the building and ensure the building's functional needs (for example, lifts, escalators and production technological equipment), take into account the energy efficiency rating of the building, but the calculations don't take into account in determining the annual energy consumption. 5. Building energy consumption assessment includes additional energy supply and engineering systems of the building energy loss. 6. energy consumption for heating, cooling, heat transmission losses and heat loss through the ventilation shall be assessed in accordance with the provisions of 3, 4, 5, and 6. the Department, taking into account internal and solar heat gains and building engineering systems loss recoveries. 2.2. in hot water supply system in buildings 7 Projected energy consumption for hot water systems assessed in accordance with the standard EN EN 15316-3-1:2009 L "building heating system. System energy consumption and efficiency calculation methodology. 3-part 1: household hot water system: requirements (water supply system requirements) "Chapter 5.2, annex A, A1 and A2 table or section 5.3 and Appendix B, standard EN EN 15316-3-2:2008" building heating system. System energy consumption and efficiency calculation methodology. 3-part 2: domestic hot water systems: hot water distribution "and the standard LVS EN 15316-3-3:2009 L" building heating system. System energy consumption and efficiency calculation methodology. 3-part 3: domestic hot water systems: hot water preparation ". 8. Existing buildings energy consumption for hot water system is assessed on the basis of the measured data on the consumption of heat and hot water consumption. 9. Energy consumption in the hot water preheating Infringed the calculation period shall be determined using the following formula: where (1) Infringed – energy consumption of hot water heating (kWh); V – hot water consumption (m3); ρk – water density at the hot water temperature of θw, o (kg/m3); Matter-water specific heat (J/kg K);
θū, delivery – cold water temperature (° c);
θk – hot water temperature (° c);
3600-conversion coefficients to take account of the transition from megadžoul to the kWh consumed. 10. If the building heating and hot water supply systems is a common heat energy accounting, then based on the data on energy and hot water consumption in the period is not used when heating, existing buildings tolerated such a simplification of the calculation of energy consumption in the water supply system (heating and hot water circulation) year period calculated using linear extrapolation. In this case, you must determine the hot water circulation heat losses from distribution: losses not conditioned 10.1 zones (such as a basement or attic); 10.2. the loss in the air-conditioned areas, which includes the period of heating heat gains. 2.3. Lighting Design buildings 11 energy consumption lighting evaluation to be carried out in accordance with the standard EN EN 15193:2009 L "energy performance of buildings. The energy requirements for lighting "(hereinafter referred to as the standard LVS EN 15193:2009 L). 12. Existing buildings energy consumption evaluation of lighting based on the lighting system (luminaries and their control) capacity, the actual working hours and measured the power consumption of the building. 13. Residential buildings the building's lighting system power consumption is not taken into account and does not include the annual energy consumption figures. 3. assessment of the energy performance of the building's boundary and evaluation 3.1. building energy efficiency assessment boundaries 14. Building energy efficiency assessment boundaries determined before the commencement of the assessment. System boundary is associated with a priceless object (such as a building, part of the building, the apartment) and includes all indoor and outdoor elements that are associated with building where energy is produced or consumed. Within the framework of the system of calculation of losses in detail, but outside the system boundaries are calculated using the conversion factors. Building energy efficiency rating and energy flow diagram given in annex 2 to these regulations. 15. Energy can be imported or exported through the building. If the system installation (for example, boiler, chiller, cooling tower) is located outside the boundaries of the building structures, energonesēj consumption (such as gas, electricity, heat, water) is determined using the meter. 16. energy efficiency rating of the building limit energonesēj (gas, electricity, heating and water) has a counter, but liquid and solid energy-storage system. If part of the building engineering systems (such as boiler, chiller, cooling tower) are located outside the boundaries of the building structures, consider that they located inside the boundaries, and the loss of the system concerned is taken into account. 17. The active solar, wind and water energy are not the building's energy balance. Energy balance include energy delivered by the energy consumption of buildings, equipment and additional energy required to deliver building energy from heat sources (such as from the solar collector). 18. the primary energy consumption calculation, in the rating system, which is included in the building or buildings within the site in accordance with the provisions of annex 3. 19. building energy efficiency evaluation of a group of buildings can be made if all the following conditions: 19.1. building shared heating or cooling systems; 19.2. building on the same property; 19.3. the total air-conditioned area of buildings does not exceed 1000 square meters. 3.2. building energy efficiency evaluation in building energy efficiency assessment measured shall be determined in accordance with the provisions of Chapter 4. The calculated energy efficiency assessment of the building shall be determined in accordance with section 5 of these regulations. 21. the Projected, compensated and renovējam buildings, making a calculated assessment of energy efficiency in the design phase, the following output data: 21.1. climatic data, established by the Cabinet of Ministers of 23 august 2001 Regulation No. 376 of the "rules for the Latvian et seq of LBN 002-01" Būvklimatoloģij "," approved in the Latvian et seq LBN 003-01 "Būvklimatoloģij" (hereinafter "LBN 003-01 Būvklimatoloģij"); 21.2. the space comfort and population parameters, which determine the legal construction, health and hygiene, environment and other areas; 21.3. the design of the building external delimiting and engineering system design characteristics. 22. If in the course of construction deviation from the original construction plan affect scores of buildings, then by passing the building into the calculation of the adjustment, taking into account the actual building construction and external delimiting engineering system properties. 23. Operational buildings measured energy efficiency rating and energy efficiency calculated assessment is determined using data on: 23.1. actual energy consumption; 23.2. the actual external climatic conditions; 23.3. the actual space and population parameters of comfort; 23.4. actual building construction and external delimiting engineering system characteristics. 24. Operational buildings measured energy efficiency rating and energy efficiency calculated assessment validated in accordance with the provisions of Chapter 6. 4. building energy efficiency assessment measured 4.1 General requirements the evaluation period 25. energy consumption for all energonesēj in the same period to be assessed. If the previous period of not counting energonesēj, the building measured energy efficiency assessment cannot be performed. 26. evaluation period is the full number of years. If the evaluation period is not the full number of years, the annual energy consumption is obtained by using the method of extrapolation. 27. If the assessment period is shorter than five years, made the adjustment in energy consumption due to climatic conditions. 28. If the assessment period of the building made changes that affect its energy efficiency by more than 10 percent, the above findings are not to be used for assessing the energy performance of the building. If the building changes affect buildings to 10 percent, above the data obtained can be used with adjustments based on the appropriate calculations. 4.2. data acquisition and correction (extrapolation) 4.2.1. With meter energonesēj listed 29. With meter energonesēj listed (electricity, gas, heat) consumption is the difference between the two readings of the meter reading assessment at the beginning and end of the period. 30. Electricity, gas and heat supplier or building operator invoices can be used to evaluate the energonesēj consumption (evaluation period-full years). 31. If energonesēj is used in multiple technical systems and multiple uses, energonesēj consumption divided by technical systems and goals. 4.2.2. the liquid fuel tank 32. Heating Oil level in the tank is measured assessment at the beginning and end of the period, using a calibrated scale. Heating oil consumption in the period of the assessment is the assessment of the tank contents at the beginning of the period, minus any content of the tank at the end of the period of the assessment and evaluation period plus the quantity of fuel purchased. 33. If the gas balloons, delivered fuel valued by adding the number of the cylinder used (take into account the volume of the cylinder). 34. If the burner works with a fixed capacity (without modulation) and is equipped with a burning time of the meter, fuel consumption is the difference between the two readings, made the assessment at the beginning and end of the period, multiplied by the flow rate of the burner. The flow rate is measured before the first aspirate reading and after each burner adjustment or cleaning. 35. The amount of energy delivered is determined in one of the following ways: 21.8. multiplying the heating oil quantity used with it the lower heating and boiler efficiency, established by a lower calorific value of fuel (heat of the fuel quantity unit when it is completely burnt, and subtracted from the combustion process in water evaporation heat). Lower calorific value of fuel shall be determined in accordance with the provisions of paragraph 1 of annex 1; 35.2. multiplying the heating oil quantity used, with its gross calorific value and efficiency of the boiler, as determined by the highest calorific value of fuel (heat of the fuel quantity unit when it is completely burnt). The higher heating value of fuels shall be determined in accordance with the provisions of paragraph 2 of annex 1. 4.2.3. Solid fuels 36. Solid fuels (e.g. coal, wood) energy content depends on its quality and density. Solid fuel consumption is the fuel mass inventory assessment at the beginning of the period, minus the mass of the fuel stocks for the end of the period of assessment and evaluation period plus fuel bought in mass. 37. The amount of energy delivered is determined in one of the following ways: 37.1. multiplying the waste solid fuels with it the lower heating and boiler efficiency, established by a lower calorific value of fuel; 37.2. multiplying the solid fuel waste quantity with its gross calorific value and efficiency of the boiler, as determined by the highest calorific value of the fuel. 38. for solid fuels, the measured volume of the mass multiplied by the density of the fuel. Calculating confidence intervals in mass, density and moisture must be taken into account for uncertainty. 4.2.4. Energonesēj consumption, if the installation of a constant average power, and heating and cooling in energonesēj 39. Energonesēj to be used, if the installation medium power is constant and is a linear extrapolation, quantity is calculated using the following formula: where (2) E-corrected energonesēj quantity (kg, m3 or Wh); EPER-energonesēj quantity consumed energonesēj the accounting period (kg, m3 or Wh); -evaluation period tkop (year or season); tper-energonesēj accounting period (year or season). 