Advanced Search

Order Of 13 June 2008 On The Energy Performance Of Surface Greater Than 1 000 Square Meters, Existing Buildings When They Undergo Major Renovation Work

Original Language Title: Arrêté du 13 juin 2008 relatif à la performance énergétique des bâtiments existants de surface supérieure à 1 000 mètres carrés, lorsqu'ils font l'objet de travaux de rénovation importants

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$40 per month.
Learn more about this text...

Information on this text

Texts transposed

Directive 2010/31/EU of the European Parliament and the Council on Energy Performance of Buildings

Summary

Partial transfer of Directive 2010/31/EU of the European Parliament and the Council on the energy performance of buildings.

Keywords

SUSTAINABLE DEVELOPMENT, EUROPEAN DIRECTIVE, PART TRANSPOSITION


JORF n°0184 of 8 August 2008 page 12656
text No. 1



Judgment of June 13, 2008 on the energy performance of existing surface buildings greater than 1,000 square metres, when major renovation works

NOR: DEVU0813714A ELI: https://www.legifrance.gouv.fr/eli/arrete/2008/6/13/DEVU0813714A/jo/texte


Minister of State, Minister of Ecology, Energy, Sustainable Development and Land Management, and Minister of Housing and Town,
In light of Directive 89/106/EC of 21 December 1988 on the approximation of the legislative, regulatory and administrative provisions of member States concerning construction products;
Considering Directive 98/34/EC of 22 June 1998 providing for an information procedure in the field of technical standards and regulations;
Considering the code of construction and housing, and in particular article R. 131-26;
In view of the decision of 20 December 2007 on the cost of construction taken into account to determine the value of the building referred to in section R. 131-26 of the Construction and Housing Code,
Stop:

  • TITRE IER : GENERALITES
    • CHAPTER IER: PAPLICATION CHAMP Article 1 Learn more about this article...


      The purpose of this Order is to determine the terms and conditions for the application ofArticle R. 131-26 of the Construction and Housing Code.
      The provisions of this Order apply to existing buildings and parts of non-network surface buildings greater than 1,000 square metres, with the exception of the following categories of buildings:
      (a) Buildings or parts of buildings that, due to special constraints related to non-residential use, must guarantee special conditions of temperature, humidity or air quality;
      (b) The buildings or parts of buildings for agricultural, artisanal or industrial use, other than the premises for housing, in which the heating or cooling or hot water system for human occupancy produces a small amount of energy in relation to that required for economic activities;
      (c) Non-heated buildings or parts, in which the only fixed heating equipment is open fireplaces, and does not have a cooling system for the premises;
      (d) The buildings intended to remain completely open on the outside in normal operation;
      (e) Buildings located in overseas departments.
      The provisions of this Order apply when rehabilitation work is undertaken on the envelope, heating, hot water production, cooling, ventilation, lighting or equipment using the renewable energy of a building, at a total cost greater than 25% of the value of the building concerned.

      Article 2 Learn more about this article...


      The provisions applicable to buildings or parts of buildings whose completion date is prior to January 1, 1948 are those of sections 2 to 44 of the May 3, 2007 Order relating to the thermal characteristics and energy performance of existing buildings.
      The provisions applicable to buildings or parts of buildings whose completion date is after 1 January 1948 are those of sections 3 and following of this Order.

      Article 3 Learn more about this article...


      The value of the building concerned is determined according to its use and its non-network surface in accordance with the provisions of the December 20, 2007 Order relating to the cost of construction taken into account in determining the value of the building referred to in theArticle R. 131-26 of the Construction and Housing Code.

      Article 4 Learn more about this article...


