Cabinet of Ministers Regulations No. 82 in Riga on 17 February 2004 (pr. 27. § 7) fire regulations Issued under the law of the fire protection and fire-fighting article 12 1. General questions 1. determines the fire safety requirements for natural and legal persons, to be observed regardless of the form of ownership of the object and the location of prevent and successfully deleted the fires, as well as mitigate their effects. 2. the non-profit organization public limited liability company "Latvian standards" at the recommendation of the Ministry of the Interior submitted for publication in the newspaper "journal" to "national list of the standards applicable to implementation of those rules (applicable standards).
2. Natural and legal persons obligations 2.1. Natural persons responsibilities 3. it is the responsibility of any person, to prevent the outbreak of the fire, or actions that may lead to fire. 4. The Person must know how to handle fire and evacuation, and how to use fire. 5. If fire, has the following responsibilities: 5.1 reporting on the State fire and rescue service, naming the object address, fire the provenance, the rapporteur's name and telephone number, as well as the additional information requested on the fire; 5.2. to execute fire extinguishing and rescue Manager orders; 5.3. to inform the fire extinguishing and rescue Manager for people who are or might be at risk in the area of fire, fire ūdensņemšan and access roads, the risk of explosion and fire risk object (process, stored and used and the nature of the material).
2.2. the head of the legal person and the duties of the employee 6. Legal persons driver has the following responsibilities: 6.1. ensure the laws contained in the fire safety requirements; 6.2. ensuring fire safety instructions development in accordance with the provisions of paragraph 10; 6.3. to organize employees instruction in the field of fire protection and fire safety briefing to make mark in the journal of accounting (annex 1); 6.4. make possible fire risk assessment and, based on this, develop and implement fire safety measures at the site; 6.5. to provide heating and ventilation equipment, guideline, other engineering equipment, technological and production facilities to meet fire safety requirements, as well as damage resulting from these plants; 6.6. to ensure national fire safety inspectors monitoring the fire; 6.7. to provide the object with fire-fighting equipment, fire-fighting water supply, automatic fire protection equipment, Fire Department call equipment, fire extinguishers and equipment according to the laws in the field of fire protection, as well as to maintain the equipment and human resources; 6.8. to draw up an action plan in case of fire the objects with potentially explosive environments and objects which may contain more than 50 people (excluding residential home). At least once a year under the plan to organize practice sessions, as well as to ensure implementation of the action plan in the event of fire.
7. the head of the person performing the duties of the individual in the field of fire protection may ask the responsible employee. 8. the object of the staff responsible for fire protection, individuals who develop a plan of action in case of fire and fire instructions, as well as people who perform the necessary fire safety instruction, training in the field of fire protection: 8.1. According to national fire and rescue service designed for 40-hour training program, if that person works objects which may contain more than 50 people (excluding residential home), or objects with potentially explosive environment; 8.2. According to Ministry of education and science developed a training program for licensed (no less than 160 hours) If that person working on the objects, which may contain more than 200 people (excluding residential home), or increased the risk of industrial accidents.
9. Fire safety instructions drawn up in accordance with fire regulations, technology and production equipment operating instructions, as well as the view of the buildings and structures, technological equipment and production facilities to the risk of explosion and fire. 10. Fire safety instructions shall contain the following information: 10.1 the procedures are maintained in the territory, buildings, facilities, evacuation roads and driveways at the buildings, structures and sites for fire water supply, as well as news on the fire protection of object; 10.2. fire mode, fire safety requirements for buildings and premises engineering equipment, possible risk factors, technological processes and the explosive fire risk;
10.3. use and storage of hazardous substances and materials characteristics, explosive and fire risk, as well as the use of substances and materials, storage and transportation; 10.4. the technological equipment and space control and measuring devices maximum readings and readings that the explosion may occur or be a fire; 10.5. the location and room cleaning and elektropatērētāj procedures for disconnecting after the end of the work; 10.6. procedures after the end of the work collected in combustible substances and material waste, maintained and stored in a greasy work clothes; 10.7. the places where smoking is allowed; 10.8. fire work arrangements; 10.9. the duties and conduct of employees in the event of fire: 10.9.1. fire service call; 10.9.2. technological equipment of the suspension order; 10.9.3 there. the ventilator, electrical and other engineering equipment is disconnected; 10.9.4. fire dampers, fire extinguishing systems and equipment; 10.9.5. people evacuation procedures; 10.9.6. escape of material value.
11. Fire safety instruction approved by the head of the legal person. 12. Fire safety instructions shall be amended if: 12.1. changes in technological processes, raw materials and raw materials mix; 12.2. changed or upgraded equipment affecting fire safety; 12.3. the amended law on the basis of which the designed fire safety instruction.
13. Fire safety briefing object requires all employees and persons who carry out temporary work in the production practice or training, as well as living in hotels, guest houses and nursing homes. 14. Fire safety briefing shall be made not less frequently than once a year, as well as if: 14.1. amended the provisions of the fire protection and fire safety instructions; 14.2. changes in technological processes, raw materials and raw materials mix; 14.3. change or upgraded equipment affecting fire safety; 14.4. employees violated fire safety rules or fire safety instructions.
15. in the event of a fire action plan indicates the order in which the State called 15.1: the fire and rescue service; 15.2. withdrawn people from danger areas, protects and withdrawn material values; 15.3. expects the fire and rescue service, indicating the shortest distance to the fire location and place of ūdensņemšan; 15.4. stop electricity supply (except power fire-fighting appliances); 15.5. exclude the implementation of technological equipment and utilities; 15.6. starts fire-fighting systems and appliances; 15.7. protects the fire involved people from hazardous factors of fire; 15.8. running the fire service and the object are used in fire-fighting resources and technology; 15.9. the personnel of the object of the act according to the circumstances (for example, time of day, weather conditions, time of year).
16. In the event of fire, the head of the legal person before the State fire and rescue service arrived, organized by: 16.1. people evacuation and other fire-fighting measures; 16.2. the technological equipment, the guideline and the disconnection or switching utilities to work mode, which does not contribute to the development of the fire and restrict its deletion; 16.3. emergency medical assistance or emergency (if necessary).
17. After the fire of the liquidation of a legal person the Manager assessed and remedied the causes and the circumstances that caused the fire and contributed to its spread. 18. it is the responsibility of the employee to learn fire safety instructions, appropriate training programmes in the field of fire protection in accordance with the provisions of paragraph 8, as well as to comply with the fire safety instructions and a plan of action in the event of fire.
3. Fire protection requirements in the area of object

19. the territory of the object with a fire used for safety signs according to the Latvian standard LVS 446 "Fire and civil protection-safety signs and signālkrāsojum" (hereinafter referred to as the standard EN 446). 20. the object of systematically treating the territory of combustible waste, but buildings around 10 metres wide band cleans from dry grass and harvested crop residues. 21. the land owner (possessor) take the necessary measures to avoid the territory at burning. 22. Roads and driveway at the buildings, structures and sites for fire ūdensņemšan maintain it to ensure access for fire-fighting vehicles. 23. For road, bridge, tunnel, viaduct, a railway crossing or repair, if not fire, as well as the movement of cars on the road restoration work, the operator shall immediately inform the State fire and rescue service's territorial Department. 24. the object that contains the fire places, at ūdensņemšan near or in the territory of the pass room housed the fire ūdensņemšan site placement scheme. 25. in the area of the object is izlijušo extremely flammable, highly flammable or flammable liquids immediately collected and where they spilled, sprinkle with absorbent or sand. Absorbent or sand then collected and stored in a specially arranged space. 26. it is prohibited to: 26.1. smoking production, warehouse and transport in the territory, with the exception of objects according to the arranged and marked the spot; 26.2. fire protection in spaces between buildings or structures placed combustible materials and objects or build temporary buildings or structures; 16.3. restricting the area that restricts access for fire vehicles to buildings or structures; 26.4. spill extremely flammable, highly flammable, or flammable liquids are collecting systems; 26.5. keep combustible wastes outside the specifically designated and equipped areas; 16.5. to enter vehicles (except for specially-equipped vehicles) in potentially explosive atmospheres; 16.6. to place the fuel transport vehicle closer than 12 metres from public buildings and residential homes.
27. under the bridges prohibited to raft, boat, barge, vessel and other floating devices in the parking lots.
28. under the overpass prohibited deploying a combustible material or combustible buildings and put the trucks to carry flammable cargo.
4. Fire safety requirements for the national forest service 29 defines the period of forest combustible and advertised throughout the territory of the Republic of Latvia. District and city authorities, in coordination with the national forest service, the respective administrative territory, may provide for other forest combustible period. 30. the particular circumstances of the fire district and city authorities have the right to take measures to reduce the possibility of fire in the forest. 31. Where road or rail land partition bar bordered by woods, this land partition bar owner (possessor) shall be not less than 1.5 m wide, up to minerālslān the soil clean up soil or flip bar that prevents fire from spreading (hereinafter referred to as the mineralized zone). The land owner (possessor) mineralized zone renewed each year. 32. If the forest owner (possessor) managed forest area greater than 10000 hectares, he developed the forest fire preventive measures. That plan approved by the State Forestry Department. 33. the period of forest combustible burn digging balances only allowed by State Rangers from written permission. 34. the period of forest combustible banned: 34.1. Stoke fires in forests and marshes, except specially engineered sites, preventing the fire from spreading outside these places; 21.3. leave a fire unattended. Fire extinguishing and fire the space left when it's smouldering combustion completely ended; 21.3. drop forest, marshes, or on those crossing routes in combustible or burning matches, butts and other items; 21.4. the Woods and marshes of blasting work and organize shooting lessons, except according to the installed location. 34.5. hunting and shooting sessions in the Woods and marshes to use tracking shots, deglod and wads of flammable and smolder able material; 21.5. drive a motor vehicle through the Woods and swamps beyond the road, except where it is necessary for deletion, fire assistance in case of accidents and forest management; 21.6. to operate the forest, marshes, or on forest paths and other mechanisms with a damaged gas internal combustion engine exhaust system; 21.6. without reconciliation with the Government to carry out any wood burning, which creates smoke that can mislead the observation tower of fire attendant.
35. Forest banned: 21.8. damage the forest path, track, bridges, culverts, fire observation towers, other structures and buildings, as well as security; 35.2. burn waste; 35.3. burn digging balances or bonfire closer than two metres from growing trees; 35.4. burn or bonfire, if soil peat layer is thicker than 0.5 metres, except where the burning occurs after a rain or winter period.
5. The building and space maintenance 5.1 General requirements 36. Buildings which you can stay more than 50 people (excluding residential home), develop human evacuation plans according to the requirements of standard EN 446. 37. the premises of public measures number of people must not exceed the maximum number, considering that the minimum area per person is 1.35 m2. 38. If escape routes do not meet the requirements, et seq limits the number of people who are staying at the building or space. 39. Floor evacuation routes are applied, in order not to disturb people in the evacuation. 40. the door of escape paths are easily opened from the inside without the key space and marked with relevant safety signs. 41. Escape routes represents the standard LVS 446 and other labour protection laws and regulatory requirements. 42. the Evacuation routes prohibited: 42.1. retrofit evacuation routes or change the door going, not subject to the requirements of et seq; 26.2. turnstiles incorporated, sliding, retractable doors or revolving doors, if they are not equipped with the devices for manual opening or devices that support automatic opening and lock in the open position; 26.3. piedūmojam not in the stairwells glazing the area; 26.3. to place objects, furniture and equipment, if they reduce the būvnormatīvo the width of the escape route; 26.4. Human evacuation for the outer door fitted with fasteners and bolts which cannot be opened from the inside. 26.5. installation of the warehouse and pieliekamo, as well as various materials to keep stairwells; 26.5. aizkrau with furniture, equipment and articles for escape hatches and doors on the balcony or Loggia, and the transition to the next section and exit to the external evacuation stairs.
43. Devices intended to close the door to close stairwells, hallways, lobbies, and vējtvero hall, staying working order. 44. the meeting and conference rooms, cultural and entertainment institutions Viewer halls and other public spaces of measures, with more than 200 seats, chairs and seats, 5.1.1.the rows and fastened to the floor. If the room is from 50 to 200 seats, 5.1.1.the chairs. 45. the amendment to the construction of buildings, structures or premises design and pārprofilēšan pursuant to the būvnormatīvo requirements. 46.10 or more floors of public buildings where you can stay for more than 200 people, the head of the legal person provides caught the assisting personnel with respiratory protective equipment in case of fire. 47. in the attic, the basement and the conclusion of the technical room, to prevent unauthorised access (except viendzīvokļ 's House). 48. for flame resistant obstacles not dense space with refractory for sealing fasteners, smoke-proof materials. 49. Building, finishing and insulation of combustible material in fire protection equipment damage immediately repaired. 50. With fire-resistant material treated burning equipment checked by equipment manufacturers or processing work within a specific guarantee of the performer. If no time limit is specified, the check shall be carried out at least every three years. If fire aizsargīpašīb loss, treatment with fireproof protective devices made. 51. the production plants and warehouses needed storage and use of hazardous chemicals and hazardous chemical products safety data sheets or other similar information about the chemicals or chemical products, physical and chemical