40. Energonesēj, which are used for heating or cooling, the extrapolation made using energy accounting or simplify the calculation under this provision, paragraph 42. 41. If the assessment is carried out using energy accounting, the assessment period should cover a wide range (at least monthly) average external air temperature range. 42. the simplified calculation of extrapolation used to calculate the quantity of energonesēj used for heating or cooling during the entire year. It is calculated using the following formula: where (3) Qkop-year apr calculated energy required heating and cooling (who); Qnov, apr-assessment period calculated energy required heating and cooling (who); Enov-energonesēj quantity that used for heating and cooling of the evaluation period (kg, m3, or What). 43. The year calculated energy required heating and cooling Qkop, apr is calculated using the formula and add 4 separate heating and cooling energy, calculated by using the formula of 5 and 6: Qkop, apr, apr + Qdz, Qapk = apr Qapk apr = (4) HK (T1-T2) t-ηapk (Asol-Esol + Qiek) (5) Qdz apr = (Asol Esol + Qiek) – ηdz HK (T1-T2) t (6): Qapk, April – the energy required for heating (Wh); Qdz, apr – cooling requires energy (Wh); HK-building the overall coefficient of heat loss (W/K), which is determined in accordance with the provisions of paragraph 133; t-assessment period, one full heating or cooling (tapk) (tdz) season (hours); T1-the average rating of the setpoint temperature (heating or cooling) period (oC); T2 – the average outside air temperature (oC) the calculation period; ηapk-benefit ratio of using heating under this provision or paragraph 99 standard LVS EN ISO 13790:2009 L; ηdz-benefit ratio of using cooling under this provision or standard 101 LVS EN ISO 13790:2009 L;-building effective Asol solar energy savācoš area (m2); ESOL-solar radiation assessment period t to the Asol (Wh/m2); Qiek-all the benefits of building internal evaluation period t (Wh). 4.3. Energy consumption adjustment, due to climatic conditions, 44. If the measured energy efficiency assessment is based on the energy consumption data obtained from the period, which is less than five full years, the required measured power consumption adjustment due to climatic conditions, to ensure measurement period in compliance with the energy consumed by the average local climate. 45. The measured energy consumption for heating and cooling medium adapted to the climatic conditions of the location of the building. Power adjustment according to the climatic conditions of use LBN 003-01 "Būvklimatoloģij" table 7 heating under the period length and the average outside air temperature values. 46. Power correction due to climatic conditions, calculated in accordance with the provisions of paragraph 47 and 48. 47. Energy consumption adjustment using degree days, carried out using the following formula: where (7) Q-corrected energy consumption (Wh); Q1-energy consumption evaluation period (the who); GDD1-legislative degree days, which shall be determined in accordance with this rule 48; GDD-degree days evaluation period, determined in accordance with this rule 48. 48. the degrees of the number of days is determined using the following formula: 29.9. GDD1 = Dnapk (T1-T2) (8) 30.0. GDD = Dapk (T1-T3) (9): GDD1 – the regulatory degree days; GDD-degree days evaluation period; Dnapk-the number of heating days, regulations under the LBN 003-01 "Būvklimatoloģij"; Dapk – heating days evaluation period; T1-indoor temperature (° c) during the period of the evaluation; T2 – the average external air temperature under LBN 003-01 "Būvklimatoloģij" (oC); T3 – actual average external air temperature (° c) during the period of the evaluation. 5. building energy efficiency calculated assessment 5.1. required and the data obtained 49. building energy efficiency calculated data necessary for the evaluation to be obtained: 30.5. surveying the building; 30.6. using the characteristics laid down in the construction and building energy efficiency regulatory laws; 30.6. the building of technical documentation (for example, technical project, inventory plan). 50. building energy efficiency evaluation of calculated need following data: 50.1. heat transmission and ventilation characteristics; 50.2. heat gains from internal heat resources, solar heat gain; 50.3. klimatoloģisk indicators; 50.4. the buildings and building components, systems and use of the specification; 50.5. the comfort requirements – set temperature and air exchange rates. 51. building engineering systems assessment requires the following information: 51.1. the breakdown by areas of the building (the different areas you can use various building engineering systems); 51.2. building heat loss distribution or recovery building (internal heat gains, heat recovery ventilation heat); 51.3. the supply air ventilation rates and temperature if the building centrally or cooled and the fire blazing is the combined use of energy for air circulation and cooling or apkurināšan. 52. Using a calculation method retrieves the following data: 52.1. the total energy required heating and cooling; 52.2. the total energy consumption for heating and cooling; 52.3. heating and cooling season duration (hours of operation of the system); 52.4. advanced energy consumption for heating, cooling and ventilation systems. 5.2. building calculated energy efficiency assessment procedure 5.2.1. building heating and cooling energy needs and indicators 53. Energy is calculated based on the area of the building heat balance. Heating and cooling energy is a necessary building engineering system energy balance data. Making buildings energy efficiency assessment calculated the energy balance of a building divided into: 53.1. level to determine the overall energy consumption indicators; 53.2. building a inženiersistēm to determine the level of primary energy consumption and carbon emissions. 54. The calculated energy efficiency indicators necessary for the evaluation to be obtained in the following order: 54.1. choose heat balance calculation method in accordance with the provisions of this subchapter 5.2.2.; 54.2. lays down common conditioned and non-conditioned space within the premises in accordance with the provisions of this subchapter 5.3; 54.3. determines the calculation of the area of the border in accordance with the provisions of subchapter 5.3; 54.4. the conditions for the calculation defined in the indoor, external climatic and other environmental data; 54.5. calculation of the building and its individual areas in the energy required for heating and energy Qapk cooling Qdz: 54.5.1 during the period. the calculation heat loss with heat transmission in accordance with the provisions of this subchapter 5.5; 54.5.2. calculation of heat losses through ventilation in accordance with the provisions of subsection 5.6; 54.5.3. calculation of indoor thermal benefits under this provision 5.7 subdivision; 54.5.4. calculation of solar heat gains in accordance with the provisions of subsection 5.8; 54.5.5. calculation of the dynamic parameters in accordance with the provisions of this subchapter 5.9; 54.6. calculation of the heating and cooling season duration in accordance with the provisions of subchapter 5.4.1. 5.2.2. heat balance calculation method you choose in the building or the area 55. thermal balance determination shall take into account: 55.1. transmission of heat flow between conditioned space and external environment-the difference between the set temperature conditioned space and external air temperature; 55.2. transmission and ventilation heat flows between neighbouring areas – the difference between the set temperature in the air-conditioned area and indoor temperature next to the premises; 55.3. natural or mechanical ventilation heat flow – the difference between the set temperature in the air-conditioned room and supply air temperature; 55.4. internal heat gains (including negative benefits of heat loss), such as people, equipment, lighting, and heat flow or absorption of building engineering systems; 55.5. solar thermal benefits that you can get directly (for example, through Windows) or indirectly (for example, with the absorption through the building's elements); 57.5. heat savings of building engineering systems and depending on the thermal inertia of the building; 55.7. heating energy required when building engineering systems supply heat to raise the temperature to the indoor minimum level requested (the set temperature for heating); 55.8. energy for cooling if the building cooling system remove heat to decrease the indoor temperature to the maximum requested levels (setpoint temperature for cooling). 56. the energy balance of the building recovered energy also included buildings from different parts of the building engineering systems. 57. The building's energy balance calculation is carried out using one of the following methods: 57.1. smooth method. Heat balance calculation for a long enough period, a month or a full season. The calculation ignores accumulated and played part of the heat, but take into account the dynamic effects, empirically determining the use of benefits and the loss factor; 57.2. dynamic method. It is used to heat balance calculation of short periods of time (for example, by hours). Take into account the provision of heat and heat from building the last part which depends on the building's thermal inertia. The application of dynamic calculation method, to be taken in accordance with the standard EN ISO 13790: EN 2009 Annex L C. 58. Dynamic method simulates the heat resistance, heat capacity and internal and solar thermal benefits of building or building areas. Using dynamic method takes into account that heating season thermal surplus affect the internal temperature rises above the set temperature, the leftover heat carrying with an additional transmission, ventilation and accumulation, if you do not use the motor cooling. Turn off the oven can not be directly applied to reduce the internal temperature, as it is dependent on the inertia of the building (the building of heat release from the array). The calculation of the cooling period that set the internal temperature falls below the set temperature. 59. with the steady method to take into account the dynamic effects, calculated using the correlation factors. Internal heating and solar heat gain calculation shall take into account the use that only part of the benefit is used, reducing the building's energy needs for heating, if the internal temperature increase above the set temperature. 60. The cooling calculation by using the method even take into account the following factors: 60.1. loss – transmission and ventilation heat loss calculations must take into account that only a part of the transmission and the ventilation heat loss is used, reducing the need for cooling. Unused transmission and ventilation heat flow occurs in periods or intervals (for example, at night), when cooling is not required, but it may be necessary for other periods or intervals (e.g. daily); 60.2. the yield – internal and solar heat gain calculation to take into account that only a part of the internal heat gain and solar heat transmission and compensate for ventilation losses, in accepting a certain maximum indoor temperature. Unused part of the heat contribute to cooling the need to avoid the indoor temperature rises above the set temperature. 5.3. the boundaries and area of the building 5.3.1. Building border and area determination 61. Heating and cooling needed for calculation of energy down the building. The limits of all the buildings, building būvelement, which separates the conditioned spaces from the external environment (air, soil or water) and the adjacent buildings or not conditioned spaces. 