      The calculation of the anticipated cost of the work referred to in section 1 of this Order shall include at least the cost of:
      - construction or replacement of an opaque wall separating the heated atmosphere from the outside, from the ground or from an unheated space;
      - works of insulation of opaque walls, including works of paints, plasters, tiles, electricity resulting from insulation work;
      ― works to rehabilitate the sealing of terraced roofs, including works induced on acroteries and inseparable technical equipment of the building located in the roof;
      - repair or roof cover work;
      – installation or replacement of glass walls or doors overlooking the outside, including works of paints, consecutive plasters;
      - installation or replacement of solar closures or protections;
      - work on the installation or replacement of elements of the heating system or the production of sanitary hot water, including work of large work or deck outside the building, work on the networks, work on the exhaust system of combustion products and work on the resumption of paints, consecutive plasters;
      – removal or installation of chimneys;
      - installation or replacement of elements of the ventilation system;
      - installation or replacement of elements of the cooling system;
      - installation or replacement of elements of the lighting system in non-residential buildings, including consecutive electricity work;
      - installation or replacement of building regulatory, programming or technical management elements, including consecutive electricity work;
      ― replacement or installation of continuous electricity production systems;
      – installation or replacement of solar thermal installations.
      This cost includes all expenses related to the removal and release of the equipment and structures replaced, the provision and installation of new structures and equipment, as well as all possible induced work, including all of the construction facilities, and were subject to the execution of this work.

      Article 5 Learn more about this article...


      For the purposes of this Order, prior to the filing of the construction permit application or the pre-reportation within the meaning ofarticle L. 421-4 of the urban planning code or, if the work is not subject to this permit or to this declaration, prior to the acceptance of the quotations or the procurement of the work, the owner shall make an estimate of the cost of the work referred to in Article 4.
      In the absence of a detailed costing of each of the types of work referred to in Article 4, and if the market benefits for this work are subject to separate lots, this estimate may be made on the basis of the estimation of the lots containing this work.

    • CHAPTER II: DEFINITIONS Article 6 Learn more about this article...


      Eight H1a, H1b, H1c, H2a, H2b, H2c, H2d, H3 are defined in annex I to this Order.
      Three classes of exposure of buildings to noise from transport infrastructure BR 1, BR 2 and BR 3 are defined and determined in accordance with the terms of Appendix II to this Order.

      Article 7 Learn more about this article...


      The terms necessary for understanding this Order are set out in annex III.

      Article 8 Learn more about this article...


      The building is called the initial building as it exists before the rehabilitation work. The building is called a project building as designed following the renovation work.

      Article 9 Learn more about this article...


      The conventional energy consumption of a building for heating, cooling, production of sanitary hot water, lighting, and auxiliaries for heating, cooling, hot water and ventilation, is expressed as a coefficient expressed in kWh/m2 of primary energy, noted Cep. This coefficient takes into account a possible production of electricity to remain in the building.
      The area taken into account is equal to the non-network floor area within the meaning ofarticle R. 112-2 of the urban planning code.
      This coefficient is calculated for a period of one year by adopting conventional climate data for each climate zone, according to the calculation methods defined in the TH-C-E ex calculation method approved by an order of the Minister in charge of construction.
      Cepinital and Cepproject respectively note the conventional energy consumption calculated for the original building and for the project building.
      The reference consumption of the building is called in the project and is noted This prefects the conventional energy consumption of the project building, calculated on the basis of the reference characteristics given in Title II of this Order.

      Article 10 Learn more about this article...


      The conventional indoor temperature reached in summer, noted Tic, is the maximum hourly value during the period of occupancy of the operating temperature; for residential the period of occupation considered is the entire day. It is calculated by adopting conventional climate data for each climate zone.
      Tic's calculation methods are defined in the TH-C-E ex calculation method approved by a Minister's Construction Order.
      Conventional reference internal temperature is called and Tic refutes the conventional indoor temperature reached in the summer, determined on the basis of the reference thermal characteristics given in Title II of this Order.

      Article 11 Learn more about this article...


      There are two categories of premises in respect of summer comfort and cooling, named CE1 and CE2, and defined in Annex III.

    • CHAPTER III: EXIGENCE Article 12 Learn more about this article...