properties, hazards and possible effects on the environment and human health. This information must be sufficient to identify the substances or products concerned of possible threats to the environment, human life, health and property, and ensure the appropriate action in the event of fire or explosion. 52. with the materials, substances or chemical products, follow the instructions. Using and storing chemicals, chemical products and materials that the explosion and fire risk profile is not known, take the same measures as explosive fire and carry flammable materials, substances or products. 53. Extremely flammable, highly flammable and flammable liquids are divided up and tightly close the safety in containers that are resistant to the manufacturer's intended use and storage conditions. 54. In rooms where explosive atmospheres are automatic air analyser that warns of the explosive concentration maintained in working order and operated in accordance with the manufacturer's specifications. 55. Forbidden: 55.1. to use the elevator in case of fire for the evacuation of people; 55.2. exceed the construction or fire safety instruction specified in the size of the ugunsslodz; 55.3. cleaning use for extremely flammable, highly flammable and flammable liquids that are not specifically intended for that purpose; 55.4. leave unattended light the ovens and fireplaces, as well as electric network added to the household electrical appliances when it prohibited the operating instructions; 55.5. thaw frozen pipelines using open fire; 57.5. operating the building, premises, facilities, or after the completion of the works in the order of pārprofilēšan is not put into operation, which are not made in the construction of fire protection measures in accordance with the requirements of the fire; et seq 55.7. store cylinders, as well as extremely flammable, highly flammable and flammable liquids cellars, cokolstāvo, attic, balconies and loggia; 55.8. use attics and technical spaces in unexpected construction purposes; 34.7. after work in the workplace leave combustible waste production, extremely flammable, highly flammable and flammable liquids and slaukāmo materials used; 55.10. smoking in public and the production premises, except for specially arranged places marked in accordance with the requirements of standard EN 446.
56. The public spaces of the building spent the night people, deploy: 56.1. floor evacuation plan, which highlight the corresponding room, escape routes and exits, as well as fire-fighting and fire notification device location; 56.2. information on fire safety measures and action in the event of a fire.
5.2. Recreational, cultural and sporting institutions 57. Open fire is used only with the legal person of the driver's written permission. The head of the legal person provides the necessary measures to prevent the outbreak of the fire. 58. Scene, šņorbēniņ and attic wooden structures, as well as the combustible decorations and scene design with pretugun a safener, which represents, in drawing up the Act. 59. After the performances or the attempting to fire the curtain descends immediately. 60. Fire curtain with flexible sealing gasket to fit the stage floor. The lifting and lowering mechanism adjusted so that the curtain drop on average speed of not less than 0.2 metres per second. 61. Dūmatver management nodes maintain a working order. 62. The stage part design columns delimiting fire doors shall be provided with self-closing devices. 63. Between scenery and stage delimited structures provides at least one metre wide path along the perimeter of the stage. 64. at the limits of the stage shall be placed not more than two performances of the necessary props and stage design features. 65. If the measure, which at the same time participating in the more than 50 people (hereinafter referred to as the mass action), in facilities, the number of sites they may not exceed the number of seats provided for in the project. 66. Sofiš enclosure of fire isolated from turētājtros. To sofit from light side installed metal aizsargtīkl. 67. Evacuation of the head of the legal person supplying the staff duty with a flashlight. 68. Forbidden: 68.1. keep decorations, props and equipment not intended for locations; 68.2. spotlights and sofiš glass use combustible light filters; 68.3. rooms and balcony spectator routes performances or concerts during the place papildkrēsl.
69. in addition to the circus, the following requirements shall be met: 69.1. travelling circus tent type combustible cover treated with ugunsaizsargviel; EB 69.2. animal feed made special premises or places; 69.3. hay and straw keep purpose and according to the installation locations; 69.4. If a side room level is different, the routes be sloping (sloping) pandus. All the seats in the Hall the viewer connects lines and fixed to the floor.
70. Kinoaparatūr room: 70.1. movie locations movie playback plays out according to our kinoaparatūr rooms; 70.2. kinoaparatūr room installed in the halls of the dežūrapgaismojum Viewer control; 70.3. at all projection and observation boxes from a projector fitted side glass stopcocks and mechanically in degtnespējīg drop-down blinds (locks).
5.3. Treatment Services 71. Number of patients in the room must not exceed the number of patients prescribed regulations. 72. it is prohibited to place a bed evacuation routes. 73. Heat sterilization machine, water heaters and sterilizers for medical instruments provide adequate furnished room (site) to degtnespējīg material.
74. If the x-ray film is used in the manufacture of combustible materials, archives equipment on the top floor of the building or room, separated by fireproof walls and floors. Movies keep degtnespējīg material cupboard. 75. Dežurējošaj treatment of people with information about the number of patients in the ward and their placement.
5.4. Educational institutions 76. Educational facilities, except the laboratory shall keep extremely flammable, highly flammable and flammable liquids, as well as the use of open fire. 77. The supervising staff has information on education through the night and the number of people remaining in their placement. 78. Work with laboratory chemicals, electrical equipment and heating systems are only allowed in the presence of teachers or operators and management. 79. the laboratory work using combustible gas or extremely flammable, highly flammable and flammable liquids and which can occur during the auto-ignition of combustible or explosive substances or withdrawal, carried out ventilējamo cabinets. 80. Education and laboratory chemicals warehouse stores only aizslēdzamo cabinets. This cupboard keys located at the Faculty (analysts). Extremely flammable, highly flammable and flammable liquids are kept in special metal cabinets. 81. the training workshops each of the classes removed and oily combustible waste materials slaukāmo. Carpentry workshop in store no more than one day, the quantity of material required. 82. A teacher after class view and disconnect electrical appliances.
5.5. Hotels, office buildings and residential home 83. High rise living in a House wired manhole covers are without fault and close tightly. 84. Hotel, Office building and in a residential house in banned: 84.1. equipment of production facilities, which use explosive materials, extremely flammable, highly flammable and flammable liquids. 52.3. to use technical and technical spaces in unexpected construction purposes; installation of the combustible material. 84.3 warehouse and workshop premises is not fireproof separate from other facilities, evacuation routes and staircases; 84.4. keep on balconies and loggia-extremely flammable, highly flammable or flammable liquids. 84.5. use devices with an open fire, according to their operational rules.
5.6. the laboratories that use hazardous chemical substances

85. chemicals kept within their storage conditions and requirements laid down in these rules (annex 2). 86. Combustible construction and material table, shelving, shelving and cabinets of the ventilated work surfaces that are designed to work with extremely flammable, highly flammable, flammable liquids and substances, covered with a degtn-capable materials. 87. Work with chemicals used in degtnespējīg material table. Desk work surfaces fitted the degtnespējīg material borders. 88. the chemicals stored in the degtnespējīg material cupboard. 89. the work which may be combustible vapour or gas release, take ventilējamo cabinets. 90. The glass dishes with acids, bases or other corrosive substances carried in special packaging. 91. Gas cylinders, except work required, placed outside the building's metal cabinets with ventilation holes. 92. The oxygen cylinders and cylinders with combustible gases stored separately in special premises or under cover and protected from heat sources as well as from exposure to oils and fats. 93. it is prohibited to use the damaged ventilējamo cabinets.
5.7. the objects of trade and services trade premises 94. number of persons shall not exceed the maximum number, subject to the būvnormatīvo of the minimum area per visitor. 95. The implementation, which is expected to operate for 24 hours, provides a separate mains. 96. it is prohibited to: make elektrometināšan 96.1., gas welding, metal cutting, working with a torch, melting bitumen, as well as other works that use open flames or sparks can occur (hereinafter referred to as fire works) at a time when the premises staying visitors; 96.2. the market and store extremely flammable, highly flammable and flammable liquids in quantities can lead to explosive concentrations of the premises; 96.3. place the combustible goods or goods in containers less than 0.5 aerosol meters of heating devices; 59.9. installation of outlets and to place the goods, as well as other items go into the showroom, if you reduce the width of the escape route.
97. The open and temporary trade places: 60.3. trade line facilities, providing the width of the passageways between them, not less than two meters, and after each trade line 30 metres shall be provided not less than šķērsej, 1.4 metres; 97.2. shelters set up in groups not exceeding 500 m2 area (free area), between groups providing a distance not less than six metres; 60.5. shelter facility not less than six metres from buildings and structures.
98. Liquefied gas cylinders intended for trade and Exchange in the open squares, placed in a container or bench (bench), subject to the following conditions: 98.1. Billboard made of degtnespējīg material. The bench is well ventilated to prevent gas leakage in the event of an explosive concentration. The bench from at least three sides of open aisle, their area is at least 50% of the wall area, and at least half of them are on the lower part. Stand construction protects cylinders from direct sunlight exposure; 98.2. Billboard placed on a solid material base of degtnespējīg;
98.3. Billboard stands with the relevant fire safety signs according to the requirements of standard EN 446; 98.4. the maximum capacity of gas cylinders in the stands must not exceed 2000 litres, but the maximum volume of one cylinder-80 litres; area of three metres 98.5. radius around the stands shall be considered as potentially explosive. Electrical equipment within the zone are sprādzienaizsargāt and marked accordingly, communication, well here is protected against gas leakage communications wells; 98.6. smoking and using open fire is prohibited within a range of 10 meters around the stands. On notice of a security; 61.3. If the stand is not in operation lightning protection zone, bench provides a separate lightning protection; 98.8. no further than 15 metres from the bench placed at least two fire extinguishers and fire apron; 98.9. gas cylinders issued by specially trained staff.
99. The minimum distance from the gas cylinder stand: 99.1 to schools, kindergartens, hospitals, homes, markets, as well as other public buildings and structures where you can stay in more than 800 people – 40 meters; 99.2 to residential buildings and other public buildings and structures (except those referred to in subparagraph 98.4.1 of the rules.)-20 meters; 99.3-production and warehouse buildings and structures-10 meters; 99.4. gas cylinder to another bench-6 metres; 99.5 to automotive fuel and gas station buildings, structures and installations – 6 metres; 99.6 to sharing Street-5 meters.
100. it is prohibited to sell and store extremely flammable, highly flammable and flammable liquids are inappropriate or damaged containers (packaging). 101. Containers (packaging) that contains the extremely flammable, highly flammable and flammable liquid, place the solid. 102. Liquefied gas cylinder in place of banned trade in refilled or repaired cylinders.
6. Engineering systems and equipment 6.1. Automatic fire protection equipment operation General requirements 103. automatic fire protection equipment shall be maintained in working order and operated in accordance with the equipment manufacturer's technical documentation requirements. 104. automatic fire protection equipment and those changes correspond to the technical project and fire automation equipment construction regulatory and standards requirements, et seq. 105. Automatic fire protection equipment (or its mounting row) before the commencement of operation of the relevant Commission. About automatic fire protection equipment commissioning draws up Act (annex 3). 106. the object stores the automatic fire protection equipment technical design and automatic fire protection equipment for operating instructions. Act concerning automatic fire protection equipment commissioning, then annexed documents, equipment manufacturer technical passports, as well as automatic fire protection equipment and conformity of the appliances to the supporting documents located at the possessor or operator object. 107. Automatic fire protection equipment for the operation of the post: 107.1. automatic fire protection equipment operation responsible employees; 107.2. caught the staff 24-hour control of the equipment and the uptime (excluding objects that transmit alarms to central fire alarm control); 107.3. assisting personnel that perform equipment maintenance and repair (except when the contract has been concluded with the Organization of automatic fire protection equipment maintenance and repairs).
108. For automatic fire protection equipment operation responsible employee shall have the following responsibilities: 108.1. maintain automatic fire protection equipment in working order; 108.2. follow automatic fire protection equipment operating conditions; 108.3. ensure automatic fire-protection device design of operational documentation; 108.4. provide the supervising staff training automatic fire protection equipment operation; 108.5. control automatic fire-protection equipment maintenance and repair. 109. The automated fire protection equipment of the object or the operator shall develop the following operation and maintenance documentation: 109.1. instruction on equipment operation and protected area (the area) list; 109.2. instruction on action in the event of automatic fire protection equipment alarm comes on the outbreak of the fire or equipment damage, as well as instructions on action fixed firefighting systems during operation and after the machine function execution; automatic fire protection of 109.3. equipment maintenance and repair tracking log (annex 4); 109.4. automatic fire protection equipment in the event of exposure and damage assessment (annex 5); 109.5. automatic fire protection equipment maintenance (annex 6).
110. The supervising personnel should know: 110.1. automatic fire protection equipment technical characteristics and operational procedures; 110.2. automatic fire protection equipment uptime detection; 110.3. the protected space for names and locations; 110.4. in cases where the action of automatic fire protection equipment alarm comes on the outbreak of the fire or equipment damage, as well as the action of fixed fire-fighting installations during operation and after the machine function execution.