62. Heating and cooling energy required for the calculation of the distribution of buildings: 62.1. in one area; 62.2. multiple zones (multizon calculation), taking into account the heat flow between the zones; 38.7. multiple zones (multizon calculation), without taking into account the heat flow between the zones. 63. If a building divided into multiple zones, building heating and cooling energy is calculated separately for each zone. The heat flow between the zones take into account, if necessary recommended energy efficiency measures or further evaluation of results. 5.3.2. building the distribution zones 64. Small (up to five percent of the zone's area) is not heated area (non-conditioned space) can be included in an air-conditioned (heated) and be considered to be conditioned. The building Division of the number of zones is not required when the buildings are ascribed to all of these conditions: 64.1. setpoint temperature heated spaces no higher than 4 ° c; 64.2. all premises (areas) are not mechanically refrigerated or mechanically cooled and set is the temperature difference of cooling the premises does not exceed 4 ° c; 64.3. rooms used the same heating system (if any) and the same cooling system (if any); 64.4. building at least 80 percent of the total floor used the same ventilation system; 64.5. building at least 80 percent of the total floor ventilation air quantity (m3) rooms on the floor area (m2) per unit of time differs by more than four times. 65. If at least one of these rules in paragraph 64 above conditions are not met, the building is divided into zones and each of them is attributed one area calculation conditions. 5.3.3. One area calculation 66. One area in the calculation of the heating temperature set is determined using the following formula: where (10)-setpoint temperature Tapk of a building or area heating (° C); Tuzs, DAC, the heating setpoint temperature (° C) for the area, determined in accordance with this rule 5.10 subdivision; Aapr-calculates area (m2), which is determined in accordance with the provisions of subsection 5.3.5. 67. One area in the calculation of the cooling temperature set is determined using the following formula: where Tdz-(11) setpoint temperature of a building or area for cooling (° C); Tuzs, dz-setpoint temperature cooling area (° C), which shall be determined in accordance with this rule 5.10. subdivision; Aapr-calculates area (m2), which is determined in accordance with the provisions of subsection 5.3.5. 5.3.4. calculation of multiple zone 68. If the building is divided into a number of zones and the heat flow between the zones shall not be taken into account (calculation with associated areas), then the calculations to be made, are not taken into account any type of heat transmission (e.g., air motion). In this case, the calculations are made separately for each zone under one area calculation procedure. 69. some areas, which have a combined heating and cooling system, heating and cooling energy is required to separate zones calculated the amount of energy required. Separate zones, which are not common in the heating and cooling system, energy consumption of the building is a separate zones calculated the amount of energy used. 70. If the building is divided into several areas and take into account the heat flow between the zones, then take into account any type of heat transmission (air movement) and the calculation carried out in accordance with the standard EN ISO 13790: EN 2009 Annex L B. 5.3.5. Calculate the area of floor space of 71. determination, located within the building are air-conditioned building floor area Aapr is calculated. If the building is divided into zones, zone of all conditioned floor area calculation amount must be equal to the all the buildings of the conditioned room floor area calculations. 72. in the area of the Aapr is calculated including: 72.1. all conditioned space; 72.2 conditioned space area. not if they are linked to an air-conditioned rooms and they are maintained in the internal microclimate (such as inner halls, passageways, corridors, stairwells). 73. the calculation area does not include premises not intended to maintain internal space temperature (e.g. in the cellar, heated attics, garages). Calculate the area of heating and cooling season can be determined separately. 5.4. building heating and cooling Calculation procedures 5.4.1 and seasonal duration discovery 74. heating and cooling heating and cooling calculation is performed in the following order: 74.1. the duration of the season. 74.2. calculation of energy required; 46.2. the possible repetition of the calculation related to the building and the system interaction, or additional information is received. 75. the calculation of the length of the heating season tapk shall be determined in accordance with the LBN 003-01 "Būvklimatoloģij". 76. The actual length of the heating season is determined according to the number of hours worked for the season when the system in question (for example, pumps, fans). It shall be based on at least one month for the measurements. 77. the duration of the heating season uses the calculation model validation in accordance with the provisions of this subchapter 6.2. 78. The actual cooling season duration is determined according to the number of hours worked for the season when the system in question (for example, pumps, fans). It shall be based on at least one month for the measurements. 79. the calculation of the length of the cooling season tapk determined using data on the actual length of the cooling season. 5.4.2. The building's heating and cooling needs in the energy calculation using the method even 80. each building in the area of heating energy for each calculation period (month or season) is determined using the following formula (note that Qapk > = 0): Qapk, n = Qapk, z-ηapk, Qapk, ieg, which lit × (12) for each building and each month or season: Qapk, n-building necessary for heating energy (Wh); Qapk, z is the total heat loss for heating (Wh), which shall be determined in accordance with the provisions of paragraph 81; Qapk, ieg-total benefits of heat for heating (Wh), which shall be determined in accordance with the provisions of paragraph 82; ηapk, ieg-heat gain factor, the use of which is determined in accordance with the provisions of this subsection 5.9.2. 81. additional heat (humans) need not be included in the calculation of the energy. 82. the area of each building cooling energy required for each calculation period (month or season) is determined using the following formula (note that Qdz > = 0): Qdz, n = Qdz,-ηdz, z × Qdz ieg, which z (13) each building and each month or season: Qdz, n-building cooling requires energy (Wh); Qdz, z is the total heat loss in cooling (Wh), which shall be determined in accordance with the provisions of paragraph 83; Qdz, ieg-total heat gain for cooling (Wh), which is determined in accordance with the provisions of paragraph 84; ηdz, z-heat loss factor, the use of which is determined in accordance with the provisions of subsection 5.9.3. 83. The total heat loss in buildings area calculation period: 83.1. heating Qapk, z = Qapk, pr + Qapk, ve (14) 51.7. cooling Qdz, z = Qdz, pr + Qdz, ve (15) which each building and each month or season: Qapk, z is the total heat loss for heating (Wh); Qdz, z is the total heat loss in cooling (who); Qapk, pr-total heat loss for heating with transmission (who), to be determined in accordance with the provisions of this subchapter 5.5; Qdz, pr-total heat losses the cooling of the transmission (who), to be determined in accordance with the provisions of this subchapter 5.5; Qapk, ve-total heat loss for heating with ventilation (Wh), determined in accordance with the provisions of this subsection 5.6; Qdz, ve-total heat loss in cooling by ventilation (Wh), determined in accordance with the provisions of this subsection 5.6. 84. The total heat gain of building area calculation period: 84.1. heating Qapk = Qiek + Qsol, ieg (16) 52.3. cooling Qdz = Qiek + Qsol, ieg (17) which each building and each month or season: Qapk, ieg-total benefits of heat for heating (Wh); Qdz, ieg-total benefits of heat for cooling (who); Qiek-internal heat gains amount calculation period (Wh), determined in accordance with the provisions of this subchapter 5.7; Qsol-solar heat gain calculates the sum of the period (Wh), which is determined in accordance with the provisions of subsection 5.8. 5.5. transmission of heat loss through the steady 85. method, the total heat loss with transmission calculation each month or season and for each zone by using the following formula: 85.1. heating (18) 85.2. cooling Qdz, pr = 1990s k {HT, k × (T1, T2, or-k)} × where tdz (19) for each building and each calculation period: Qapk, pr-total heat transmission losses for heating (Wh); Qdz, pr-the total loss of heat transmission in cooling (who); HT, k – building heat loss through the transmission coefficient of the element k to the next room, the environment or area with temperature T2, k (W/K), which is determined in accordance with the provisions of paragraph 86; T1, DAC-building or buildings for part of the heating setpoint temperature (° c), which shall be determined in accordance with this rule 5.10. subdivision; T1, or – the building or buildings for part of the cooling setpoint temperature (oC), determined in accordance with this rule 5.10 subdivision; T2, k-temperature element k next to the space, the environment or area (c), which shall be determined in accordance with the provisions of paragraph 87; tapk-duration of the period of calculation for heating (h); tdz — calculate the period length for cooling (h). 86. the transmission of heat loss coefficient k HT, element k is determined in accordance with the Cabinet of Ministers of 27 November 2001, regulations no 495 "rules for the Latvian et seq of LBN 002-01" building construction siltumtehnik "delimiting the approved Latvian et seq LBN 002-01 to" building construction "delimiting siltumtehnik. 87. the side room, external temperature T2, or k value determined by the following situations: 87.1. heat transmission to the external environment-temperature T2, k value is the value of the external temperature; 87.2. the heat transmission to the adjacent kondicionētaj areas – not to the temperature T2, k value is near room temperature or external temperature value, if used in the calculation of the adjustment factor that reduces the heat transmission coefficient of temperature difference; 101.8. heat transmission to the adjacent zone of influence of the Sun (for example, glazed Loggia, terrace, Sun garden) – calculation of heat transmission as the adjacent kondicionētaj not spaces. The impact of solar radiation on the impact area of the Sun the temperature of the room is taken into account in calculating heat gain; 87.4. calculation with linked areas, heat transmission to the adjacent kondicionētaj areas – temperature T2, k value is adjacent to the temperature value of the area; calculation with an 87.5. linked areas – heat transmission with other kondicionētaj zones shall not be taken into account; 87.6. heat transmission through the soil-temperature T2, k value of external temperature value, the calculation using the customization factor that reduces the heat transmission coefficient of temperature difference and determined in accordance with the standard EN ISO 2008 EN 13789: "thermal characteristics of the building. Heat transition and space airing generated heat exchange coefficient. Calculation methodology "(hereinafter referred to as the standard LVS EN ISO 13789:2008); 87.7. heat transmission to the adjacent buildings-temperature T2, k value is next to the building's indoor temperature on the basis of the building next to the appropriate data and use. 5.6. ventilation heat loss with 88. Overall heat loss with ventilation of conditioned floor area is calculated for each month or season and for each zone by using the following formula: 88.1. heating Qapk, ve = 1990s k {HVE, k (T1 – T2, delivery, DAC)} × tapk (20) 88.2. cooling Qdz, ve = 1990s k {HVE, k (T1,-T2, or delivery)} × tdz (21) where each building zone z and for each calculation period: Qapk ve – the total heat flow with ventilation heating season (who); Qdz, ve – the total heat flow with ventilation cooling season (who); HVE, k – coefficient of heat transmission with air flow ventilation, element k entering an area with delivery temperature T2, delivery, k (W/K), which is determined in accordance with the provisions of paragraph 89; T1, DAC-building or building zone heating setpoint temperature (oC), determined in accordance with this rule 5.10 subdivision; T1, or building or buildings – zone setpoint temperature for cooling (c), which shall be determined in accordance with this rule 5.10 subdivision; T2, delivery – element k air supply temperature (oC), including buildings or buildings with ventilation or seepage area that is determined in accordance with the provisions of paragraph 89; tapk-duration of the period of calculation for heating (h); tdz — calculate the period length for cooling (h). 