      1. Is considered to satisfy this thermal regulation any project building for which the construction master is able to show that the following conditions are met simultaneously:
      1° The conventional energy consumption of the initial Cepinital building is estimated using TH-C-E ex, in accordance with the terms specified in Article 14 of this Order;
      2° The conventional energy consumption of the building in the Cepproject project is less than or equal to its reference consumption Cepref;
      3° For buildings in residential projects, conventional energy consumption for heating, cooling and production of sanitary hot water, expressed in kWh/m2 of primary energy of the building in project, is less than or equal to a maximum Cepmax coefficient, determined in the manner specified in Article 13 of this Order;
      4° For non-residential project buildings, conventional energy consumption of the Cepproject building is less than 30% than the consumption of the original Cepinital building, estimated as 1 (1°) of this article.
      5° The minimum requirements set out in Part III of this Order are met.
      6° For areas or parts of CE1 category areas and for each of the project areas defined by its use, the conventional internal temperature of the Tic zone is less than or equal to the conventional internal reference temperature of the Tic ref area. This requirement can also be met by considering each part of the building areas for which Tic and Tic ref tower are calculated; If the calculation leads to a value of Tic ref below 26 °C, Tic ref is then equal to 26 °C.
      This requirement does not apply to areas comprised of EC2 class premises.
      2. Project buildings whose construction products and their implementations are deemed to be in compliance with the technical processes and solutions approved under the conditions described in Part IV of this Order are deemed to be in compliance with the regulations.

      Article 13 Learn more about this article...


      For the purposes of Article 12, the values of the maximum Cepmax coefficient are given in the following table:


      TYPE
      heating system
      ZONE
      climate
      CEPmax EN kWh
      Primary energy
      /m2/an

      Fossil or wood fuels

      H1

      130


      H2

      110


      H3

      80

      Electric heating

      H1

      165

      (including heat pumps)

      H2

      145

      or Heat Network
      starting January 1, 2010.

      H3

      115

      Electric heating

      H1

      195

      (including heat pumps)

      H2

      175

      or Heat Network
      until December 31, 2009.

      H3

      145


      In the case of a building using different heating systems, the Cepmax coefficient is equal to the average Cepmax coefficients for heating systems, weighted by the corresponding heating requirements.

      Article 14 Learn more about this article...


      In the following two cases, by derogation from 1 (1°) and 1 (4°) of Article 12, it is not required to evaluate the Cepinital consumption and, for non-residential buildings, the consumption of the Cepproject building must not necessarily be less than 30% than the Cepinital consumption:
      ― renovation work is accompanied by a change of use within the meaning of the TH-C-E ex method;
      ― or the entire pre-renovation building was not used, or heated or cooled.
      The other provisions of section 12 apply.

      Article 15 Learn more about this article...


      The workmaster must be able to justify any value used as input data for the calculation of the Cep and Tic coefficients in accordance with the TH-C-E ex calculation method:
      where products are subject to application Decree No. 92-647 of 8 July 1992 modified with respect to the suitability of the use of construction products, the products identified in this case by the affixing of the CE mark, and that the latter includes the thermal characteristic, the justification of this value is provided by reference to the harmonized standards or European technical approvals;
      otherwise, the characteristics of the products are justified by reference to French standards or equivalent technical advice or national standard accepted by a member country of the European Union or contracting party of the EEE agreement, and are issued by an independent third party body notified under Directive 89/106 recognized by a member State of the European Community or a Contracting State of the Agreement establishing the European Economic Area. The benefit of this provision is only valid during the period preceding the application of a harmonized European standard or European technical approval.
      In the absence of the power to justify a value of the thermal characteristic of a product under these terms, the value to be used is specified in the TH-C-E ex calculation method.

      Article 16 Learn more about this article...


      With the exception of buildings whose construction products and their implementation are in accordance with technical processes and solutions, the construction master shall make the description of the data used for the calculation in electronic format, according to the model defined in the TH-C-E ex calculation method.
      The master also prepares, at the latest, a synthesis of thermal study according to the terms specified in Annex VI.

  • TITRE II : BATIMENT DE REFERENCE
    • CHAPTER IER: THERMAL CARACTERISTICS OF THE BATI


      Inertia

      Article 17 Learn more about this article...


      The reference daily inertia is determined by inertia prior to renovation work using the TH-C-E ex method. If the inertia before work is light or very light, the reference inertia is equal to the inertia of the building before work. Otherwise, the reference inertia is medium.
      The reference sequential inertia is very light within the meaning of TH-C-E ex.