111. Automatic fire protection equipment maintenance and repair is performed by specially trained person with the necessary knowledge of the identity document. If the object referred to by employees work can not be carried out with the agreement of the organization. 112. With the organisations concerned, the contract concluded on the automatic fire protection equipment maintenance and repair does not release the object of liability of the staff to be responsible for this operation. 113. Automatic fire protection equipment maintenance is carried out in accordance with an approved maintenance rules. Rules of procedure-based equipment manufacturer's technical regulations and the nature of the protected object. 114. Automatic fire protection equipment maintenance and repair jobs recorded automatic fire protection equipment maintenance and repair tracking log. 115. automatic fire protection equipment in the event of exposure and damage recorded in the log (annex 5).
116. the capacity of the machine as soon as possible, but not later than 24 hours after exposure, or damage to the equipment in the opening minute. 117. If during the execution of the work required automatic fire protection equipment for full or partial shutdown, the responsible person shall ensure regular inspection of the premises and fire control of the situation. 118. Automatic fire protection equipment operation shall not exceed the specified by the manufacturer. 119. When it is not possible to provide 24-hour on-call, according to the requirements provide for automatic et seq of the fire-protection equipment alarm signal transmission to the room with the 24-hour duty personnel (central fire alarm control). 120. automatic fire protection devices in areas where they may be mechanically damage the protected with special fixed protective devices. Protective devices must not affect the automatic fire protection equipment uptime and transaction parameters. 121. Automatic fire protection equipment manual remote triggering devices deployed to illuminate and available places, protects against accidental actuation, provided with explanatory captions. 122. If repairs can affect the capacity of the automatic protection devices, the device must be protected by means of what is removed after the completion of repairs. 123. the object manager or operator to provide free access to automatic fire protection equipment of the devices to be able to make their maintenance and repair. 124. Forbidden: 124.1. make changes to the automatic fire protection equipment and protected zone, if it affects the automatic fire protection equipment uptime or the exercise of their functions; 124.2. automatic fire protection key or switch it from automatic to manual control mode the control mode, except for the maintenance or restoration of the system; to disable automatic fire protection 124.3. installations for the capture, management, control, sound, and other devices, as well as to change the mode of operation of the equipment; key lock the lift 124.4. (the elevator cab drop to the floor, from the human evacuation routes to the outside); 124.5. unlock the fire elevator fire movement operating mode; 124.6. aizkrau access to automated fire protection devices; 124.7. hang up or attached to objects at the automated fire protection devices, pipelines and cables.
6.2. Automatic fire detection and alarm equipment 125. Facilities where necessary to protect more than 10 fire detection zones, set up to capture and control panel, which signals about the fire from other alarms, as well as provide technological process, electrical or other equipment (including automatic fire protection equipment) management. 126. At automatic fire protection equipment for reception and control panel placed in the protected premises and zones. 127. Automatic fire detection and alarm equipment provides uninterrupted power supply for signālķēž and automatic control. 128. it is prohibited to: 128.1. the technical project for fire detector site to install other types of detector or operation; 128.2. materials and objects to be positioned closer than 0.6 metres of fire detectors; 128.3. place the heating device closer than one metre from the fire detector, as well as capture and Control Panel.
6.3. Fixed firefighting systems 129. Fixed automatic fire-fighting equipment, except for sprinkler installations, a remote control and manual actuation mode. Fixed firefighting systems also automatically fire detection and alarm equipment, if it is not the function of the individual machine performance. 130. The stationary fire extinguishing equipment in the pump and control room locked. At the entrance to the room is placed a statement of key location. 131. At the entrance to the stationary water (foam) fire-fighting equipment pump rooms set up highlight marked "fire-fighting pump station" at the entrances of the fixed gas fire-fighting equipment stations – "gas fire station" and warning labels for high pressure gas cylinder being in space. At the entrance to the premises where the fire equipment management node, highlight the words "fire equipment control nodes". 132. The stationary fire extinguishing equipment in the pump rooms and control rooms equipment placed common schema and mapping scheme, as well as instructions on starting the machine in the event of a fire. The control of the Cabinet provides the explanatory captions. 133. At the stationary water (foam) fire-fighting equipment management node placed explanatory inscription stating the names of the protected area the sprinkler (drencher) type and quantity, as well as the working pressure. 134. At each fixed gas fire-fighting equipment distribution device placed explanatory inscription stating the names of the protected space of the battery group numbers, and work pressure. 135. Fixed firefighting systems noslēgarmatūr stands and numbered in accordance with the connecting diagram. Noslēgarmatūr-sealed at working state if its working condition is not controlled automatically.
136. the color of fixed fire-fighting equipment appropriate to the requirements of standard EN 446. 137. At the entrance to the room in which the fire is for deletion with an automatic gas fire extinguishing installations, place the highlight "do not enter! Gas and sound signalling device. At the exit of the room places highlight "to leave the room! Gas and sound signalling device. Highlight the words and sound signalling devices, if the call to turn on the gas fire equipment. 138. At the entrance to the room, which is located in the high pressure gas cylinder, place the appropriate safety mark. 139. If space is protected by a stationary gas or powder fire equipment, the door shall be equipped with self-closing devices and compressing the piedurlīst. 140. non-automatic Fixed fire equipment checks at least once a year and shall draw up a report. 141. it is prohibited to: place the substances 141.1. materials and other objects closer than 0.9 metres of water dispensers (sprinklers and drencher), but the heating device and other devices that emit heat, closer than one metre from the sprinklers;
141.2. Add production and other equipment at the fixed fire-fighting equipment pipeline; set noslēgarmatūr to 141.3. fixed fire-fighting equipment in the pipeline, if it wasn't for the technical project.
6.4. The fixed smoke control equipment 142. Smoke control equipment casings and valves are leak-tight. Smoke valves are closed. The control of the closet (remote and manual actuation) provided with explanatory captions. 143. it is prohibited to: 143.1. deploy different installations, materials or items that interfere with the operation of the smoke valve maintenance; 143.2. connect other ventilation equipment at the smoke discharge facilities.
6.5. notification and evacuation of fire control equipment head 144. legal persons shall lay down the fire and evacuation procedures for starting up the controller and designate the employees have the right to operate the equipment. 145. The speakers and sirens sound power level is not lower than 65 dB (people-75 dB dormitory), and it should be about 10 dB higher than the other noises of people at any location possible. 146. the maximum sound power level one meter away from the speakers and sirens may not be higher than 120 dB. 147. the evacuation announcement is audible and understandable in any possible location of people. Before the announcement sends out eye-catching signal. 148. Evacuation of the broadcasting time shall not be less than people in the time needed to escape. 149. The loudspeaker is no sound regulators and permanently connected to the network without disconnecting. 150. the object, in which the aliens, the notification of fire text translates the Latvian, English and Russian. 151. the notification of a fire and evacuation controller alarm notify, in the following order: 151.1. fire alarm microphone; 151.2. previously recorded escape report; 151.3. other transmissions and notifications.
6.6. Fire water supply

152. the structures, systems, and devices that provide object fire water supply, corresponds to the technical project solutions and fire-fighting water supply construction regulatory requirements. fire et seq They maintain in working order. 153. The fire-fighting water supply system and device damage prevents the short period of time as possible. If the repair due to disconnect the external water station, which is located in the fire hydrants, or lowers the pressure tap shall so inform the State fire and rescue service. 154. Fire hydrants and ūdensņemšan sites, as well as access routes to them denoted by the signs instructions according to the requirements of standard EN 446. 155. Tap network owner checked fire hydrants not less frequently than once a year and shall be drawn up on the checks. 156. Fire ūdensņemšan place shall be so arranged that fire fighting equipment could take water at any time of year. 157. it is prohibited to place parking and motor vehicles to the fire hydrant wells or its aizkrau. 158. Artificial fire reservoirs provide technical project for the water margin. 159. If the object, except for the viendzīvokļ House is not equipped with a fire-fighting water supply and its area is located in or near the natural reservoir, the construction of driveway and water sampling sites for fire trucks. 160. The fire-fighting water supply pump rooms placed fire water pumps for the common schema and mapping scheme. 161. the fire pumps shall be inspected at least once every quarter. The results of the verification shall be recorded in the inspection log fire pumps (annex 7). 162. Elektroaizbīdn, in fire-fighting water supply system for the input, you must duplicate the manual opening device. 163. Fire pumps and elektroaizbīdņ the manual remote triggering devices deployed to reach and protect against accidental actuation as well as provided with explanatory captions. 164. the non-heated premises and structures before the cold season joining from internal fire tap networks releases water. Noslēgarmatūr, which disconnects this tap stage located in the heated space. 165. The internal fire tap tap placed in a special closet or alcove, tap and the hose attached to the barrel. 166. To the fire tap closet door indicates the sequential number, fire service emergency phone number, as well as deploy instructions signs according to the requirements of standard EN 446.
167. The fire-fighting equipment and tap check once a year. The results of the verification shall be recorded in the internal fire hydrants and water equipment testing journal (annex 8).
168. Fire-extinguishing water reserve for the use of economic or production needs.
6.7. the fire-fighting equipment, apparatus and equipment 169. object provided with fire extinguishers and equipment according to the requirements of this Regulation (annex 9). 170. Fire extinguishers meet the requirements of the applicable standards. 171. Fire extinguishers shall be installed and used according to the manufacturer's technical requirements. 172. The fire-fighting appliances kept ready places for this purpose according to the technical rules of operation. 173. Fire apparatus and equipment installed in the visible, easily accessible, and represents the standard requirements of LV in 446.
174. Fire extinguishers shall be placed not more than 1.5 metres from floor to machine handles. 175. The cold time of year not heated premises and territory placed fire apparatus, operating conditions permit. 176. fire-fighting apparatus operates, check, repair and make up according to the manufacturer's specifications and the Latvian standard LVS 332 "fire apparatus maintenance operation-ready condition". 177. Fire apparatus records and recorded the location of the fire apparatus inventory journal (annex 10). 178. Fire apparatus maintenance carried out staff with appropriate professional qualifications of maintenance points, which comply with standard EN 402 "fire apparatus in service points. General requirements ". 179. it is prohibited to use fire-179.1.: techniques, tools and fire apparatus of economic or production needs; 179.2. violating fire techniques, and fire apparatus maintenance and usage rules; 179.3. operate fire apparatus without marking or with damaged labels.
6.8. The implementation of the implementation of the nutrition 180. working order, the operation carried out in accordance with the manufacturer's technical regulations and guideline of the regulatory laws and fire safety requirements. 181. Earthing and lightning protection devices using the diet. 182. Earthing and lightning protection device checks and wiring insulation resistance measurement shall be carried out every six years, explosive or chemically aggressive environment-once a year. 183. the portable lights shall be fitted with aizsargvairog or domes. 184. Electrical equipment and electrical apparatus is cleaned from dust and debris. 185. emergency and evacuation lighting networks and devices using the diet. 186. it is prohibited to: use damaged 186.1. implementation and the homemade electric heater; 186.2. use calibrated and not self-made-mains protection fuse; 186.3. use wires and cables with damaged insulation, as well as connect it in a way that creates a dangerous transition resistance; 186.4. left unattended in the implementation of the network, if it is prohibited by the rules of operation; 186.5. explosive environment use the implementation that are not sprādzienaizsargāt and not the label; 186.6. combustible materials be placed closer than 0.5 metres of light fixtures.
6.9. Heating and water heating 187. Heating and water-heating equipment and devices (hereinafter-heating equipment and devices) maintained in working order and operated in accordance with the manufacturer's technical requirements and construction of heating devices regulatory requirements. fire et seq 188. Metal and ceramic flue (fireclay) shall be arranged and maintained in accordance with applicable standards and et seq requirements. 189. the flues and ventilation channels clean, adequately trained and skursteņslaucītāj for the record heating and ventilation devices cleaning log (annex 11). 190. the flue, dūmej, and dūmkanāl technical state inspection every three years a certified skursteņslaucītāj and draw up the Act (annex 12). 191. the Flue, which added to the gas appliances and gas installation space ventilation channels during operation checks and cleans the following periods of time: 191.1. brick flues-no less than annually; 191.2. brick flues with liners and metal flues-no less than once every two years; 191.3. ventilation channels-not less frequently than every three years.
192. Heating equipment and device checks twice a year, if the operating rules do not otherwise specified, and, if necessary, cleaned of soot. 193. Soot from chimneys, furnace and hearth for clean dūmkanāl before the start of the heating season and the heating season: 193.1. not less than once a month – ilgdedz-heating furnaces; 193.2. twice-the other heating devices.
194. In rooms where combustible dust is released, avoid surface is smooth. 195. Solid fuel heating appliances combustible material in front of the furnace floor covered with degtnespējīg material, the size of which shall not be less than 0.5 metres perpendicular to the furnace and 0.7 metres parallel to it. 196. in the attic of the building and the wall flue, which is located in the dūmkanāl, nobalsin or degtnespējīg in the shade with the light color. 197. an erased in the slag, coal and ash discharges no closer than six meters from residential buildings combustible structures specially engineered sites to prevent the fire from spreading outside of this site. 198. Fuel (e.g. coal, peat) that can pašaizdegt, stored in areas not closer than six meters from residential buildings combustible structures. 199. In rooms where mass action, firing furnace stopped two hours before the event. 200. A heating device that uses gas or liquid fuel, provide safety automation, which stops the gas or liquid fuel supplies, if the furnace flame goes out. 201. If the heating equipment shall be changed to another type (other fuel) equipment, check the flue (dūmkanāl) and the ventilation channel, determining their conformity with the new equipment. 202. it is prohibited to: 202.1. use damaged heating equipment and flues; 202.2. pārkurin the oven; 202.3. leave unattended light the heating device, if it does not allow the technical conditions of use; 202.4. place on heating systems and devices in combustible materials; 202.5. let liquid fuel or gas leakage; place the fuel and 202.6. other combustible material in front of the furnace closer than 1.2 metres;