89. total ventilation heat loss coefficient, k with HVE air flow ventilation element k values, or the values of flow qve, k comply with appropriate ventilation system standards EN EN 15242:2009 L "building ventilation. Calculation method of air flow (including caursūc) determination in buildings "(hereinafter referred to as the standard LVS EN 15242:2009 L) and LVS EN 15241:2009 L" building ventilation. Methods to calculate the ventilation and caursūc of energy loss caused by commercial buildings "(hereinafter referred to as the standard LVS EN 15241:2009 L). Individual air supply temperature T2 k, delivery, k value assumes the following: 89.1. ventilation with air infiltration from the external environment, the delivery temperature T2, delivery, k value is the value of the external temperature; 89.2. ventilation with air infiltration from neighbouring kondicionētaj areas or not a porch, the delivery temperature T2, delivery, k value of external temperature value. The impact of solar radiation in addition to the impact of the Sun the temperature is taken into account in calculating heat gain; 89.3. calculations with the States in which areas the ventilation included air infiltration from neighbouring kondicionētaj areas, the delivery temperature T2, delivery, k value is the next value in the temperature of the area; 89.4. mechanical ventilation supply temperature T2, delivery, k value is the air delivery temperature value, the air exits from the central air handling equipment and entering a building or building zones, determined in accordance with the standards EN EN 15242:2009 L and LV EN 15241:2009 L; 89.5. If using centralized or piedzesēšan piesildīšan and energy piesildīšan or to piedzesēšan is calculated separately, the delivery temperature is the temperature at central piesildīšan or piedzesēšan; calculation of heat recovery 55.7. external air temperature T2 change with supply air temperature, which is obtained in accordance with the standards EN EN 15241:2009 L and LV EN 15242:2009 L. 90. Total ventilation heat loss coefficient for each month or season and each heating or cooling zone is calculated using the following formula: k = ρac of HVE, qve, k, where the environment (22) Hv, k – coefficient of heat transmission with air flow ventilation element k, entering the area with the delivery temperature T2, delivery, k (W/K), which is determined in accordance with the provisions of paragraph 89; qve, k, environment – air flow element k time average flow rate (m3/h), which is determined in accordance with this rule 91; ρac-air volume = 0.34 for calorific value (Wh/(m3 × oC)); k-each of the applicable air flow elements (such as mechanical ventilation, natural ventilation, caursūc). 91. The air flow element k time average flow level is calculated using the following formula: qve, k = fv, t, k, k, which qve (23) qve, k – air flow element k time average flow rate (m3/h), which is determined in accordance with the standards EN EN 15241:2009 L and LV EN 15242:2009 L; k, t, fve-air element k the part, which is determined by the same standard as qve , k. 5.7. Internal heat gains 5.7.1. Internal heat gains calculation procedure 92. Internal heat is the heat benefits the benefits of internal heat sources, including negative thermal gains (from the room to the cold source). Internal heat is the heat of any benefits resulting from the internal sources and used for space heating, space cooling, or hot water. 93. The internal heat gains include: 93.1. the metabolic heat from the public and dispel the heat of the devices; 93.2. ambient heat from lighting devices; 93.3. heat that spread from the hot water system or absorbed by the hot water system; 93.4. heat that spread from the air conditioning and ventilation systems or absorbed by the heating, air conditioning and ventilation systems; heat from 93.5. processes and objects or to them. 5.7.2. General internal heat gains under the steady and dynamic method 94. According to the uniform method of heat gains from internal sources in a given area of the building in a given month or season is calculated using the following formula: where (24) Qiek – internal heat gains amount to a certain month or season (Wh) (heating and cooling is determined separately); BL-reducing factor next to the conditioned area with no internal heat source, l, determined in accordance with the standard EN ISO 2008 EN 13789: (if the heat source l power does not affect the calculation result, bl = 1); Φiek, k – the average heat flow of the internal heat source (k) the calculation period (month or season) (W), which is determined in accordance with the provisions of paragraph 97; Φiek, no, l – the average heat flow of the internal heat source l adjacent non air-conditioned room calculation period (month or season) (W), which is determined in accordance with the provisions of paragraph 97; t-specific month or season duration (h), which is determined in accordance with the provisions of this subchapter 5.4.1. 95. in the next room is not conditioned not conditioned space outside the heating and cooling energy consumption calculation area borders. If not conditioned area located more than one conditioned, heat flow indicator at the internal heat source l not conditioned room Φiek, no, l must be split by kondicionētaj zones according to conditioned floor area, in accordance with the provisions of subsection 5.3.5. 96. Using dynamic method, heat flows from the internal heat sources in a given area of the building is calculated for each hour, using the following formula: where (25) Φiek – internal heat gain heat flow amount (W); BL-reducing factor next to the conditioned area with no internal heat sources in accordance with the standard EN l a EN ISO 13789:2008; Φiek, k – hours of heat flow from the internal heat source k (W), which is determined in accordance with the provisions of this subchapter 5.7.3; Φiek, no, l-hour heat flow from the internal heat source l adjacent not conditioned room (W), which is determined in accordance with the provisions of paragraph 97. 5.7.3. Internal heat gains elements 97. Thermal benefits of internal heat sources in a given building or building area is calculated for each hour, using the following formula: Φiek = Φiek + Φiek + passengers, population, Φiek, apg + Φiek + ADzV + þ, Φiek, Φiek, proc, which (26) Φiek-heat gain (or Φiek, Φiek k no, l) the amount of the internal heat source stream (W); Φiek, population-heat flow from the population (W), which is determined in accordance with the provisions of paragraph 99; Φiek, passenger-flow of heat from the device (W), which is determined in accordance with the provisions of paragraph 100; Φiek, apg-heat flux from the light (W), which is determined in accordance with the provisions of paragraph 101; Φiek, w-heat flow of the hot water system (W), which is determined in accordance with the provisions of paragraph 103; Φiek, ADzV-heat flow from the heating, air conditioning and ventilation systems (W), which is determined in accordance with the provisions of paragraph 105; Φiek, proc-heat flow of processes and objects (W), which is determined in accordance with the provisions of paragraph 109. 98. The cold source that outputs heat from the building (area), is the heat source with a negative sign. 99. The metabolic heat from the population, population Φiek for each building and each calculation period shall be determined in accordance with the provisions of the annex or calculated using the following formula: Φiek = qiedz, where an fiedz Aapr (27)-time part fiedz when residents in the building; qiedz-specific heat input from citizens to the calculated building area (W/m2); Aapr-calculates area (m2), which is determined in accordance with the provisions of subsection 5.3.5. 100. the ambient heat from appliances, passenger Φiek for each building and each calculation period shall be determined in accordance with the provisions of the annex or calculated using the following formula: Φiek, dev = Aapr qier which fier (28) Fiera-time part when the device works; qier – specific heat input of the devices to the calculated building area (W/m2); Aapr-calculates area (m2), which is determined in accordance with the provisions of subsection 5.3.5. 101. heat flow values from lighting devices have the following value Φiek, apg: 101.1. heat flow value of luminaires, calculated as part of the lighting systems of the energy consumed. The energy consumed by the part that is less than 1, if the suction ventilation allows heat discharged directly from luminaries; 101.2. heat flow value of other lighting elements (for example, decorative lighting, specialty lighting, lighting of the process). 102. the flow of Heat from the lights lighting systems shall be calculated in accordance with the standard EN EN 15193:2009 l. heat flow from other lighting elements calculated taking into account the function of the building, lighting, usage and calculated purpose. 103. The heat flow value of hot water supply system in Φiek, þ is the sum of the following: Φiek, Φiek, WW WW =, + Φiek, WW, circus, which other (29) Φiek, w-thermal flow of hot water supply system (W); Φiek, þ, circus-heat flow from the hot water circulation hot water systems (W), which is determined in accordance with the provisions of paragraph 104; Φiek, Wow, another – the heat flow from a hot water system (except the hot water circulation) (W), which is determined in accordance with the standard EN EN 15316-3-2:2008.104. heat flow from the water circulation hot water systems is determined using the following formula: w = qiek Φiek,, ū, Circus Circus, circus, where Lou, (30) Φiek, þ, circus-heat flow from standing water circulation hot water systems (W); qiek, þ, circus-heat flow from the hot water circulation system to meters length (W/m), which is determined in accordance with the standard EN EN 15316-3-2:2008; Lou, circus-hot water supply system water circulation pipe length in a particular area of the building (m). 105. the value of the heat flux to the heating, air conditioning and ventilation systems or from them (scatter) Φiek, ADzV is the sum of the following: Φiek, ADzV = Φiek, Φiek, Or + A + Φiek, where V (31) Φiek, ADzV-heat flow from the space heating, air conditioning and ventilation systems (W); Φiek, A – heat flow from the space heating systems (W), which is determined in accordance with the provisions of paragraph 106; Φiek, Dz-heat flow from the room air conditioners (W), which is determined in accordance with the provisions of paragraph 107; Φiek, V-heat flow from venting system (W), which is determined in accordance with the provisions of paragraph 108. 