      Surfaces and wall orientation

      Article 18 Learn more about this article...


      For the calculation of Tic ref and Cepref, the reference bay surfaces are those of the project.
      However:
      ― where the renovation works provide for the installation or replacement of the entire curtain façade such as the bay surface is greater than 50% of the façade surface, it is considered to be 50% of the façade surface for the reference building calculation. The considered front surface is equal to the sum of vertical wall surfaces in contact with the outside or with a non-heated space;
      ― where the renovation works provide for the replacement of the entire cover of a high floor, the surface of the reference horizontal bays has a maximum limit of 10% of the total surface of this floor.
      Surfaces above these thresholds are considered opaque walls and are added to them.

      Article 19 Learn more about this article...


      For the calculation of Tic ref and Cepref, the reference bays are those of the project building.

    • CHAPTER II: THERMICAL ISOLATION Rule 20 Learn more about this article...


      Thermal deflections by transmission through the walls and bays of a building are characterized by the average thermal depletion coefficient of the building, called Ubat, expressed in W/(m2.K), and determined in the TH-C-E ex calculation method.

      Article 21 Learn more about this article...

      The reference thermal deflections are calculated with dimensional characteristics A1 to A7 and L8 to L10 of the project defined as follows:
      A1: surface of vertical opaque walls, including the vertical walls of the fitted panels and projected surfaces of roller shutters not integrated into the bay, with the exception of opaque surfaces taken into account in A5, A6 and A7;
      A2 : surface of high floors and roofs other than those taken into account in A3 ;
      A3 : surface of high floors overlooking the exterior of concrete or masonry for any building, and surface of high floors based on metal plates of non-residential buildings;
      A4: low floor surface;
      A5: surface of doors, except for fully glazed doors;
      A6: surface of windows, fully glazed doors, windows and transparent or translucent walls of non-residential buildings;
      A7: surface of windows, fully glazed doors, windows doors or transparent and translucent walls of residential buildings;
      L8: linear of the peripheral link of low floors with a wall;
      L9: linear of the peripheral link of the intermediate or sub-alloyable floors with a wall;
      L10: linear of the peripheral link with a wall of high concrete, masonry floors or with ribbed metal plates.
      The surfaces of vertical opaque walls and bays take into account the specifications of Article 18.
      A1 to A7 surfaces are the inner surfaces of the walls and linear L8 to L10 are determined from the inner dimensions of the premises. Only, for the determinations of these surfaces and linear, are taken into account the walls or connections giving on a heated space, on the one hand, and on the outside, an unheated space, the ground or a sanitary vacuum.
      The surface to be taken into account for doors, windows and windows is the table.
      In case the peripheral link of a floor is at the junction of an intermediate floor with a low floor or a high floor, the linear to be taken into account is L8 or L10 respectively.
      The values of the reference thermal transmission coefficients a1 to a10 corresponding to the dimensional characteristics A1 to A7 and L8 to L10 are given in the table below:

      COEFFICIENT
      have

      ZONES H1, H2
      and H3 800 metres
      ZONE H3
      ≤ 800 metres
      a1 (W/m2K)
      0.36
      0.40
      a2 (W/m2K)
      0.20
      0.25
      a3 (W/m2K)
      0.27
      0.27
      a4 (W/m2K)
      0.27
      0.36
      a5 (W/m2K)
      1.50
      1.50
      a6 (W/m2K)
      2,10
      2,30
      a7 (W/m2K)
      1.80
      2,10
      a8 (W/m.K)
      0.50
      0.50
      a9 (W/m.K)
      0.9
      0.9
      a10 (W/m.K)
      0.9
      0.9

      For other wrap elements, reference thermal transmission coefficients are zero.
      For residential buildings, the value of a7 corresponds to bays with closure.
      For displays and entrance doors for public access to non-residential buildings, lanterns, smoke outlets and fire openings, the coefficient a6 is taken equal to 5.8 W/(m2.K).