202.7. drill use extremely flammable, highly flammable and flammable liquids, except specially for that purpose; 202.8. Stoke ovens and stoves with wood, which is more than the size of the furnace; 202.9. use vent channels in the heating installation of smoke discharge.
6.10. Ventilation and air conditioning 203. Ventilation and air conditioning equipment installed and operated according to the manufacturer's technical regulations, as well as ventilation and air conditioning equipment construction regulatory requirements. fire et seq 204. The ventilation system that is draining the combustible gases, vapours or dust, shall be fitted with protective devices that prevent foreign matter from entering the system. 205. The ventilation system devices and earthed equipment. 206. automatic fire protection devices and their actuating mechanisms from cleans dust and other debris. 207. The ventilator the room locked. 208. it is prohibited to: 208.1. explosive and fire rooms run technological equipment and technological processes, if damaged or does not operate the ventilation equipment; 208.2. the ventilator filter and ventilator indoors to store materials and objects; 208.3. explosive and fire zones operate unsuitable ventilation devices that are not appropriate for security sprādzienaizsardzīb; 208.4. clearing of the ventilation system, they burn through the pipelines.
7. Technological equipment requirements 209. Technological equipment installed and operated according to the manufacturer's technical requirements. 210. the process of Explosive technological equipment be fitted with static electricity removal, and ground installations. 211. it is prohibited to: 211.1. use defective technological equipment; 211.2. work with the equipment, if the explosion and fire hazards do not work control and measuring devices.
8. Fire protection requirements, performing the works Of Fire 212. requirements of the site and construction work progresses the answer works contractor (Builder or contractor). 213. the project manager, project coordinator of the preparation and execution of the project coordinator of the assignment shall not relieve the contractor of the works (Builder and contractor) from liability for fire safety requirements. 214. When performing the works, without interrupting the process or activity requires the appropriate compensatory measures the reaction. 215. the Site is provided with an external fire-fighting water supply. To this end, the construction may be fitted with temporary water-supply or adjust the existing ūdensgūtn. 216. the Site is provided for use with fire safety signs according to the laws and regulations on the use of safety signs at places of work and the standard LVS 446. 217. The construction site shall be provided and the passage of the fire ground vehicles. 218. Piebrauktuvj and caurbrauktuvj width shall not be less than 3.5 metres. Strupceļo will be at least 12 x 12 meters large areas or bows, which turn the fire trucks. 219. Temporary structures, building materials storage areas and warehouses located no closer than six meters from the buildings to be built and built, or to the ugunsdrošaj walls. 220. Under construction buildings or structures allowed the installation of temporary storage, administrative facilities and individual work stations, distanced them from the other rooms by fireproof partitions (with limit of fire resistance EI-60), a division of fire (with the limit of fire resistance REI-60) and the fire door (with the limit of fire resistance EI-30). 221. the Site provides staff evacuation in case of fire, provide the necessary escape routes and fire notification device. 222. the escape route, routes and exits the number, location and size determined depending on the construction sites, buildings, structures and premises, the use of the existing equipment and building materials, as well as the maximum number of employees. 223. Escape routes and exits provided with emergency lighting. 224. the Site more than 10 metres or three floors, a staircase under construction built at the stairwell of load-bearing structures. 225. If the site is not higher than 10 metres or three floors, allowed the landing using a temporary staircase. 226. A construction for external fire ladders and roof on the building site fence roof fitted immediately after the wall and roof construction. 227. the Site more than 10 metres or three floors, scaffolding is the structure of the degtnespējīg materials.
228. The structure of the scaffolding every 50 buildings or premises perimeter meters equipped with scaffolding ladder. Provide at least two stepladders. 229. the Construction of the structures provided for in the pretugun aizsargapstrād shall be carried out simultaneously with the construction of buildings or structures. 230. in order to prevent construction of the works during the construction of the degtnespējīg damage to materials allowed temporarily settled with combustible materials. 231. during the work of the vulnerable area of combustible insulation must not exceed 1000 m2. After combustible thermal decking removed and immediately put būvatkritum construction material provided. 232. the explosive, extremely flammable, highly flammable and flammable substances and materials, as well as the sprādzienb of gas cylinders will be stored and be prepared to work in separate ventilated rooms as well as specially those in individual working stations. 233. With the extremely flammable, highly flammable and flammable substances and materials of construction covers well ventilated spaces only, avoiding a potentially explosive concentration. This work space, use tools and equipment designed for work or carry flammable and explosive atmosphere. Jobs in these spaces start from a place that is farthest from the escape exits. 234. In closed rooms and containers worked with explosive, extremely flammable, highly flammable and flammable substances and chemical products, to resume work only after analysis of the air and not substance or product in explosive concentrations. 235. it is prohibited to use open fire closer than 10 meters from the place where the substance and material mixing with explosive, extremely flammable, highly flammable and flammable substances or chemical products. 236. the Site is provided with fire extinguishers and equipment in accordance with the requirements of this Regulation (annex 9). Fire apparatus and equipment locations marked with appropriate signs.
9. Fire the work 9.1. General requirements of the work or carry flammable 237. for equipment and devices maintained in working order, they are used in accordance with the manufacturer's technical requirements. 238. Ugunsbīstamo work out: 238.1. dedicated places, with the written order is determined by the head of the legal person; 238.2. temporary locations.
239. Assignments or carry flammable job temporary site (hereinafter referred to as the order) shall be issued by the head or a legal person with the written order posted workers (annex 13). 240. State the Type Designation, location, time and fire safety measures and issued to the operator. 241. In the event of an emergency you can make ugunsbīstamo work without written permission of the head of the legal person or by a written order in the seconded employee's presence. 242. in Assignment Manager or a legal person with the written order posted employee: 242.1. establish arrangements, work order and fire safety measures in the workplace izvietojamo for fire apparatus and equipment, as well as job control procedures after the end of work and breaks, but also in potentially explosive atmospheres air control procedures; 242.2. determine the artists responsible for site preparation works, the work of the fire and the control at the place of work or working breaks. These duties may be performed by one person, as well as the operator; 242.3. record direct labor workers and makes the grade for fire safety briefing.
243. Assignment shall be drawn up in duplicate. One copy is at the installer all the work at the time, the other-to the posting of the Publisher. Assignment Publisher keep it three more 24-hour fire at the end of the work. 244. the Fire work temporary space provided with fire extinguishers and equipment according to the requirements of this Regulation (annex 9). 245. If ugunsbīstamo works out of the building or structure or combustible combustible construction materials, they are protected from fire. 246. The workplace is ensured at least four hours after the end of the work of the fire. 247. the work carried out by the fire in the temporary location for the control of the workplace, the person responsible for posting the entry jobs monitoring the termination date and time, signed and handed it to the issuing assignments. 248. the location of the fire, perform exempt from combustible materials and shall be drawn up in accordance with the technical regulations for the preparation of the equipment maintenance. 249. the design of buildings and premises and engineering communications from cleans the dust or combustible materials. 250. in the ugunsbīstamo, the following shall be prohibited:

250.1. weld, cut, solder and fired with an open fire: 250.1.1. Design and products, if they are not free of combustible material coatings; 250.1.2. tanks, equipment and communications, filled with combustible substances and materials; 250.1.3. metal multi-layer structures filled with combustible the warmer; 250.2. use clothing and gloves with oil or grease, extremely flammable, highly flammable or flammable liquid stains; 250.3. place the fuel closer than 10 meters from the place of work.
9.2. the Fire work in potentially explosive atmospheres 251. legal persons approved by the head of the space, building and civil engineering works, a list of the works carried out according to the ugunsbīstamo fire of maintenance requirements for use in potentially explosive atmospheres. 252. Ugunsbīstamo work in explosive environments only, if it is not possible to make a dedicated location. 253. the limits of the potentially explosive atmosphere marked with safety signs according to the requirements of standard EN 446. 254. Explosive atmospheres ugunsbīstamo work is carried out only after an analysis of the composition of the air and the concentration of explosive have been found. 255. before welding work in silos, which were extremely flammable, highly flammable and flammable liquids or combustible gas tank disconnected from all communications, cleaned, dried, evaporated, cooling and tank air composition analysis. Ugunsbīstamo work out if the tank has been explosive concentrations. 256. the working space around the fire within 10 meters of the sewage system in pouring funnel, trays and other open aisles. 257. the Fire work in progress: 257.1. take measures to prevent the occurrence of potentially explosive atmospheres;
257.2. welding tank, they hatch and another kept open and provides air exchange with the portable ventilation equipment; the control of explosive substances 257.3. concentration. If it exceeds the allowable, work stopped immediately.
9.3. gas welding and elektrometināšan (cutting) 258. Welding work places being: 258.1. areas identified at least 10 feet away from combustible building structures and premises; 258.2. fire separated on separate premises; 258.3. fire room, separated from the other work stations, with at least 2.5 metres high continuous partitions from degtnespējīg material.
259. The welding places permanent floor shall be constructed of degtnespējīg material. 260. Ugunsbīstamo work out the staff with the required professional qualifications, certified by the document. 261. The welding spot cleans from combustible materials. 262. Gas cylinders stored and transported only with screwed-on valve protective cover. Balloons transported without jolts and bumps. 263. Storing and using gas cylinders, it protects from Sun and heat sources. 264. acetylene gas cylinders and generators shall be placed no closer than one metre from the heat source and no closer than five metres from the open fire. 265. The calcium carbide keep airtight in a dry and ventilated standartiepakojum spaces. 266. it is prohibited to: with an open fire, 266.1. or nokarsēt objects of the frozen thawed acetylene generators, piping, valves, regulator and other welding equipment details; 266.2. allow oxygen cylinder, reducer and other gas welding and machine to machine components in contact with oils, greasy clothes and rinse the material; 266.3. calcium carbide barrel opening to use tools that can create a spark after impact; elektrometināšan use of 266.4. atpakaļvad internal railroad tracks, Earth networks as well as building communication and technological equipment for metal structures.
9.4. Bitumen fusion 267. Pots, bitumen or resin melting using open fire, placed in special areas not closer than 10 meters from degtnespējīg, no closer than 15 metres from hard combustible and not less than 20 metres from combustible buildings, structures, new construction and building materials. 268. the boiler filled with mastic of bitumen, or three-fourths of the amount of the total volume and covered with a fitting lid of the degtnespējīg material. 269. Gas cylinders placed 10 metres away from the cauldron, which want to use liquefied gas heating. 270. it is prohibited to: leave light 270.1. boilers without supervision; 270.2. set the pots on a combustible roof coverings.
9.5. Work with extremely flammable, highly flammable and flammable liquids 271. Mixtures of extremely flammable, highly flammable and flammable liquids shall be prepared in separate premises or a stand-alone, ventilated places of work. 272. Work equipment and tools used must not be to strike a spark. 273. The floor spaces, which prepares the varnishes and paints, as well as color, wash and defatted products are degtnespējīg and dzirksteļdroš. 274. it is prohibited to dye, wash and carried the details, as well as to cook liquid mixtures, if not working ventilation system. 275. Painting cabinets, and suction booths ventilation systems may not be used without the combustible particles in paint and varnish effective detection devices. 276. Painting the camera every day clean of combustible material in the sediment. The work shall be carried out, if the running of ventilation equipment, and uses tools that are not liable to spark. 277. the Lake Spilled, paint and solvent immediately collect and return the site for extremely flammable, highly flammable and combustible liquid storage. 278. Mixture with extremely flammable, highly flammable and flammable liquids delivered in the workplace ready to, in particular the safety and leak free containers. 279. Painting Chamber varnishes and paints supply and pipeline movements automatically stops when the ventilator stops working. 280. the camera design painting, sprinklers, other technological equipment, ventilation air wires and piping earthed. 281. The bath, which carried the products, wash or paint with the immersion method using a mixture with extremely flammable, highly flammable or flammable liquids, take a break covered with the lid. 282. Drying Chamber degtnespējīg used for insulation materials. 283. The drying chamber is equipped with automatic drying process control and adjustment devices. 284. If nokrāsoto technology or products, it is not possible to gauge the drying chamber or dry the cabinets, it is dried in the station, equipped with ventilation to prevent explosive concentration.
10. requirements for mass events fire mass 285. in its reply the measures the organizer or his authorised person. 286. the mass action in the open fire is used only by the organizer or his authorized person's written permission, if measures are taken to prevent the outbreak of the fire. 287. the temporary housing needs of mass measure builds from hard combustible or degtnespējīg of building structures and materials. 288. If the mass action using special effects and equipment shall comply with the technical rules of operation of the equipment in certain fire safety requirements. 289. the children and young people in mass events do designate a responsible person who is instructed on fire and action in the event of a fire. 290. the number of visitors to the mass action must not exceed the maximum, taking into account the statutory area per person. 291. If mass action using pyrotechnic articles, pyrotechnic articles comply with the movement of the laws governing the fire safety requirements. 292. Holiday tree event during the prohibited place the tree escape routes and use Christmas tree iluminācij the stearin (wax) candles or flashcards implementation. 293. Mass measures prohibited to hold a room with barred Windows.
11. Warehouse operational requirements 11.1. Materials and articles warehouse