106. The heat flow from the space heating system Φiek, (A) consists of building area distributed heat from advanced power sources (for example, pump, fan, electronic devices) and the heat, which dispersed from the emissions of heating systems, circulation, distribution, storage and production of energy. The value obtained in accordance with the standard EN EN 15316-2-1:2009 L "building heating system. System energoprasīb and efficiency calculation method. 2-part 1: heat transfer in space heating system "(hereinafter referred to as the standard LVS EN 15316-2-1:2009 L) and standard LVS EN 15316-2-3:2009 L" building heating system. System energoprasīb and efficiency calculation method. 2-part 3: the Siltumsadal network for space heating "(hereinafter referred to as the standard LVS EN 15316-2-3:2009 L). 107. the flow of heat from the air conditioning system or Φiek, Or consists of the heat from the power source (such as a pump, fan, electronic devices) that are dispersed in the building area, and heat that spread of air conditioning system with cold emission circulation, distribution, storage and production of energy. Heat flow value from the air conditioning system or obtained in accordance with the standard EN EN: 15243 ventilation of buildings L ' 2009. Room temperature, as well as siltumslodz and calculating energy buildings with room conditioning systems "(hereinafter referred to as the standard LVS EN 15243:2009 L). 108. The heat flow value of ventilation system in your building area Φiek, V is the relevant building heat dissipated from the zone ventilation systems. Heat flow value is determined in accordance with the standard EN EN 15243:2009 L. Supply air dispersed heat includes supply increase in temperature, determined under the relevant air flow and ventilation systems standard EN EN 15241:2009 L or standard LVS EN 15242:2009 L and what are not considered internal heat sources. Internal heat from ventilation systems which are not taken into account in determining the supply temperature may include ambient heat from the blower motor. 109. The warmth of the processes and objects or Φiek, consists of heat from certain common processes in the relevant area or on the building and (or) of the items placed in the building area. If the surface temperature of the heat source is close to the room temperature, the heat actually transferred the quantity depends on the heat source and the external air temperature difference. The following is added to the heat internal heat gains, but the heat transfer added to the heat transmission loss under this provision 5.5. the subheading. 5.8. Solar Heat gains 5.8.1. Solar thermal conditions calculated 110. Energy balance uses only solar energy equipment and energy delivered additional energy required for the administration of the building from heat energy source. 111. The heat gains from solar heat sources (solar-irradiated buildings construction elements and air-conditioned premises) resulting from solar radiation available to the building's location, as well as from the surface and the area of the savācoš orientation, shading, solar constant permeability and absorption and thermal heat transfer. Factor, which includes the areas of savācoš and savācoš characteristics of the surface area (including shaded effects), there are solar thermal actual savācoš area. 5.8.2. General solar heat gains 112. heat benefits of solar building area in a particular month or season is calculated using the following formula: where (32) Qsol-solar heat gain in the amount of the current month or season (who); BL-reducing factor next to the conditioned area with no internal heat source, l, determined in accordance with the standard EN ISO 13790: EN 2009 L; Φsol, k – average heat flux from the Sun the heat source in a given month or season k (W), which is determined in accordance with the provisions of this subsection 5.8.3; Φsol, l – the average heat flux from the sun heat sources adjacent to the l not conditioned spaces in a given month or season (W), which is determined in accordance with the standard EN ISO 13790: EN 2009 L; t-specific month or season's duration in hours, which shall be determined in accordance with the provisions of this subchapter 5.4.1. 113. Using dynamic method, heat flow from the solar heat sources in a given area of the building is calculated for each hour, using the following formula: where (33) Φsol – solar heat gain heat flow amount (W); BL-reducing factor next to the existing not conditioned area with solar heat sources l, which is determined in accordance with the standard EN ISO 13790: EN 2009 L; Φsol, k-hour heat flux from the sun heat source k (W), which is determined in accordance with the provisions of this subsection 5.8.3; Φsol, l – hours of heat flow from the solar heat source l adjacent not conditioned room (W), which is determined in accordance with the standard EN ISO 13790: EN 2009 L. 5.8.3. Solar heat gain elements 114. Sun savācoš areas are glazing external opaque elements of inner porch wall and floor, as well as the wall behind the transparent or translucent insulating covers. Characteristics as a whole depend on climate, weather, and location (for example, from the Sun, the relationship between direct and diffuse radiation). 115. in the light of that overall changes and characteristics by hours, and during the year, select the appropriate medium and constant values that correspond, for example, a heating, cooling or summer comfort calculation. 116. the flow of Heat from solar heat gains calculation, using the following formula: k = Φsol, Hairdryer, I, k, where k (34), Φsol (k)-solar heat gain through building element k (W); Hairdryer-external obstacles due to the reducing coefficient k effective surface solar savācoš square, which is determined in accordance with the provisions of paragraph 121 and 122.; S, k-surface (k) (with a specific orientation and tilt angle) the effective area of savācoš in the area (m2), which is determined in accordance with paragraph 117 of these regulations (glazing) and 118 (opaque building elements); I, k-calculation period in solar radiation received at the surface of savācoš square meter (W/m2), which is determined using meteorological information in statistical data. 117. the construction of the Glazed delimiting element (such as) effective savācoš the area is calculated using the following formula: k = the hair dryer, g, gg (1-FF) Al, p, S, k (35) which, in the savācoš of the element the glazed area (m2). For the glazed elements shall be deemed to include polymers and other light permeable material containment structures, which act as glazed elements; Hairdryer, g – shading reduction coefficient with the conditions of transferability, which is determined in accordance with the provisions of paragraph 119; GG-common element transparent parts of the solar energy transmittance, determined in accordance with the provisions of annex 5. The transparent part of the element can consist of glazing or from permanent sunlight dissipating or aizēnojoš layers; FF-frame part of the projected area of the frame area relative to the total projected area of the element the glazed, which is determined in accordance with the provisions of paragraph 123; Al, p-General glass elements (such as Windows) the projected area (m2). 118. Opaque buildings delimiting the effective part of the design with the warmth of the Sun savācoš the area is calculated using the following formula: k = αs, c Sharp, Rs etc. (36), which Ac, S, k – opaque parts of the effective area (m2) savācoš; αs, c – absorption coefficient opaque parts of the Sun's radiation, which is determined in accordance with the standard EN ISO 6946:2009 EN L ' būvkomponent and būvelement buildings. Siltumpretestīb and heat exchange coefficient. Calculation methodology "(hereinafter referred to as the standard LVS EN ISO 6946:2009 L); RS-opaque parts of the external surface of the thermal resistance (m2 K/W), which is determined in accordance with the standard EN ISO 6946: EN 2009 L; Etc.-opaque parts of the heat transmission coefficient (w/(m2 × oC)), which is determined in accordance with the standard EN ISO 6946: EN 2009 L; Eye-opaque parts of the projected area (m2). 119. The shading with the conditions of transferability shading reduction factor for a hairdryer, g is calculated using the following formula: (37) or (38) where: yy-total solar energy transmittance through the window, if you are not using the solar shading, which is determined in accordance with the provisions of annex 5, table 1; GG + shadow – total solar energy transmitted through the window if you use solar shading, which is determined in accordance with the provisions of annex 5 of tables 1 and 2; FL, in, the time factor is assessed in part through solar shading (such as solar radiation intensity function which depends on the season and the orientation of the window), which is determined in accordance with the provisions of annex 5 of table 3; Gene-solar reduction factor, which is determined in accordance with the provisions of annex 5 of table 2. 120. Solar control shading to distinguish between such solar shading control types: 120.1. no control (included in the window g value); 120.2. manual operation; 120.3. the motorised operation; 120.4. automatic control. 121. the external shading reduction ratio, amplitude is kurа hair dryer from 0 (fully reduced) and 1 (not reduced) to reflect a reduction in the intensity of the solar radiation to determine the permanent surface from shading: 121.1. other buildings; 121.2. the surrounding terrain and land cover; 121.3. shelters, overhanging and similar structures; 121.4. the same building other elements; 121.5. the wall external parts, which mounted the glass elements. 122. Shading correction factor is calculated using the following formula: a = the hair dryer Fh Fp (39) Fl, where Fh-shading correction factor for the horizon effect under this provision 6. table 1 of the annex; FP-shading correction factor for hanging and shelter effects in accordance with the provisions of annex 6, table 2; FL-shading correction factor the effects of window position in accordance with the provisions of annex 6 of table 3. 123. each window frame square portion shall be determined in accordance with the standard EN ISO 10077-1 EN: 2009 L ' window, door and shutter thermal characteristics. Calculation of Siltumcaurlaidīb. Part 1: General "or the calculation uses a fixed FF value = 0.3.5.9. Dynamic characteristics 5.9.1. calculation procedure 124. Using dynamic method takes into account the heat resistance, heat capacity (power) and thermal benefits of solar and internal heat resources building or building area. 125. the calculations take into account the dynamic effects, introducing using benefit factor for heating and cooling of the use factors in the loss. 126. If the heating is intermittent or turned off, the building's thermal inertia effects taken into account separately. 