    • CHAPTER III: SOLAR AND LUMINAL APPORTS Article 22 Learn more about this article...


      For the calculation of the Cepref coefficient, berries are equipped with mobile protections such as the solar factor and the luminous transmission rate are 0.40 in open position and 0.15 in closed position.

      Article 23 Learn more about this article...

      For the calculation of Tic ref the reference solar factor of the berries is defined in the table below, depending on their exposure to noise, orientation and inclination, as well as the climatic zone and altitude. The reference luminous transmission factor is taken equal to the reference solar factor.

      H1a and H2a
      All altitudes
      H1b and H2b
      Altitude
      400 m
      Altitude
      ≤ 400 m
      H1c and H2c
      Altitude
      800 m
      Altitude
      ≤ 800 m
      H2d and H3 areas
      Altitude
      400 m
      Altitude
      ≤ 400 m
      1. Exposed BR1 bays with non-domestic occupation:
      North Bay
      0.65
      0.45
      0.25
      Vertical bay other than north
      0.45
      0.25
      0.15
      Horizontal Bay
      0.25
      0.15
      0.10
      2. Exposed BR2 or BR3 bays off-site with non-domestic occupation:
      North Bay
      0.45
      0.25
      0.25
      Vertical bay other than north
      0.25
      0.15
      0.15
      Horizontal Bay
      0.15
      0.10
      0.10
      3. Passive occupancy:
      Vertical Bay
      0.65
      0.65
      0.45
      Horizontal Bay
      0.45
      0.45
      0.45

      Article 24 Learn more about this article...


      The reference solar factor for opaque walls and peripheral connections is 0.01 for the calculation of Cepref and 0.02 for the calculation of Ticréf.

    • CHAPTER IV: PERMEABILITY Rule 25 Learn more about this article...


      Air permeability under 4 Pa of the exterior envelope of the building referenced and reported to the surface of the envelope is equal to:
      1.7 m3/(h.m2) for residential or office buildings, hotels, catering and teaching facilities as well as sanitary facilities;
      3 m3/(h.m2) for other uses.
      For buildings with different areas of use, the reference value is calculated on average weighted by the useful surfaces of the areas as defined in the TH-C-E ex calculation method.
      The surface of the envelope referred to in this article is the sum of the A1 to A7 surfaces referred to in Article 21, excluding the surfaces of the low floors (A4).

    • CHAPTER V: VENTILATION Rule 26 Learn more about this article...


      The reference ventilation system is such that the same outdoor air is used to ventilate the contiguous or separated premises only by traffic, within the limits of existing regulations.

      Rule 27 Learn more about this article...


      For residential premises, the reference system is a system by air extraction taking air directly outside, the sum of the modules of the air inputs is 90% of the maximum flow value resulting from hygiene regulations.
      The flow rates to be recovered are equal to the minimum flow rates resulting from hygiene regulations or, if not, conventional specific flow rates defined in TH-C-E ex rules, plus the Crdb flow rate control coefficient equal to 1, and the overflow factors taking into account the uncertainties associated with the characterization of the mouths and leaks of the Cd aerallic network equal to 1.1 and Cfres equal to 1.
      The extractor mouths located in the kitchen are at two flow rates and equipped with a manual flow management device. The other mouths are flat-rate.
      The reference power of the Pventref fans is 0.25 watt per cubic metre and per hour of airflow per fan. This value is ranged to 0.40 if the installed system is equipped with a Class F5 to F9 Insufficient Filter. Powers are calculated for hygienic rates increased by 10%.

      Rule 28 Learn more about this article...


      For residential premises heated by Joule effect, the reference ventilation system is a system of modulation of ventilation flows to reduce by 25% the energy depletion due to the specific ventilation, calculated on the basis of articles 26 and 27.
      For other residential premises, the reference ventilation system is a system of modulation of ventilation or heat recovery flows to reduce by 10% the energy losses due to the specific ventilation calculated on the basis of articles 26 and 27.
      For all of these premises, the impact of the reduction of the flow from the flow through the leakage defects is taken into account in the calculation.

      Rule 29 Learn more about this article...