294. The materials and articles warehouse stores, taking into account their physical and chemical characteristics (annex 2) and fire extinguishing agent uniformity principle. 295. If combustible materials combustible materials or degtnespējīg package stored in warehouse space in the basement or cokolstāv, provide for the discharge of smoke. 296. the premises of the warehouse to warehouse the doorway to leave the column width of the passageway, but not less than one metre. 297. at the end of the work with the common electrical disconnect switch in the warehouse. Warehouse equipment operating in the 24-hour mode, provides a separate network from the input to the consumer. 298. Hazardous Chemical storage locations marked with a safety signs according to the requirements of the standard EN 446 and inscriptions placed by name. 299. Chemical substances which, in contact with the air, water, chemicals or other combustible materials, pašaizdegt, can cause burning or form explosive mixtures, kept in separate fire buildings or buildings with fire resistant partitions. 300. In rooms that keep chemicals that in the event of fire temperature may melt, these substances released into the restrictive construction. 301. the chemicals that should not be exposed to sunlight exposure, prohibited to store open squares. 302. the acid or alkali warehouse equipped with neutralizing substances in such quantities as to ensure crash spilled acid or alkali neutralization. 303. Ammonium nitrate stored in a special storage bins located at the exterior of the building and separated from the common warehouse with fire resistant bulkheads. The premises must be dry, and there must not be other material remains. 304. Ammonium nitrate is prohibited to keep warehouses built from combustible materials, as well as constructing a wooden bulkhead or wooden floors. 305. the storage of materials and products in containers in open space, every 100 meters container line, as well as between the heavyweight cargo container lines create spaces, the reaction to not less than five metres. After each pair of rows of containers creates two metres wide space across the region year-round. 306. The warehouse premises prohibited: 306.1. set local heating devices; 306.2. keep materials to the warehouse ramps; 306.3. store and elektrokrāvēj trucks.
11.2. Extremely flammable, highly flammable and flammable liquid storage 307. In open areas that store extremely flammable, highly flammable and flammable liquids, bounded by Dyke or degtnespējīg material. Norobežotājvaļņ and walls must be without defects. 308. Reservoir parks and containers filled with liquid storage areas, cleaning up spilled liquids and combustible waste collected and immediately delivered a specially equipped places. 309. the area inside the walls horizontally and noplan harvested dry grass. 310. Reservoir breathing valves and fire norobežojošo barriers maintained in working order. 311. Looking at the reservoir, taking liquid samples by measuring the level of liquids in open barrels and performing other tasks, use the devices and tools after the impact can not cause sparks. 312. the reservoir repair them before the release of the fluid, disconnect the conduits, all hatches open, clean, wash basins and evaporate, as well as an analysis of the air to make sure reservoirs are not explosive concentrations. 313. the containers of oil filled warehouses between the barrels makes gaskets that they cannot be made to one another. The barrel is placed with the Stoppers on top. 314. the storage barrels with extremely flammable, highly flammable and flammable liquid bluff stacked two layers two barrel diameter width. The distance between the waves of one metre, the main aisle width – 1.8 meters. 315. the forbidden package to the warehouse, extremely flammable, highly flammable and flammable liquids and store packing materials and containers. 316. the oil is heated with steam, hot water, air, heated sand or special electrical equipment. Maximum fluid warm-up temperature should be about 10 ° C lower than the temperature of the fluid in the outbreak. Oil with steam or elektrosildītāj heated only when the liquid layer above the heater elements (tubes) is not less than 0.5 metres. 317. the clothing is of a material that does not accumulate static power, footwear must be clad with nails or that can cause sparks. 318. A shelter built from degtnespējīg materials. 319. Tanks with extremely flammable, highly flammable and flammable liquids must not be crowded. Thunder Storm and stopped filling spilling. 320. to cast or filled rail tankers, and drag the piestumj without jerks and jolts. 321. rail and filling of tanks spilling in the territory are not permitted during the brake with the blocks, which can create a spark. 322. the road tanker spilling and filling seats shall be fitted with a tank shell grounding devices. 323. Explosive atmospheres used in portable electrical equipment sprādziendroš and communication features. 324. At the train set estakād "diesel entering prohibited '. 325. it is prohibited to: to enter the warehouse 325.1. (explosive atmospheres) the motor vehicles with winter tires with studs, and motor vehicles, which do not have a special spark suppressor; use open 325.2. fire, cold, thickened, hardened oil, slēgarmatūr and heating of pipelines; 325.3. place norobežotājvaļņ inside materials and equipment; 325.4. leave open reservoir, spilling well here and the tray.
11.3. Textile 326. a place to store the storage area identified fibre plants are fenced in. 327. In open areas shall be kept in stacked fibre plants, designations, Rick or under shelters. 328. the maximum permissible range designations and Rick area must not exceed 320 m2, and the height of 10 meters. 329. sheds, fibre plants, designations and Rick is in the distance from buildings and structures, where the construction of buildings and premises is: degtnespējīg materials from 329.1. – 12 meters; 329.2. combustible materials from hard-to-15 metres; 329.3. from combustible materials to 18 meters.
330. In an open area between the ridges, designations and Rick for 15 metres wide spaces. 331. in open areas or fibre plants beneath shelters covered with a coating of hard combustible material. 332. During textile with motor vehicles, it is covered with a coating of hard combustible material. 333. Motor vehicles with internal combustion engines used for the transport of fibre plants, provided with spark-suppressor. 334. The cotton warehouses: 334.1. maximum cotton bale stack area must not exceed 22 x 11 metres; 334.2. distance from bales stacked up electric luminaires must not be less than one metre; 334.3. the distance between the ridges, as well as from the stack to a wall shall be not less than 0.7 metres; If space width 334.4. greater than 15 metres in length, two meters wide aisle throughout the length of the room.
11.4. Coal and peat warehouse 335. Location of stored coal and peat, cleared of combustible waste and plant remains, the bottom noplan and nobliet. 336. The coal and peat stack may not be placed over a heat source (steam and hot water pipelines, warm air channel). 337. Different types of coal, gabalkūdr, and frēzkūdr drop in separate stacked. 338. the coal Bluff, implemented stacking stacked technology conditions, prevent foreign matter loading combustible range. 339. The coal or peat stacked controls the temperature. When the temperature has reached 60 ° C, warm material removed and placed separately. 340. Aizdeguš or hot coal coal stacked delete with the water is prohibited. Aizdeguš carbon removes with water just after removing it from the stack. After you reset the load back prohibited ranges.
11.5. Combustible Gas and gas cylinder warehouse 341. Acting with empty gas cylinders combustible, follow the same precautions as when working on full cylinders. 342. In rooms where combustible gas may leak, take measures to avoid a potentially explosive mixture formation. 343. Stationary compressor station emergency ventilator distance starting button placed at the entrance of the compressor room. 344. The warehouse that stored in cylinders with combustible gases, heated by water, steam or air low pressure heating devices. 345. Storage cylinders stacked, their height shall not exceed 1.5 meters. On all cylinders mounted valve protective cover that turned to one side. Between cylinders inserted into the dampening material gaskets. 346. a 10-metre radius around the warehouse that stored in cylinders with combustible gases, forbidden to place the combustible material and the use of open fire. 347. with the balloon, filled with combustible gas, stored in a vertical position. 348. it is prohibited to:

348.1. storage cylinders with combustible gases and cylinders with oxidizing gases; 348.2. storing oxygen cylinders, to allow fitting in contact with oils and oily materials; 348.3. lifting his oxygen cylinders by hand, grabbed it behind the valve; 348.4. warehouse where stored in cylinders with combustible gases, employees wear clothing from materials that accumulate static electricity, and shoes with nails and clad, which can cause sparks; 348.5. repair and refilled gas cylinders, and perform other operations.
12. Transport cars in the parking lot of 12.1, garages and maintenance space for cars with 349. provide fire extinguishers according to the requirements of this Regulation (annex 9). 350. The parking lot shall be provided with towing rope or rod. 351. the maintenance room, with more than 10 service stations, or more than 25 car parking spaces, shall provide at least two goals. 352. Car parking spaces and open areas must not be placed items and equipment that could interfere with the car evacuation in the event of a fire. 353. at the end of the work premises, repair and inspection pits eļļaino of slaukāmo removed materials collected in the izlijušo extremely flammable, highly flammable and flammable liquids. 354. Car parking spaces and maintenance sites banned: 354.1. take blacksmith work, heat treatment, welding, painting and wood processing, as well as to wash parts with flammable liquids; 354.2. increase provided for in the regulations, the number of the parking lot, change the placement order of cars, reduce distances between cars, and between cars and building elements; 354.3. place the cars with fuel tanks and open cars, which noted the fuel or oil leakage; keep fuel 354.4. with the exception of fuel tanks of cars and trucks in gas balloons mounted; 354.5. dispense automotive fuel tanks; keep fuel containers 354.6.; use open 354.7. fire illuminate and the heating of the engine; 354.8. leave a car at the end of oily slaukāmo materials and clothing.
355. The individual car transport small garage repair and maintenance carried out on the territory of the izbūvēto garage in special areas. The used fuel and lubrication materials, filter and rinse the material to set up a special collection of metal tanks. Spilled fuel and oil, sprinkle with absorbent or sand, then collect the tightly sealed containers and stored in a specially arranged space. 356. the prohibited Individual car garage: 356.1. place motor cars with a fuel leak or damaged electrical equipment; 356.2. store more than 40 litres of petrol and more than 20 litres of oil. Gasoline and oil stored in tightly sealed containers and safety; 356.3. color car, transfer fuel tank car wash parts with extremely flammable, highly flammable and flammable liquids; 356.4. use open fire car engine heating and repairs; 356.5. the installation of the local heating devices that use an open fire; 356.6. used oil into drains or garage.
12.2. The fuel and gas filling stations in the territory and 357. Station buildings is prohibited to smoke. About post warning signs and inscriptions. 358. Fuel tanks pouring and measuring pipe and manhole covers are closed. 359. Filling up the fuel tank of the vehicle, the engine must be switched off. Fuel can also apply special containers provided for this purpose. Containers should be tightly sealed, unbreakable material that does not accumulate static electricity. 360. it is prohibited to station surface module type reservoir filling time, dispense vehicular fuel from pildn. 361. During Maintenance stops all with liquid fuel and gas and filling operations and related equipment, the operation, except for the compressor pumps and fans that must run continuously. 362. If the area of the work by the open fire, stop filling, discharge and loading operations and placed the signs prohibiting entry. 363. the reservoir clean and repair only after a in the reservoir volume of air and gas analysis of samples to make sure reservoirs are not explosive concentrations.
12.3. The alkaline and acid battery charging 364. Battery charging specially equipped room. 365. The battery charging area and charge the battery storage space for ventilation equipment running continuously. 366. If the room stops functioning ventilation, automatically stops the charging power. 367. Battery charging room ventilation equipment prohibited to add to the total ventilation system. 368. The battery charging area prohibited to repair batteries and other devices, as well as to keep the total alkali and acid batteries.
12.4. rail transport 369. Level crossings outside railway equipment switch blades and krusteņ borders. 370. the placing of dīzeļlokomotīv, motorvilcēj and diesel powered in the parking lot, to do the repairs, diesel and oil poured tanks outside the special shops, except where it is not intended for maintenance. 371. The diesel and the car remontuzņēmum on the premises of the forbidden: place the repair of 371.1. parking in tanks with extremely flammable, highly flammable and flammable liquids; apply 371.2. dīzeļlokomotīv fuel and lubricants will be outside of the technological process for places; 371.3. remove old paint from coachwork with roasting method; 371.4. dīzeļlokomotīv and wagons to enter with the heating equipment.
372. rail band harvested land partition krital (dead trees), the digging balances, old sleepers and other combustible material and waste.
373. The land around a wooden core, feeder mast pole, power and communication line of ridges within a radius of one meter apart or threw up. 374. If the period between the two rail stations or stations temporarily stored in the sleepers and impregnated beams, scooping them stacked. Low low ridges and three metres from cleans around them, wood and other combustible materials, apart or threw up. 375. If sleeper and stacked beams stored in long, parallel to the bluff rail 30 feet away from buildings and structures. The distance from the air power lines may not be less than half the height of the overhead electric power lines. 376. in each range in dense Cliff more than 100 sleepers. Beside stacked four ranges form a group. The distance between the ridges must be not less than one metre, but between groups of stacked-less than 10 metres. 377. the hay and straw, as well as a pile of fagots not Kraut closer than 50 meters from railway bridges, railroad structures and train the permanent motion paths, as well as power and communication lines. 378. the Crossing building, pumping stations and other buildings from the coniferous forests and crops of the parties delimit with ditches or mineralized bars that are not less than 1.5 metres. 379. The railway station of coniferous forests and cereal fields delimited with at least 1.5 metre wide mineralized bar. Peat bog railway stations by the 1.5 metres wide ditch. 380. the wagons, which furnished the garage, Office, kitchen or hewn or similar needs, allowed mūrē to metal frame contains, beside the wagon floor stable attached brick oven (stove). 381. the wagons containing people, prohibited to carry extremely flammable, highly flammable and flammable liquids, regardless of their quantity and bulk. 382. it is prohibited to store and carry extremely flammable, highly flammable and flammable liquids in noliktavvagono segto. 383. it is prohibited to throw hot slag, coal, ash and other combustible items of locomotives, wagons and railcars as well as operating the dīzeļlokomotīv without sparks suppressor.
12.5.384. Vessels shipping remontuzņēmum the leader board during the repairs provided: 384.1. to make sure the ship moored at a marina and fire vehicles proposed driveways (depends on the length of the ship and the dock design features) should use; ship to be 384.2. ground with ground equipment and the berth to the electrical fire pumps would be autonomous electrical connection; 384.3. to be able to take water from the existing tap external fire (fire hoses to be on board, one for him and the ship's poop in the area).
13. Wood processing and timber storage