5.9.2. the yield factor for heating use 127. Benefits of using factor heating ηapk, ieg is the heat balance and the numerical value of the γapk parameter aapk (which depends on the building's thermal inertia). The benefits of using factor heating is determined using the following formula: 127.1. If yapk > 0 and ≠ 1, yapk (40), 127.2. If yapk = 1 (41) if yapk 0, 127.3. (42) < 127.4. (43) where each month or season and each building area: ηapk, ieg-benefit utilization factor for heating; γapk-heat balance factor heating nodes; Qapk, z is the total heat loss for heating (Wh), which shall be determined in accordance with the provisions of section 83.1.; Qapk, ieg-total heat gain for heating (Wh), which is determined in accordance with the provisions of section 84.1.; aapk-from the time constants t Dac depend on numerical parameter, which is determined using the following formula: = τ aapk aapk .0 .0 + DAC DAC, where τ (44) .0-aapk dimensionless numerical parameter. Continuously (more than the fire blazing 12 hours a day), buildings (such as apartment buildings, hotels) for the calculation of the month aapk .0 = 1, the calculation of aapk .0 season = 0.8; DAC-τ of a building or area time constant (h), which is determined in accordance with the provisions of paragraph 132; .0-specified time τ DAC constant. Continuous fire blazing (more than 12 hours a day), buildings (such as apartment buildings, hotels) for the calculation of the month τ = 15 h, jrb .0 seasonal calculation τ = 30 h. JMC .0 128. Benefits of using factor is determined independently of the heating characteristics of the system, assuming that temperature is completely controlled and have unlimited flexibility. 5.9.3. the Loss factor of using cooling Loss of use 129. factor cooling ηdz, z is the balance sheet value of heat γdz and cooling of a numeric parameter adz (depending on the building's thermal inertia). Loss factors of use for cooling is determined using the following formula: 129.1. If ydz > 0 and ≠ 1, (45) ydz 129.2. If ydz = 1, (46) 129.3. If 0, (47) ydz < 129.4. (48) which each month or season and each building area: ηdz, z-loss factor of utilization of cooling; γdz – cooling parts heat balance; Qdz, z-cooling parts of the total heat loss with transmission and ventilation (Wh), determined in accordance with the provisions of this subparagraph; 51.7. Qdz, z-cooling parts total heat gains (Wh), determined in accordance with the provisions of this subparagraph; 52.3. adz – from the time constant τdz depending on the numeric parameter, which is determined using the following formula: adz = τ or τ or adz .0 .0 + (49) .0-adz dimensionless numerical parameter. Continuously cooled (more than 12 hours a day), buildings (such as hotels) for the calculation of the month = 1 .0 adz, seasonal calculation adz .0 = 0.8; – τ or of a building or area time constant (h), which is determined in accordance with the provisions of paragraph 132; .0-specified time τ or constant. Continuously cooled (more than 12 hours a day), buildings (such as hotels) for the calculation of the month or τ = 15 h, .0 seasonal calculation or τ .0 = 30 h. 130. Loss of use factor is determined independently of the characteristics of the cooling system, assuming that temperature is completely controlled and is flexible. 5.9.4. The building of the time constant, the coefficient of thermal mass and internal heat capacity Building 131. time constants, coefficients and the mass of heat internal heat capacity of dynamic parameter values calculated in accordance with the procedure laid down in this section or adopted in accordance with the provisions of annex 7. 132. the area of a building or of the time constant t represents the air-conditioned inner zone of thermal inertia in the heating and the cooling period. It is calculated using the following formula: τ = Cm HK that (50) – τ of a building or area time constant heating or cooling or JMC t t (h); Cm – adjust the building's internal heat capacity, calculated in accordance with the provisions of paragraph 134 (Wh/l); HK-building the overall heat loss coefficient, calculated in accordance with the provisions of paragraph 133 (W/K). 133. the area of a building or the overall heat loss factor is calculated using the following formula: HK = (HT + Hv, k, k), where (51) HT, k – building heat transmission loss factor (W/K), which is determined in accordance with the provisions of this subchapter 5.5; HVE, k – ventilation heat loss (W/K), which is determined in accordance with the provisions of subsection 5.6. 134. in the area of a building or the corrected internal heat capacity is calculated by summing all the Cm building element of the adjusted heat capacity, which is in direct thermal contact with the zone's internal air: Cm = Χj preferential (52) Cm which Aj-adjusted internal heat capacity (Wh/l); Χj – adjusted to the internal heat capacity building element j square (Wh/(m 2 x K)), which is determined in accordance with the standard EN ISO 13786:2009 EN L ' būvkomponent of the thermal characteristics of the building. Dynamic thermal characteristics. Calculation methodology (ISO 13786:2007) "; AJ-item (j) area (m2). 5.10. The indoor conditions of operating mode 5.10.1. running mode and continuous or semi-continuous heating and cooling 135. Heating and cooling used in the following operating modes: 135.1. continuous heating cooling and (or) the constant set temperature; 135.2. night time and (or) a week to set up a reduced temperature or off; 135.3. "holiday" heating or cooling (such as periods when rooms reside people); 135.4. maximum heating or cooling load (the period when the check raise relevant indicators). 136. the continuous heating of the heating period full of buildings or building zone uses the installed temperature Tuzs, DAC. 137. For continuous cooling in cooling period full of buildings or building zone uses to set up temperature of Tuzs. 138. Actual average temperature in heating period can be higher, and it creates a pārkurināšan and should be taken into account with respect to benefits of use. Cooling for part of the actual average internal temperature may be lower, and this creates unnecessary consumption of energy (losses). 139. Irregular (semi-permanent) heating and cooling down as a continuous (heating or cooling) to adjust the set temperature by meeting one or more of the following conditions: 139.1. average room temperature is used in the calculation, as the set temperature: 139.1.1. If installed temperature difference between the heating or cooling of permanent and reduce the heating or cooling is less than 3 ° c; 139.1.2. If the building time constant, determined in accordance with the provisions of paragraph 132, is at least five times less than the shortest reduced heating (heating) or cooling (cooling); 139.2. Permanent heating part of the set temperature set temperature is used as the calculation of all the periods, if the time constant, determined in accordance with the provisions of paragraph 132, is three times larger than the longest period of reduced heating. 140. The installed temperature of continuous use refrigeration period all periods when the building time constant, determined in accordance with the provisions of paragraph 132, is three times larger than the longest period of reduced cooling. 5.10.2. adjustment of heating break 141. Where is the heating break and are not met, this provision sub-chapter conditions 5.10.1., heating energy is calculated using the following formula: Qapk, n = asamz × Qapk, DAC, n, N, n-Qapk (53) heating power required, taking into account the breaks (who); Qapk, n, n-energy required for heating the continuous heating period, assuming that the set temperatures are controlled in all days of the month (who); asamz, DAC-reduction factor heating break time, determined in accordance with the provisions of paragraph 142. 142. The reduction factor for heating with breaks asamz, DAC is calculated using the following formula: asamz = 1, bsamz, DAC, DAC (τapk .0/τ) × γapk × (1-fN, DAC) (54) (with minimal value, DAC, DAC asamaz = fN and maximum value asamaz, DAC = 1): asamz, DAC-reduction factor for heating with breaks; fn, DAC-part of the number of hours a week with a continuous heating (setpoint temperature is not reduced or heating is not turned off), for example, (5 x 14)/(7 × 24) = 0.42; bsamz, DAC-empirical correlation factor (the value bsamz, DAC = 3); τ-area of a building or of the time constant (h), which is determined in accordance with the provisions of paragraph 132; τapk .0-recommended time constant heating part (h), which is determined in accordance with the provisions of this subchapter 5.9.2.; γapk-heat balance of heating part proportion to be determined in accordance with the provisions of this subsection 5.9.2. 143. If there is a cooling break and this provision is not complied with section 5.10.1. these conditions, cooling energy is calculated using the following formula: Qdz, n = asamz, or × Qdz, n, N, n-Qdz (55) cooling power required, taking into account the breaks (who); Qdz, n, n-cooling energy required for continuous cooling period, assuming that the set temperatures are controlled in all days of the month (who); asamz, dz-reduction factor for cooling with breaks, which is determined in accordance with the provisions of paragraph 144. 144. The reduction factor for cooling with breaks, or asamz is calculated using the following formula: asamz, bsamz, or or = 1-(τdz .0/τ) × γdz × (1-fN, or) (56) (with minimal value, or asamz = fN, and the maximum value of either asamz, or = 1): asamz, dz-reduction factor for cooling with breaks; fn, or – the number of days part of the week at least to the time of day the set temperature for cooling (the temperature is reduced, or the machine is not turned off), such as 5/7; bsamz, dz-empirical correlation factor (the value bsamz, or = 3); τ-area of a building or of the time constant (h) shall be determined in accordance with the provisions of paragraph 132; τdz .0-specified time constant cooling part (h), which is determined in accordance with the provisions of this subsection 5.9.3; γdz-heat balance the ratio of the cooling part, determined in accordance with the provisions of this subsection 5.9.3. 5.10.3. "holiday" period of adjustment 145. individual buildings (such as schools) in the heating or cooling season, the "holiday" period significantly reduce heating or cooling energy. 146. Months, which include the "holiday" period, the heating and cooling energy is calculated separately for a continuous period and the "holiday" period and results in linear interpolated according to holiday and residential part of the period, using the following formula: 146.1. Qapk, n = N × Qapk, fapk, n, n + (1-fapk, N) × Qapk, on the (57) 146.2. Qdz, n = N × Qdz, fdz, n, n + (1-fdz, N) × Qdz, on (58) : Qapk, n-heating power required, taking into account the "holiday" period (the who); Qdz, n-cooling power required, taking into account the "holiday" period (the who); Qapk, n, n-need for heating energy in a continuous heating period, assuming that the set temperatures are controlled in all days of the month (who); Qdz, n, n-cooling energy required for continuous cooling period, assuming that the set temperatures are controlled in all days of the month (who); Qapk, n, on-heating energy required "holiday" period, assuming that the set temperatures are controlled in all days of the month (who); Qdz, n, on-cooling energy required for the "holiday" period, assuming that the set temperatures are controlled in all days of the month (who); fapk, N – "holiday" period part month heating period (e.g. 10/31); fdz, N – "holiday" period part month cooling period (for example, "10/31). 5.11. Energy use heating and cooling the building zone common 5.11.1. the necessary energy for heating and cooling 147. total energy required heating and cooling the building zone is calculated by summing the under this provision and paragraph 141.142 calculated energy of the period, taking into account the possible workload for different heating or cooling parts: 147.1. (59) 147.2. (60): Qapk, n, which set – the total energy required for heating specific zone (Wh); Qapk, n, i-heating energy required for a given calculation period in zone i (hourly or monthly) (Wh), determined in accordance with the provisions of this subchapter 5.4.2; Qdz, n,-total energy needed in a given area (who); Qdz, n, j-cooling energy required for a given calculation period in zone j (an hour or a month) (Wh), determined in accordance with the provisions of this subchapter 5.4.2. 