Shop 385. technological equipment, heating appliances and electrical equipment from every shift released wood dust, shavings and other combustible materials. Constructions and electrical light fixtures to cleanse once a month. 386. Woodworking machine shall be fitted with mechanical shavings and dust suction systems. Prohibited from working with the ventilation and pneimotransport. 387. the dust collecting Chamber and cyclones there closed and production waste collected in time. Cyclones should not overburden and area piegruž by industry. 388. In operating with oil-filled equipment, monitor that the oil does not leak out and not soaked wooden construction. 389. Carpenters glue is heated by steam or electrical equipment with water heated in the interlayer. Glue, which is made up of synthetic resin or easily combustible solvents, store in a fireproof warehouses or metal boxes. 390. Each wood chisel for maximum permissible loading rate and temperature mode. Temperature of drying Chambers with temperature adjuster the diet. 391. Timber dryers drying products with continuous progress towards the heating system automatically unlocks when stopping the conveyor, or it shall be equipped with an alarm that warns of the conveyor stopping. 392. the wood storage areas and warehouses, Timber Ridge stacked under the previously designed technological cards. 393. the location of lumber or logs set, cleared of combustible waste. 394. The access and driveway, as well as the Timber Ridge fire maintains a free space between them. 395. in hot, sunny and windy during the territory between the ridges and around them every day watering with water.
14. Peat mining objects 396. peat extraction fields, motor vehicles and peat mining technical features with internal combustion engines be equipped with spark-suppressor. 397. Each technical feature provided with fire extinguishers and bucket with five meters long rope may fire. 398. Peat extraction sites equipped with fire-fighting techniques and equipment minimum requirements (annex 14). 399. Peat extraction site divided compartments with one metre wide ditches, which depth is 0.5 metres below ground water level, but not shallow about 1.5 metres. 400. Peat extraction site digging and harvesting krital. 401. Wood and other combustible residues of forest felling period burn according to installation places specially designated employee supervision and only in rainy weather. 402. Smoking shall be provided at the place of the channels with water or water reservoirs. 403. Peat extraction and storage locations in accordance with the rules of procedure of the process organized by peat stacked temperature control. Finding the peat temperature ranges increase in dangerous, take measures to prevent the outbreak of the fire.
15. the agricultural items 15.1 grain warehouse and grain dryers grain dryers from 404. grain storehouses separated by fireproof walls. 405. grain dryers, grain warehouses and other premises where possible dust formation, used electrical appliances with the sprādzienaizsargāt markings. 406. the electrical actuation and protection devices and touch movable machines and mechanism for connection to the grain warehouse attached to the walls or degtnespējīg degtnespējīg to support standalone 2.5 meters from the walls, if the warehouse building constructed of combustible constructions. 407. grain warehouses banned: 407.1. keep combustible material and various equipment; 407.2. run grain-cleaning equipment and other equipment with internal combustion engines; 407.3. let the conveyor belt friction against its construction.
408. The grain is running, the grain for the temperature control of the technological instructions within the time and in order. 409. The mines and the type of forged drying for shutter camera filled with grains so that the drying time over drying amended or blinds the grain layer thickness of at least 0.4 m. 410. where grain dryers technological mode is not automatically regulated, forged during the work of one employee a permanent building and supervision of forged technological rules. 411. The grain elevators and feed mills: 411.1 company in the area. prohibited open way to store waste from cereals and corn husk; 411.2. from where rail transport and cars unloaded flour and bran, raw materials, installed dust suction device to prevent dust from spreading; 411.3. premises of equipment possible dust release, not be raised embossed design (except for the required technology), so they are the accumulated dust; 411.4. cereals processing rooms and combined fodder enterprise space dust from paint in different color shades; 411.5. tanks and bunkers and lūciņ of the gravity of the hatch lines, wires and air aspiration systems constantly is in the locked position.
15.2. The harvest, feed preparation and storage of cereals harvest 412. works and preparation of feed motor used agricultural vehicle engine exhaust pipes shall be fitted with a suppressor and Sparks to the engine manifold and exhaust pipe gasket should not screwed flanges tears and other damage. 413. Bīter, compactors, straw, straw conveyor collector and other harvesting machinery rotating parts and Assembly shaft from the time straw weight and protect the equipment, which prevents the winding. 414. Between individual straw or Hay Stacks, awnings or designations for 20 metres wide spaces. 415. the distance of the designations, shelters and stacked up: air power 415.1. lines is equal to half the height of the line support; 415.2. buildings and premises in 30 meters; 415.3. roads is 5 meters; 415.4. coniferous arrays is 30 meters; 415.5. deciduous arrays are 25 meters.
416. Enclosed feed yards of total power switch mounted on the outside wall of the degtnespējīg, but if the walls are combustible, – to support savrupstāvoš 2.5 meters from the wall. 417. fodder drying fans placed outside the warehouse one meter away from buildings (structures) degtnespējīg walls and 2.5 meters of combustible of norobežotājkonstrukcij. Air wires are made of degtnespējīg materials. 418. Fan installation locations around freely, the fan air suction openings protected by a metal screen. 419. Fan operation of electrical apparatus mounted on degtnespējīg or hard combustible constructions sites, from which it is possible to observe the process of starting up the fan. 420. If dry feed (sheltered) designations, the fan is set up by 2.5 meters from designations (shelters).
15.3. The livestock items 421. doors and gates through which intended to evacuate animals shall open outwards in the direction of escape, without thresholds, steps and pavārt. 422. doors and gates be kept free and easily deployable. 423. suckling pig, Chickens, cattle and sheep as well as calving yards allowed to use local heating system. 424. Storing the feed barn attic around flues premises (on the perimeter) one meter distance barrier shall be provided. 425. Power Distribution cabinets with fuses installed in vējtvero or at the exterior of the premises of livestock farming, built from degtnespējīg materials. 426. The internal combustion engine with vacuum pumps and electric power generators, cooking or sautēšan feed fuel equipment, water heaters and other flammable equipment installed in premises separated from livestock, poultry and zvērkopīb rooms with fire walls. These spaces shall be provided with an exit directly to the outside. 427. The internal combustion engine's exhaust pipe shall be fitted with spark-suppressor. If the exhaust pipe passes through the combustible structures, built around the pipe of fire of 0.25 metres wide apmūrējum. 428. the premises collect used vacuum pumps oil and fuel oil in the engine lubrication pump and stored in tightly sealed metal containers. 429. In operating local heating electrical appliances, livestock yards, the following requirements shall be met: 429.1. distance from elektrosildītāj to bedding and combustible objects vertically is 0.8 meters, horizontally-0.25 metres;
429.2. heating element shall be installed on the base of degtnespējīg; 429.3. not allowed to use elektrosildītāj with a transparent electric heating elements; 429.4. each elektrosildītāj shall be provided to the off switch; 429.5. breastfeeding elektrosildītāj grid, with common switch off the electrical switchboard, as well as ensure the mains protection against overload and short circuit.
430. Premises for the livestock and poultry and feed storage, banned: the workshop equipment, 430.1. warehousing, road, tractor and machinery parking, as well as to take any jobs that are not related to room service; 430.2. enter with tractors, cars and agricultural machinery, if the exhaust pipes are not spark-suppressor.
431. Livestock housing from the fodder storage room separated by fireproof walls and fire door.
16. Closing questions

432. If building, building and equipment designed and built in accordance with the regulations laid down in the fire safety requirements that were in effect when the buildings, structures and equipment put into operation in these regulations the requirements do not apply, unless the buildings, structures and equipment poses an unacceptable risk to humans and material values. 433. lost in the void of the Cabinet of Ministers of 30 December 1997, Regulation No 440 "fire protection regulations" (Latvian journal, 1998, 1./2.nr.; 1999, 75/78.nr.).
Prime Minister e. Repše Interior Minister m. Swan Editorial Note: regulations shall enter into force by February 21, 2004.

2. the annex to Cabinet of Ministers of 17 February 2004, regulations No 82 chemicals and storage of materials no PO box
Group and subgroup of chemicals and materials group and subgroup, which must not be stored together, storage conditions and safeguards 1 2 3 4 5 6 1.
Explosives Dinitrophenol (dry or wet in less than 15%), kolloksilīn, metilnitrāt, nitromethane, nitroglycerin, trinitrorezorcīn (STYPHNIC ACID), trinitrofenol (picric acid), etc.
2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
To comply with the provisions of the explosives storage 2.
Compressed, liquefied and dissolved under pressure gases: 2.1.
the gas that does not burst into flame and not poisonous-gas and degtnespējīg of inert gas nitrogen, argon, bromtrifluormetān (HCFCs), helium, krypton, xenon, neon, rare gases, sulfur hexafluoride, trifluormetān, carbon dioxide, carbon tetrafluorīd, hlortrifluormetān, etc.
1., 2.2., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins or isolated shelters under the open sky balloons with compressed and liquefied gas must be protected from sources of heat and sun exposure, 2.2.
poisonous gas sulphuric anhydride boron, chloride, boron trifluoride, bromomethane, bromūdeņrad (anhydrous), hydrogen chloride (anhydrous), hydrogen fluoride (anhydrous), heksafluorpropilēn, nitrogen dioxide, tetrafluorsilīcij, nitrozilhlorīd, nitrogen monoxide, phosgene, chlorine, etc.
1., 2.1., 2.3., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins with isolated natural ventilation (single air exchanges per hour) crash (astoņkārtēj air exchanges per hour), not heated rooms 2.3.
flammable and explosive gas acetylene, butane, butylene, blaugāz, hydrogen, difluoretān, difluormonohloretān, divinil, methane, methyl mercaptan, chlorination, ethylene oxide, such as propane, ethane, ethylene, trichloroethane, etilhlorīd, dimethyl ether, metiletilēter, etc.
1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins or isolated shelters under the open sky 2.4.
flammable toxic gases ammonia, anhydrous, stabilized boretān, hydrogen cyanide, cyanogen, dimetilamīn, metilamīn, carbon monoxide, hydrogen sulphide, trifluorhloretilēn, ethylene, etilamīn, etc.
1., 2.2., 2.3., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins with isolated natural ventilation (single air exchanges per hour) 3.
Extremely flammable, highly flammable, flammable liquids: 3.1.
extremely flammable liquids Amilēn, alilhlorīd, acetaldehyde, petrol, divinilēter, diethyl ether, izopentān, izopropilacetilēn, isopropylamine, oil, pentane, petroleum, etc.
1., 2.1., 2.2., 2.3., 2.4., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. Between the shelves with flammable liquids one meter apart. 3.1., 3.2 and 3.3 substances be kept in separate heated space Not on the shelves, protection against heat sources, sprādziendroš the electrical equipment 3.2.
flammable liquid acetone, Acetal, acrylic acid nitrile, amilhlorīd, butilaldehīd, benzene, cyclohexane, diethanolamine, dichloroethane, dioxane, rubber glue, hexane, heptane, bakelite lacquer, varnish, bitumlak eļļassveķ, methyl ethyl ketone, metilhlorformiāt, not oheksān, pyridine, ethyl alcohol, isopropyl alcohol, naphtha, propyl, methacrylates, tetrahydrofuran, triethylamine, etc. 
– “ –
– “ –
– “ –
3.3.
flammable liquids, Amilacetāt, acetylacetone, anizol acetate, butilmetakrilāt, dimetilaminoetanol, dimethyl sulphate, Dean, dimetilformaldehīd, bitumenlak, spirit Lake, the coal varnish, xylene, formic acid, acetic acid, butyl, izobutilspirt, heptilspirt, nonane, kerosene, pikolīnstirol, polishes, tetraetoksisilān, turpentine, furfural, chlorobenzene, hlortoluol, pernic, oksol, cikloheksanol, shellac, etc.
– “ –
– “ –
– “ –
4.
Highly flammable substances and materials during storage and transport may easily catch fire: 4.1.
solid substances and šķiedrmateriāl that can easily catch fire external circumstances (Sparks, flames, friction), and burn: 4.1.1.
solid substances Acridine, heksametilēnetramīn, dimetildioksīm, kaprolaktām, Silicon amorphous powder, synthetic camphor, magnesium granules, naphthalene, polyvinyl alcohol, foam polystyrene (PSB), suspensions of polystyrene, catechol, sulfur powder, a piece of sulphur, titanium metal powder, red phosphorus, celluloid, nitrocellulose, matches, etc. the etrol
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.2, 4.3, 5.1, 5.2, 6, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. 4.1.1 and 4.1.2 substances be kept in separate shelves for pallets 4.1.2.
šķiedrmateriāl indicator paper, paper filters, cellulose, viscose fibres, synthetic fibres, tow, cotton, wool, jute, etc.
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.2, 4.3, 5.1, 5.2, 6.1, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
– “ –

4.2.
substances and materials pašaizdeg and under normal storage and transport conditions can heat up and spontaneously combustible: 4.2.1.
Organometallic compounds Dimetilmagnij, dimetilcink, dietilmagnij, dietilcink, metilmagnijbromīd, magnijdifenil, magnesium chloride, metilalumīnij metilalumīnij seskvibromīd of the seskvihlorīd, tributilalumīnij, triizobutilalumīnij,, trimethylaluminium, triethylaluminium, dietilalumīnij chloride, etilalumīnij dichloride, etc.
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2.2, 4.2.3, 4.2.4., 4.2.5., 4.3, 5.1, 5.2, 6.1, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse 4.2.2.
metals metallic zirconium powder or dry sponges, metallic zirconium wire or sheet form, zirconium in the form of waste, sponge iron, nickel catalyst, etc.
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1, 4.2.1, 4.2.4, 4.2.5., 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. 4.2.2 and 4.2.3. substances be kept in separate shelves 4.2.3.
pyrophoric substances Aluminum powder, powder, calcium barium, caesium, cerium powder, barium alloys, pyrophoric alloy, etc.
– “ –
– “ –

4.2.4.
metal sulphide compounds of Sērūdeņražskāb salts, potassium ditionpaskāb, ditionpaskāb ditionīt 1 the calcium etc.., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1, 4.2.1, 4.2.2, 4.2.3, 4.3., 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. 4.2.4 and 4.2.5. substances be kept in separate shelves 4.2.5.
organic material Sulfoogl, animal or mineral origin carbon of plant origin carbon soot, lamp, furnace soot, acetylene soot, etc. 
– “ –
– “ –

4.3.
substances which emit flammable gases, are subjected to the water: 4.3.1.
alkaline earth metal in the alkali, (non-pyrophoric) lithium, sodium, Potassium, rubidium, caesium, calcium, barium, strontium, alkali and alkaline earth metal alloys 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3, 4.1, 4.2, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. 4.3.1, 4.3.2, 4.3.3., 4.3.4, 4.3.5, 4.3.6. and 4.3.7. substances be kept in separate rooms where shelves in stores 4.3 substances, may enter the precipitation and groundwater. Forbidden to lay water pipes, water or steam heating and sewerage. Prohibited from heating and delete with water. For each substance to be isolated from these and other groups. Ammonium nitrate and salt is in Bertolt special storage precautions 4.3.2.
metal hydride, aluminium, potassium, lithium, calcium, magnesium, sodium, rubīdij, caesium hydride, etc – "–" – 4.3.3.
metal phosphide of potassium, calcium, magnesium, sodium, strontium phosphide of Tin, etc. – "–" – 4.3.4.
Metal Carbide, calcium carbide, aluminium, etc. – "–" – 4.3.5.
metal silicīd,

Aluminum, calcium, lithium, Ferro, ferromanganese, etc. – silicīd "– –"-4.3.6.
alkali metal amalgam, and alkaline earth metal amalgam, "– –"-4.3.7.
not pyrophoric metal powders (dust) aluminum, magnesium, mixed metals, zinc, titanium, electron, etc. "– –" powder-5.
Oxidizing substances and organic peroxides, which easily liberates oxygen, as well as the corresponding conditions or in a mixture with other substances cause autoignition and explosion: 5.1.
Oxidising substances, other substances which contribute to the ignition and burning of oxygen: 5.1.1.
salts, iron, Ammonium nitrate, nitric acid vanadium salts, potassium, sodium nitrite, etc. of the slāpekļpaskāb salts, potassium, sodium salts of manganāt, mangānskāb, lithium, nickel chromates, etc. of the hromskāb salts, potassium dichromate salts, sodium dihromskāb, etc of the perchlorate salts, etc., perchloric acid potassium chlorate etc. of hlorskāb salts, nickel, etc. bromskāb salts of bromate, sodium, etc. peroksisērskāb peroksisērskāb salts of 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2. , 4.3., 5.1.2, 5.1.3, 5.2, 6.1, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse section 5.1.2 isolated.
peroxides of metals of barium, calcium, potassium, lithium, magnesium, manganese, sodium, silver, antimony, strontium, chromium trioxide and peroxides 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2., 4.3., 5.1.1, 5.1.3, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
-"— 5.1.3.
hydrogen peroxide hydrogen peroxide – "–" – Not heated rooms, keep away from heat sources 5.1.4.
bromine Bromine – – – – 5.2.
organic peroxide and hidropārskāb, which will act as oxidizing agents, easy to ignite and are sensitive to impact and friction benzoyl peroxide, peroxide, dikumil 2-4-dihlorbenzoil peroxide, acetilperoksīd, etilmetilketon peroxide, peroxide laurate, cyclohexanone peroxide, peroxide, dzintarskāb of cumene hidropārskāb 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3, 4.1, 4.2, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
-"to be taken to prevent the hidropārskābj of organic pārskābj and the exposure generated by the retarder (flegmatizator) losses below the technical regulations specified rules that can lead to group 1 substances formation 7.
Toxic substances that cause poisoning or death: 6.1.
metals, crystals, powder of metallic beryllium powder and its compounds, barium oxide and barium compounds, cadmium oxide and cadmium compounds, metallic arsenic and arsenic compounds, metallic mercury and mercury compounds, lead and its compounds, inorganic selenium and its compounds, antimony oxide and antimony salts by thallium compounds, sodium fluoride, sodium tetraborate, nonohloramīn, crystalline phenol, copper vitriol 1., 2.1., 2.2., 2.3., 2.4., 3.1. , 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6.2, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
– "-6 Group substances prohibited under awnings 6.2.
koroziāl corrosive and poisonous substances, poisonous the combustible liquids whose flash point is greater than 55 ° C aniline, aniline salt of hydrochloric acid, anabazīn-sulfate, anisidine, aldrin, benzicīn, heksametilēndiamīn, hidrazīnhidrāt and its derivatives, metafos, dinitrotoluene, Dinitrobenzene, tereftālskāb, fenetidīn, tiofos, chloroaniline, oxalic acid 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 3.4, 4.1, 4.2, 4.3, 5.1, 5.2, 6.1, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
– “ –
– “ –
7.
Radioactive substances (isotopes) 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
-"radioactive substances may be imported only with a special warehouse sanitary supervisory authorities and the Interior Ministry permit 8.
Corrosive and koroziāl substances, which cause skin, respiratory and eye mucous lesions, cause metal corrosion and damage vehicles or cargo and can also cause fires, interact with organic materials, etc.: 8.1.
acid: 8.1.1.
strong acid nitric acid and sulphuric acid and mixtures, mixtures, sērpaskāb, hydrochloric acid, trichloroacetic acid, chromic acid, hlorskāb, hlorsulfonskāb, hydrofluoric acid, sulfonic acid, bromūdeņražskāb, jodūdeņražskāb, acid electrolyte 1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins, isolated solid and liquid substances be kept in separate shelves for 72% and stronger hlorskāb must reside separately from other substances and materials, separate room in 8.1.2.
weak acid Tetrafluorborskāb, heksafluorfosforskāb, heksafluorsilīcijskāb, monobrometiķskāb, dihloretiķskāb, orthophosphoric acid, liquid fire extinguisher disphosphorus pentoxide stuffing, etc.
– “ –
– “ –
– “ –
8.2.
bases sodium alumināt (solution), the caustic sodium, caustic soda, caustic, tetramethylaminium electrolyte for alkaline batteries, potassium oxide, sodium oxide, soda lime, etc.
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins isolated 8.3.
various corrosive and koroziāl substances: 8.3.1.
strong bromine and bromine oxidizing metallic iodine, iodine chloride, hlorkaļķ, sodium hypochlorite, calcium hypochlorite, chromium oxychloride, hlorpaskāb salts, bleach, sodium fluoride and other hlorskāb salts, phosphorus pentachloride, etc. 
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 6, 7, 8.1, 8.3, 9.1, 9.2, 9.3.
1, 2, or 3. (a) the degree of reaction to isolated storage compartments. 8. the Member of the group, which does not freeze in winter, allowed to hold under awnings Not heated premises, protection against sun rays 8.3.2.
substances which becomes koroziāl in contact with damp Tetrahlorsilīcij, tetrahloralv, tetrahlortitān, Tetra-hlorfosfor, phosphorus trichloride, chloride, sulphur, phosphorus sulfohlorīd sulfurilhlorīd, Phosphorus oxychloride, etc.
– “ –
– “ –

8.3.3.
other corrosive substances and koroziāl aluminium bromide, aluminum chloride, aluminum ammonium alum, aluminum potassium alum, ammonium thiocyanate, calcium and sodium bisulphite, sodium bisulphate, potassium bisulphate, Tin dichloride, chromium rifluorīd, etc. 
– “ –
– “ –