148. Heating and cooling season duration to the appropriate system components operating period shall be determined in accordance with the provisions of this subchapter 5.4.1. 149. the results of the calculations of several zones (with thermal effects between zones or not) the total heating and cooling energy of a specific need for heating, cooling and ventilation systems to combine different areas has the necessary amount of energy through the zones, which use different HP system combination: 149.1. (61) 149.2. (62) where: n, Qapk, set, HP – the total area of the whole building heating power required HP is using a particular combination of the system (who); Qapk, n, z – the total area of the building for heating energy required for z, using a combination of certain system (Wh), which is determined in accordance with the provisions of paragraph 147; Qdz, n, set, HP – the total area of the whole building cooling energy required for HP, using a combination of certain system (who); Qdz, n, z – the total area of the building cooling energy required for z, using a combination of certain system (Wh), determined in accordance with paragraph 147 of these rules. 5.11.2. the total system energy use heating, cooling and ventilation of 150. If the heating, cooling and ventilation systems are combined, the total energy use for heating Qapk, beat and total energy use for cooling Qdz, sis (including system loss) is defined as the energy needed for heating and cooling functions in accordance with the relevant standards in the heating and cooling systems LVS EN 15316-2-1:2009 L, EN EN 15316-2-3:2009 L, EN EN 15241:2009 L and LV EN 15243:2009 L. 151. Common system of heating energy , cooling and ventilation systems is calculated according to the following system combinations: 151.1 total systems used. power Qapk, Qdz, sis, sis, i and i to energonesēj of chapter i, which included the use of palīgenerģij or (who); 151.2. heating the necessary amount of energy Qapk, n, i, a heating system losses, beat Qapk, i lose and heating systems of Qapk, papildenerģij, Papa, i hit the energonesēj i (Wh). Loss and papildenerģij include energy production, transport, control, distribution, storage and discharge. This paragraph shall also apply to the cooling systems Qdz, n, i, Qdz, Qdz, sis, sis, i and the pap, i; system heat loss 151.3. determines, taking into account the overall system efficiency. In this case, the calculation shall be made using the following formula: 151.3.1.  (63) 151.3.2.  (64): Qapk/dz, beat-energy heating or cooling systems, including system losses (who); Qapk/dz, n-energy required heating and cooling using a specific heating system (Wh), which is determined in accordance with the provisions of paragraph 149; ηapk/dz, beat-in general the effectiveness of the system heating or cooling systems, including energy production, electronics, transport, storage, distribution and exhaust losses, except when it identified as additional energy. 152. Power system loss is determined as the total losses, plus the system recover from system loss. 153. zudumo power system includes the buildings heat loss of more uneven distribution of room temperature and temperature control. 154. the total additional required power ventilation systems shall be determined in accordance with the standard EN EN 15241:2009 L and shall include the following types of energy: 154.1. fans; 154.2. heat recovery from refrigeration; It is suitable for centralised air 154.3.; 154.4. air central cooling.  6. building the model validation of calculation 6.1. calculation of Building model validation using 155. building a calculation model validation (testing) to ensure that the calculation of energy performance of the building derived indicators meet actually obtained. This is the calculated and actual buildings for pointer comparison is necessary to accurately evaluate energy efficiency measures identified benefits (calculate the planned power consumption after implementation). 156. The validated calculation model of the building used in the operation of existing buildings energy efficiency assessment (certification) and identify the energy efficiency improvement measure performance. The use of validated data sets of the building, which is building the model for calculation of raw data that one or more of the raw data have been adjusted to the actual data base so that the result of the calculation, using the model significantly different from not the actual measurement data. A validated set of data quality is a balance between the cost of acquisition (harvesting) and corresponding accuracy. 6.2. calculation of the building model validation procedure 157. building calculation model validation (testing) procedures shall be carried out in the following order: 157.1. acquire the measured energy efficiency indicators in accordance with the provisions of Chapter 4; 157.2. collects energy efficiency calculations necessary data and indicators (for example, climatic data, actual actual indoor conditions, population data, building heating dispersion of information); 157.3. energy efficiency test scores. 158. the calculation of the energy performance of the data obtained from the building design documentation, conducting surveys and measurements. 159. All data used to assess confidence intervals. Data that cannot be obtained directly, using the calculation obtained or regulations and standards. 160. the evaluation period the energy collected and calculated at the beginning of the data must refer to the same time period. 6.3. verification of indicators for energy efficiency energy efficiency indicators 161. review all energonesēj compared to the measured and calculated the energy efficiency evaluation of the results of the evaluation of the energy efficiency of energy consumption. 162. If the measured energy efficiency assessment results and the calculated results of the evaluation of the energy efficiency comparison of indoor temperature equal conditions is acceptable (differs less than 10 percent and not more than 10 kWh/m2 per year), it is considered that the calculation model of the building, including the estimated start of the data are reliable and energy efficiency assessment may proceed. 163. If the outcome of the assessment is not acceptable, do further investigation, to verify or enforce such influencing factors, which have not previously been taken into account. Repeat the test with a new start of the data set. 164. If necessary, adjust the starting data for comparison of energy performance assessment results would be acceptable. 6.4. Indoor microclimate and the external climatic conditions 165. evaluation of climatic data shall be determined in accordance with the LBN 003-01 "Būvklimatoloģij" using meteorological information in statistical data. 166. Surveying buildings, evaluate the actual internal temperature of the building, because in practice it is often different from the designed temperature, and this significantly affect the cooling and heating energy consumption is used. Internal temperature measurement (measurement) is used in the following methods: 166.1. buildings with mechanical ventilation air temperature measured in the exhaust pipe up to the direction of air flow from the fan. Ventilated area's average temperature is evaluated when the exhaust fan is turned on; 166.2. internal temperature and other parameters of the measurements of the room more buildings using building automated management and control equipment, which provides computerized records of measurements; 166.3. with small single-channel data recorder temperature measured or recorded in some common areas of the building season in typical conditions – the days of the month or seasonal meteorological indicators; 166.4. temperature set indicator used when heating or cooling system controls the thermostat and the thermostat calibration is checked. 166.5. with a pyrometer or manual air temperature gauges for air temperature shall be determined immediately several measurement points. 167. with regard to air infiltration and natural ventilation the external air flow actual evaluation used the following methods: 167.1. air handling equipment in the air flow rate; 167.2. marking of gas solution in accordance with the standard LVS EN ISO 12569:2009 L ' thermal insulation of buildings-determination of air exchange building-Marked gas dispersion method ". 168. the internal heat source, such as the number of people and duration of stay in the buildings assessed, surveying the building, or is obtained from the owner or operator of the building. 169. The internal heat sources as artificial lighting and electrical appliances are evaluated using the electricity consumption records, if the meter is not also added heating or cooling systems. If the data are not available, the lighting calculations carried out in accordance with standard EN EN 15193:2009 l. assessing internal heat sources, take note that not all the energy is used for lighting the internal heat source (for example, if lighting is located outside the building or heat is partially discharged). 170. Hot water consumption data for buildings that have installed a separate meter, obtained from the difference between the two readings of the assessment at the beginning and end of the period. If hot water is not listed, so consumption is assessed by population, building use and medium hot water consumption data using the data referred to in the standards EN EN 15316-3-1:2009 L, EN EN 15316-3-2:2008 and EN EN 15316-3-3:2009 L. 171. Consumed electricity bills used to evaluate artificial lighting energy consumption is used when the meter is connected to other systems (such as cooking, heating, cooling systems). If the counter data can not be used, energy consumption is calculated in accordance with the standard EN EN 15193:2009 L 7. Overall energy efficiency of the building a calculation of the required 172. After the (calculated) and used (measured) energonesēj calculation determines the total energy efficiency of the building. 173. The total building energy efficiency indicators calculation: 173.1. energy consumption – kWh to calculate the area of a square metre a year: 173.1.1. total heating, cooling, ventilation, mechanical hot water preparation, as well as lighting (if applicable in accordance with the provisions of paragraph 13); 173.1.2. district heating; 173.2. primary energy consumption – kWh to calculate the area of a square metre a year, as well as part of total energy consumption in the building percentages; 173.3. carbon dioxide emissions assessment – kilograms of carbon dioxide to calculate the area of a square metre a year. 174. Primary energy consumption is calculated from the energy supplied and exported energy each energonesēj (primary energy factors not part of renewable energy adopted in accordance with the provisions of paragraph 3 of annex 1), using the following formula: where (65) EP-primary energy consumption (kg); Epieg, i-energonesēj i delivered energy (Wh); EEx i-energonesēj i exported energy (Wh); FP. i-supply, primary energy factor of delivered energy for energonesēj i (kg/who); FP, ex, i-primary energy factor for exported energy energonesēj i (kg/who). 175. Assessing the emission of carbon dioxide, emitted carbon dioxide (CO2) mass is calculated from the energy delivered and exported for each energonesēj (carbon dioxide (CO2) emission factor shall be determined in accordance with the provisions of paragraph 4 of annex 1), using the following formula: where (66), carbon dioxide (CO2) emitted mass (kg); Epieg, i-energonesēj i delivered energy (Wh); EEx i-energonesēj i exported energy (Wh); Kpieg, s – carbon dioxide (CO2) emissions factor energy supplier i (kg/who); Kexi, i – carbon dioxide (CO2) emissions factor energy exporter i (kg/who). 8. energy efficiency improvement measures planned energy savings assessment 176. To assess the planned energy efficiency improvement measures, the energy savings obtained using the same buildings the calculation model used for evaluating the energy efficiency calculated. 177. If the measured energy use assessment calculation model of the building and start data validation, calculation, the values obtained are compared with measured values and check the calculation model of the building. This increases the probability that the planned measures for improving energy efficiency energy savings calculation is accurate and that the planned energy efficiency improvement measures in practice will give the expected results. 178. If a building planned to use similar to the above, the benefits of the planned energy efficiency measures for the evaluation of the use of certain climatic and population data. This allows you to assess the management practices of the buildings and the impact of changes in behaviour. 179. In identifying the necessary energy efficiency improvement measures, prepare one or more of the buildings energy efficiency scenarios in which specific and mutually agreed energy efficiency measures. Given that the individual events can interact (for example, increased thermal insulation or passive solar heat gains can lower boiler efficiency), each individual in the course of implementing the measures resulting effects may not be counted. The combined measures must be calculated taking into account the mutual interactions. 180. Each proposed scenario (includes specific energy efficiency improvement measures) the starting data changes according to the planned energy efficiency improvement measures and the calculation. The difference between the assessment, obtained before the energy efficiency improvement measures, and assessment, obtained by them, is the measure of the impact on energy consumption. 181. After the necessary identification of energy efficiency improvement measures for the calculation of a streamlined building regulatory energy efficiency assessment. For this purpose use the calculation model of the building with the issue (start) data set, taking into account the impact of energy efficiency improvement measures and regulations for the start of the data set. The energy efficiency improvement measures planned actual efficiency depends on how the building will actually be used. 182. Heating and other energy-consuming systems piegādājoš or economic assessment carried out in accordance with standard EN EN 15459:2008 "energy efficiency of buildings. Economic evaluation of building energy systems ". Informative reference to European Union Directive provisions included in the law arising from the European Parliament and of the Council of 19 May 2010 the 2010/31/EU directive on the energy performance of buildings. Prime Minister Valdis Dombrovskis Economy Minister Daniel Pavļut 1. pielikumsMinistr kabineta2013 of 25 June 2004, Regulation No 348 fuel calorific values, primary energy factors and carbon dioxide (CO2) emission factors 1. lower calorific value of fuel shall be determined in accordance with the European Commission of 21 June 2012 in Regulation No 601/2012 on greenhouse gas emissions monitoring and reporting in accordance with Directive 2003/87/EC of the European Parliament and of the Council of annex VI. 2. Fuel higher heating value shall be determined by fuel lower calorific value of the coefficients by multiplying them by a conversion factor set out in table 1 of this annex. table 1 no PO box Fuel conversion factor from the lower calorific value of the gross calorific value 1. Diesel 1.06 2. Natural gas 3 1.11. Liquefied petroleum gas 1.09 4. Hard coal (anthracite) 1.04 5. Brown coal (lignite) 1.07 6. Wood 1.08 3. Primary energy factors not renewable energy part 2. of this annex set out in the table. 2. table no PO box Energonesēj or power source primary energy factor of not renewable energy part 1 FPS. Diesel fuels 1.1 2. natural gas 3 1.1. liquefied petroleum gas 1.1 4. hard coal (anthracite) 1.1 5. Brown coal (lignite) 1.2 6. biogas 0.5 7. wood 0.2 8. Heat from the boilers, cogeneration produced in fossil fuels 0.7 9. renewable fuels 0.0 10. Heat from the boilers (without CHP) fossil fuels 1.3 11. renewable fuels 0.1 12. Of electricity grids 1.5 13. from fossil resources 2.0 14. from renewable energy produced in the building engineering systems within the 0.0 15. Wind, solar, geothermal, hydrothermal, aerotermāl and marine energy, hydropower 0.0 note. The value corresponds to the heating system with 70% return on cogeneration. 4. Carbon dioxide (CO2) emission factors specified in table 3 of this annex. table 3 no PO box Energonesēj or source of energy carbon dioxide (CO2) emission factor 10-6 kg/who 1. Fuels according to the European Commission of 21 June 2012 in Regulation No 601/2012 on greenhouse gas emissions monitoring and reporting in accordance with Directive 2003/87/EC of the European Parliament and of the Council of 2 annex VI. The electricity grids of 109 3. from fossil resources, 397 4. from renewable energy sources 7 5. Heat from the boilers to the economy Minister Daniel 264 Pavļut 2. pielikumsMinistr kabineta2013 of 25 June 2004, Regulation No 348 evaluation of energy efficiency limits and energy flow display legend: 1-consumers; 2-accumulator; 3-pot; 4 – fuel; 5 – electrical energy; 6 – additional energy; 7-the Sun collector; 8 – photovoltaic panels; 9-limit. Economy Minister Daniel Pavļut of the kabineta2013 pielikumsMinistr 3 of 25 June, Regulation No 348 system boundary representation of the primary energy consumption calculation of Limits of the primary energy factor of: (a) application-building; b – building site boundary; c – off-limits; d – distance (mains). Building area legend: S1-conditioned area; S2, S3-not the conditioned area. Energy names: 1-Photo electric elements; 2-wind generators; 3 – biomass boilers or equipment; 4-in. Economy Minister Daniel Pavļut pielikumsMinistr kabineta2013 of 4.25 June 2004, Regulation No 348 internal heat gains 1. Internal heat gains, heat flow in the part of the population and residential buildings of no PO box table 1. The day of the week 24 hours living room + kitchen (Φiek, population + Φiek, trainee)/Aapr (W/m2) of conditioned areas Other (for example, bedroom) (Φiek, Φiek, population + passenger)/Aapr (W/m2) 1. Monday-Friday 07.00-17.00 17.00-23.00 23.00 8.0 1.0 20.0 1.0-2.0 6.0 00 9.0 2.67 average 2. Saturday and Sunday 07.00-17.00 17.00-23.00 23.00 20.0 4.0 8.0 2.0-2.0 6.0 to 9.0 3.83 Average 07.00 3. Average of 24 h 2. inner heat 9.0 3.0 benefits – heat flux part of people and devices office building in table 2 no PO box The day of the week 24 hours office space (60% of the net floor area) (Φiek, Φiek, population + passenger)/Aapr (W/m2) other facilities (such as the lobby, Foyer, corridors) (40% of the net floor area) (Φiek, Φiek, population + passenger)/Aapr (W/m2) 1. Monday-Friday 07.00-17.00 17.00-23.00 23.00 20.0 8.0 2.0 1.0-2.0 1.0 00 9.50 3.92 average 2. Saturday and Sunday 07.00-17.00 17.00-23.00 23.00 2.0 1.0 2.0 1.0-2.0 1.0 2.0 1.0 00 average 3. Average of 24 h 7.4 3.1 3. Heat Flux part of residents living in buildings not table 3 no PO box The population density in the area to the Appropriate person (m2) heat flow part of the population, population/Aapr Φiek (W/m2) 1. I 1,0 15 2. 2.5 10 3 II. 5.5 5 4 III. (IV) 14 3 5. 20 2 4 v. Heat Flux part of devices in non-residential buildings 4. table no PO box The building uses the heat produced during operation of the equipment, passenger/Aapr Φiek (W/m2) the part of the average heat flow fiek from equipment, passenger/Aapr Φiek (W/m2) 1. Office 15 0.20 3 2. Training 5 1 3 0.15. Health care (the hospital's) 8 4 4 0.50. Health care (outpatient) 0.20 3 5 15. Catering 0.25 3 6 10. 3 7 10 commercial 0.25. Public meetings and events 5 0.20 1 8. Accommodation 4 2 9 0.50. Prison 0.50 2 10 4. Sports activities and measures 4 Economic Minister 0.25 1 Daniel Pavļut pielikumsMinistr 5-kabineta2013 June 25, Regulation No 348 total element transparent parts of the solar energy transmittance values and reduction factors 1. Solar energy transmittance values table 1 no PO box Type of glazing common element transparent parts of the solar energy transmittance gg 1. Single glazing 0.85 2. Double glazing 0.75 3. Double glazing with selective coating 0.67 4. Triple glazing 0.7 5. Triple glazing with two selective coating 0.5 6. Double window Translucent parts 2 0.75 solar energy transmittance values affect the cover (curtains and blinds), which significantly reduces the solar energy transmittance. Reduction factors for some obscure types listed in table 2 of this annex. Cover (curtains and blinds) impact factor must be multiplied by the total element transparent parts of the solar energy transmittance value (gg + shadow = gg × gene). 2. table no PO box Cover type cover optical qualities of the reduction factors gene with absorption transmission internal cover external cover 1. White retractable drop shades of 0.1 and 0, 050, 10, 3, 0, 0, 250, 300, 45, 100, 150,35 2. White curtains 0.1 0, 50, 70, 9, 650, 800, 0 95 0, 550, 750,95 3. Colored fabric curtains 0.3 0, 10, 30, 0, 5, 0, 420, 570 77 170, 370,57 4. Aluminum cover shield for 0.2 0.05 0.20 0.08 3. Mobile solar shading reduction factor fl, int, depending on the month and glazed surfaces orientation Period table 3 North East South West January February March 0.0 0.5 0.8 0.5 0.0 0.1 0.6 0.0 0.0 0.3 0.6 0.2 0.0 0.5 0.7 0.4 0.0 0.5 0.6 0.4 April May June July August 0.0 0.5 0.6 0.4 0.0 0.6 0.6 0.5 0.0 0.6 0.6 0.5 September October November 0.0 0.3 0.6 0.2 0.0 0.4 0.6 0.3 0.0 0.1 0.5 0.0 0.0 0.0 0.5 0.0 December heating season 0.0 0.3 0.6 0.2 Economic Minister Daniel Pavļut pielikumsMinistr of kabineta2013.6 years 25 June Regulation No 348 shading reduction coefficients of heating season 1. Shading correction factor part of the horizon effect (Fh) table 1 no PO box Horizon angle α 56 (latitudes) 57 (latitudes) 58 (latitudes) D R D R/A-Z/A-Z/A-Z R 1 D. 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0 ° 2. 10-0.93 0.92 0.99 0.92 0.91 0.99 0.92 0.91 0.98 3. 20-4.0.67 0.74 0.95 0.66 0.73 0.95 0.65 0.73 0.94 30-5.0.48 0.61 0.92 0.47 0.60 0.92 0.46 0.59 0.91 40 D – the legend: 0.39 0.55 0.89 0.38 0.54 0.88 0.37 0.54 0.88 South; R/A-West/East; Z-North 1. Horizon angle α 2. Shading correction factor part of the overhang and sheds the impact (Fp) table 2 no PO box Overhang angle α 56-57 (latitudes) 58 (latitudes) D R D R/A-Z/A-Z 1. 1.00 1.00 1.00 1.00 1.00 1.00 0 ° 2. 3. the 30 0.93 0.91 0.91 0.94 0.91 0.91 45 the 0.81 0.79 0.80 0.82 0.80 0.80 4. 60. Shading the 0.61 0.61 0.65 0.62 0.62 0.65 3 correction factor part of the protruding vertical elements (barrier) impact (Fl) table 3 no PO box The angle β of the barrier 56-58 (latitudes) D R/A Z 1. 1.00 1.00 1.00 0 ° 2. 3. the 30 0.94 0.91 0.99 45 the 0.86 0.83 0.99 4. 60. the note 0.74 0.75 0.99 Table 3 of this annex contains the values validated the South side of the barriers. For Windows with a view on the South sides both sides need to multiply two shading coefficients. For Windows, the Eastern and Western side of the barrier north side shading adjustment is required.
Figure 2. Sheds and barriers: a) vertical section overhang angle α; (b) section of the barrier) horizontal angle β. Economy Minister Daniel Pavļut 7. pielikumsMinistr kabineta2013 of 25 June 2004, Regulation No 348 dynamic parameter values no PO box The design of the building's main construction material classification * Cm (Wh/l) 1. Very lightweight glass, mineral wools is 16.7 Aapr putupolistirol 2. Lightweight wood and wooden building materials 23.1 Aapr 3. Medium, aerated concrete, the ceramic brick, dobt keramzītbeton, skaidbeton of the Aapr 34.4 4. Heavy Pilnķieģel, the reinforced concrete panel 54.2 dobt Aapr 5. Very heavy concrete, reinforced concrete, stone wall, 77.2 Aapr note. * at least 80% of the secondary containment structures. Economy Minister Daniel Pavļut in