9.
Substances that are in the process of storage is a little dangerous: 9.1.
solid substances and combustible liquids whose flash point is higher than 61 ° C, anīsaldehīd Old, antifreeze, pigments (except white), 1.2-Butanediol, benzyl alcohol, benzilbenzoāt, benzilacetāt, butilaktāt, glycerin, glycol, primer, dibutiloksalāt, dimethyl phthalate, dioktilftalāt, glycol diametāt, dodecane, Rosin, kopān, adipic acid, valeric acid, Caprylic acid, kapronskāb, butyric acid, propionic acid, powdered color, dyes and pamatkrāsviel acid (powder and paste), the hidrobremž fluid, brake fluid, synthetic paraffin oil, castor oil, aparāteļļ, vegetable oil , transformer oil, menthol, natural, pernic propanediol, ziežamviel, triethanolamine, tetradekān, bodyfiller materials, enamel, emulsion, etc. 
1., 2.1., 2.2., 2.3., 2.4., 3.1., 3.2., 3.3., 4.1., 4.2, 4.3, 5.1, 5.2, 6, 7, 8.1, 8.2., 8.3.
1, 2, or 3. (a) the degree of safety in the warehouse bins 9.2 isolation.
substances which becomes corrosive and koroziāl in contact with the moisture of ammonium bromide, ammonium phosphate, heksametafosfāt, iron sulphate, potassium sulphate, calcium thiosulfate, potassium acetate, potassium bromide, potassium iodide, potassium chloride, potassium carbonate, Sodium Thiosulphate, sodium phosphate, sodium acetate, sodium bromide, sodium iodide, sodium carbonate, nickel sulfate, nickel chloride, nickel carbonate, calcium oxide, zinc sulphate, zinc acetate, zinc chloride, etc.
– “ –
– “ –

9.3.
weak toxic substances, which becomes poisonous fire conditions, auramīn, Altak ammonium molybdate ammonium, dinitroortokrezolāt, arzamīt, bakelite (liquid and solid phenolic resin), hexachloroethane, hexachlorobutadiene, hydroquinone, diethanolamine, dodecilmerkaptān, dihlorkarbamīd, ditān, dalapon, oxalic acid, benzolskāb, kreolīn, urea, Mono, I-naphthol, ozone, not magnesium oxide, Tin sulphate, pirogallon, resorcinol, tantāl pentachloride, etc.
– "–" – notes.
1. If the substance is not listed in this table, the corresponding (sub) to be broken down in accordance with the national standard of the substance concerned or the technical regulations defined risk and toxicological characteristics. 2. If fire risk and toxicological properties are unknown, its storage rules developed after fire hazard of the substance concerned and toxicological characteristics of research and coordination with the Ministry of the Interior's national fire and rescue service. 3. chemicals and packaging materials must be warning signs about the dangers of the substance concerned.
Minister of Interior m. Swan Annex 9 of the Cabinet of Ministers of 17 February 2004, regulations No 82 fire apparatus and equipment selection

1. Fire apparatus and equipment choices, depending on the area of the premises and the premises of the process to fire risk, as well as the use and storage of the substance, physical and chemical properties. 2. vehicles and technological equipment fitted with fire extinguishers according to technical requirements.
3. According to the burning material fire are divided into the following classes: class A, 3.1-fire that is burning hard, usually organic, material and burn up the formation of glowing coals; 3.2. Class B fire that is burning-liquid or solid material melting; 3.3. class-C fires that burn gas; 3.4. Class D – fire, which is burning metals. 4. If you could be a fire attributable to different classes of fire, with priority given to the universal fire extinguisher. 5. If the premises is located in the electrical voltage of at least 50 percent of the existing premises of the fire apparatus electrical equipment must be suitable for deletion. 6. With fire apparatus of hardware, telephone station, museums, archives, and similar spaces, take account of the extinguishing agent and the protected equipment, products and materials of possible interactions. The premises in question may not use water or foam fire apparatus. 7. Maximum distance from any place in the room to fire apparatus locations: 7.1. public buildings should not exceed 20 metres; 7.2. the production and warehouse premises must not exceed the following: 7.2.1. explosive spaces 15 metres; 7.2.2.30 metres or carry flammable areas; 7.2.3.40 meters in the fire.
8. public buildings, as well as explosive and fire in buildings and structures with floor space exceeding 50 m2 each floor housed no less than two fire extinguishers. 9. Fire apparatus type and quantity required shall be determined taking into account the possible fire class, extinguishing media deletion, deletion of the maximum area facilities or equipment used and the material properties, as well as the risk of explosion and fire risk of the premises. 10. the number of fire extinguishers shall be calculated as follows: 10.1 determine potential fire class depending on the use and storage of substances and materials physical and chemical properties; 10.2. choice of fire apparatus, with the appropriate extinguishing agent substances deletion capability (depending on the class of fire) according to table 1 of this annex; 10.3. the calculation of the number of portable fire extinguishers according to table 2 of this annex; 10.4. the calculation of the number of transportable fire extinguishers according to table 3 of this annex.
1. the extinguishing agent substances table choice depending on the class of fire, no PO box
Fire extinguishing agent substances in the class of water blowing gas powder ABC class BC class class D 1.
A
++
++
+
++
-
-
2.
B
-
++
+
++
++
-
3.
C
-
-
+
++
++
-
4.
(D)-----+ + legend: 1. + + 2 + most efficiently deletes valid 3.-invalid notes 1. The use of any other type of extinguishing agent, take into account the characteristics of the deletion and the manufacturer's standard, as well as the requirements of the technical regulations. 2. delete the implementation of fire (voltage up to 1000 V) the most effective use of gas and the ABC powder fire extinguisher class. 3. to delete Fire museums, archives, computer equipment and similar buildings and premises, as well as the most efficient cars use gas, and ABC powder fire extinguisher class. 4. In rooms that have chemical liquids belonging to polar solution (water soluble) groups, deleting using powder or water foam machines with universal foam concentrate solution.
table 2 portable fire extinguishers calculation table no PO box
Fire apparatus location calculation measure of portable fire extinguishers when they have a minimum weight of extinguishing agent (powder and carbon dioxide extinguishers-kilograms of water and foam machines-liters) is 2 kg (l) 4 kg (l) 6 kg (l) 1 2 3 4 5 6 1.
Public buildings and spaces for 200 m2 4 3 2 2.
Production and warehouse space: 2.1.
200 m2 of space-explosive-2 2.2.
fire room 400 m2-4 2 2.3.
fireproof room 600 m2-4 3 2.4.
extremely flammable, highly flammable, flammable liquids and liquefied gas reservoirs and reservoir parks reservoir up to 1000 one-m3-1 one reservoir, over 1000 m3-2.5-2.
rail explicate extremely flammable, highly flammable, flammable liquids and liquefied gases of unloading and loading of 50 m each-2 2.6.
extremely flammable, highly flammable, flammable liquids and liquefied gas tanker unloading and loading station one-pildn-2 2.7.
extremely flammable, highly flammable, flammable liquids and liquefied gases berths technological area 50 m2-2 3.
Material storage under awnings and open areas: 3.1.
solid combustible materials 400 m2-2 1 3.2.
flammable and combustible liquids and gases 400 m2-3 2 4.
Open parking of vehicles: 4.1.
cars 50-3 2 4.2.
trucks-3 2 5 25.
Fuel and gas station pildn-1-1 6.
Year of construction-3 2 7 800 m2.
Fire place of work 1 place 2 1-8.
Motor vehicles: 8.1.
Vehicles of category M1 1 PCs.
11-8.2.
trucks are highly flammable and combustible liquid transport according to ADR or Directive 94/95/EC. 8.3.
N1, N2, N3, 1 PC.
12-8.4.
Vehicles of category M2, M3, 1 PC.
-2-8.5.
agricultural machinery 1 PCs.
2 1-9.
Individual light-vehicle garage 1 place 1-legend: 1 minimum one kilogram capacity (litre). 2 If the lorry is a trailer or a semi-trailer, fire apparatus, the number increased twice.
The notes.
1. in determining the number of fire extinguishers shall comply with this annex, paragraph 7, the maximum distances to the apparatus. 2. maritime, rail and air vehicles be equipped with fire extinguishers in accordance with the technical requirements of the operating rules. 3. in determining the number of fire extinguishers for a specific location, select one of the 4, 5 or 6 standards set in box.
3. the transportable fire extinguishers table calculation table no PO box
Fire apparatus location calculation measure of the transportable fire extinguishers when the minimum weight of extinguishing agent (powder and carbon dioxide extinguishers-kilograms of water and foam machines-liters) is 20 kg (l) 80 kg (l) 1 2 3 4 5 1.
Stage theaters and other public buildings in the halls with the number of visitors, more than 800 1 scene 2-2.
Production and warehouse space: 2.1.
explosive facilities, greater than 400 m2 800 m2 2 1 2.2.
fire risk, more than 600 m2, which are used or stored in combustible liquids or solid materials melting 1200 m2 2 1 2.3.
extremely flammable, highly flammable, flammable liquids and liquefied gas reservoir parks reservoir group to 5000m3-1 reservoir group over 5000m3 2-2.4.
rail explicate extremely flammable, highly flammable, flammable liquids and liquefied gases of unloading and loading of the explicate 2 1 2.5.
extremely flammable, highly flammable, flammable liquids and liquefied gas tanker unloading and loading compartment compartment 2 1 2.6.
extremely flammable, highly flammable, flammable liquids and liquefied gases in the Wharf area of technological engineering area 2 1 3.
Open parking of vehicles: 3.1.
cars 75 places 1-3.2.
trucks 2 1 4 50 seats.
Flammable and combustible liquids and gas storage under awnings and open squares 1500 m2 2 1 5.
Stationary fuel and gas station 1 station 1-note.
First, second and third class aircraft parking area provides one of 20 kg (l) and one 80 kg (l) the transportable fire extinguishers.
11. road transport unit carrying dangerous goods shall provide:

11.1. with at least one portable fire extinguisher, provided in class A, B and C fires, with a minimum capacity of at least two kilograms of dry powder (or other fire retardant substances with equivalent of deletion ability), which would be used to transport the unit burning engine or cab for deletion; 11.2. the following additional equipment: 11.2.1. transport units with full (maximum) of more than 7.5 tonnes weight, one or more portable fire extinguishers for class A, B and C fires, with a minimum total capacity of 12 kg dry powder (or other fire retardant substances with equivalent of deletion ability), of which at least one machine the minimum capacity is six kilograms; 11.2.2. transport units with full (maximum) weight of 3.5 tonnes up to 7.5 tonnes (including)-one or more portable fire extinguishers for class A, B and C fires, with a minimum total capacity of eight kilograms of dry powder (or other fire retardant substances with equivalent of deletion ability), of which at least one machine the minimum capacity is six kilograms; 11.2.3. transport units with full (maximum) up to 3.5 tons weight (inclusive) – one or more portable fire extinguishers for class A, B and C fires, with a minimum total capacity of four kilograms of dry powder (or other fire retardant substances with equivalent of deletion ability); 11.2.4. fire extinguishers the minimum total capacity of 11.2. of this annex shall be reduced by 11.1 of this annex States the capacity of fire apparatus.
12. Transport units carrying dangerous goods in accordance with exceptional conditions, the quantity must be equipped with one portable fire extinguisher, provided in class A, B and C fires, with a minimum capacity of at least two kilograms of dry powder (or other fire retardant substances with equivalent of deletion ability). 13. If space is less than 2 and 3 of this annex set out in the table, the number of fire extinguishers shall be calculated as a pro rata of the area, the number of machine rounded up. 14. If separate room area of less than 50 m2 (except for the production, storage and technical meaning in space), fire apparatus may be mounted indoors (such as corridors and lobbies) and hall. The number of the machine is determined by calculating the room overall. 15. in addition to the fire extinguishers of fire-fighting equipment will be used for the following: 15.1 fire apron; 15.2. the water barrels and pails; 15.3. the box with absorbent or sand; 15.4. special tools (bit, ķekš, axes, shovels, ladders).
16. Fire cover must not be less than one square metre. Cover for a small fire to delete and the provenance of such material for deletion that is not able to burn without air access. Where are used and stored in flammable and combustible solution (gas stations, flammable liquids pumped storage station, where work with such liquids as well as automotive sites, which number more than 50 machinery), fire cover must not be less than 1.5 m x 2.17. Box volume, in which absorbent or sand, may not be less than 0.1 m³, and is complete with a scoop. Boxes of absorbent sand or placed where possible flammable and combustible liquid spills. 18. With fire extinguishers and fire-fighting equipment required to provide individual residential home, rural houses and farms. 19. With fire extinguishers and fire-fighting equipment recommended to equip the apartments, chalets and garages.
Minister of Interior m. Swan annex 10 of the Cabinet of Ministers of 17 February 2004, regulations No 82 Interior Minister m. Swan annex 11 of the Cabinet of Ministers of 17 February 2004, regulations No 82 Interior Minister m. Swan 12. Annex to the Cabinet of Ministers of 17 February 2004, regulations No 82 Interior Minister m. Swan annex 13. Cabinet of Ministers of 17 February 2004, regulations No 82 Interior Minister m. Swan, annex 14. Cabinet of Ministers of 17 February 2004, regulations No 82 fire technique and equipment minimum peat mining objects no PO box
Shop floor area (ha) Motorsūkņ (PCs.)
Mobile containers with a capacity of not less than 1 m3.
250 2 1 2