      For non-residential premises, the reference system is a system by insufflation and air extraction without heat exchanger and without fresh air preheating and whose incoming and outward flow rates are equal. The flow rates to be supplied and taken back are equal to the minimum flow rates resulting from hygiene regulations or, if not, conventional specific flow rates defined in TH-C-E ex rules, plus the Crdb flow rate control coefficient equal to 1, and the overflow factors taking into account the uncertainties associated with the characterization of the mouths and leaks of the Cfres aerial network equal to 1.25 and Cd.
      For premises for intermittently reunification of persons, as defined in annex III, the reference Crdnr flow reduction coefficient is 0.5.
      The reference power of blowing fans and Pventref extraction fans is 0.30 watt per cubic metre and per hour of airflow per fan. This value is ranged to 0.45 for blowing fans if the installed system is equipped with a F5 to F9 Class Insufficient Filter. Powers are calculated for hygienic rates increased by 10%.

    • CHAPTER VI: CHAUFFAGE Rule 30 Learn more about this article...


      The reference consumption for a Joule effect heating system is calculated with the following data:
      1. The system does not have losses for heating generation, storage and distribution;
      2. The programming of the heating intermittences is provided by a programmator taking into account the internal temperature, directly or by a change of the control points of the terminal regulations, but not having an optimization function;
      3. The torque formed by the transmitter and its regulation has a spatial variation of Class B and a temporal variation of 0.9 K within the meaning of the TH-C-E ex calculation method;
      4. The losses on the back of the emitters are zero;
      5. For category CE1, transmitters are not equipped with fans. For category CE2 premises, the transmitters are equipped with reference fans whose power is 2 W/m2.

      Rule 31 Learn more about this article...

      For heating systems other than those referred to in Article 30, the reference consumption for heating is calculated with the following assumptions.

      1. Generation

      For liquid or gaseous fuel generators, the reference system has the following characteristics:
      - the nominal Pn heaters, expressed in kW, are those used for the calculation of Cep;
      - the minimum operating temperature is that of a low temperature boiler within the meaning of the TH-C-E ex calculation method;
      performance is shown below.


      Pn ≤ 400 kW
      Pn ✱ 400 kW
      PCI yield at full load, in percentage, for an average water temperature in the boiler of 70 °C
      88,5 + 1.5.log Pn
      92.4
      PCI yield to 30% load, per cent, for an average water temperature in the 40 °C boiler
      88,5 + 1.5.log Pn
      92.4
      Pertes with zero load, as a percentage of Pn, for a temperature difference between the average temperature of the water in the boiler and room temperature equal to 30 °C
      1,75 - 0.55.log Pn
      0.32

      When the boiler has several generators, the unused generators are hydraulically isolated.
      The operating temperature of the generators is dependent on the outside temperature if the area served by the generator is greater than 400 m2. Otherwise it is dependent on the inside temperature.
      For solid fuel generators using wood as energy, the reference system consists of a full load PCI output generator in percentage, for an average water temperature in the 70 °C generator, 57 + 6.log Pn for nominal power Pn less than or equal to 400 kW and 72.6 more.
      For thermodynamic generators using electricity, the corrected performance coefficient defined within the meaning of the TH-C-E ex calculation method (COP corrected) is 2.45. The other characteristics are those defined by default in the TH-C-E ex calculation method.
      For a heating system connected to an urban heating network, the components of the reference substation are isolated with a Category 2 product for the secondary network and 3 for the primary network, within the meaning of the TH-C-E ex calculation method.
      For other systems, excluding those defined in section 30, the reference generator is a liquid or gaseous fuel boiler.
      The reference position of the generators is that of the project.

      2. Distribution

      The reference distribution system is of the bitube type entirely in heated volume if the generator is located in heated volume, with a non-heated part otherwise. The non-heated part has Class 2 reference insulation. The other characteristics of the distribution system are those defined by default in the TH-C-E ex calculation method.
      The water temperature is average within the meaning of the TH-C-E ex calculation method. It is regulated according to the external temperature if the surface served by the generator is greater than 400 m2. Otherwise it is dependent on the inside temperature.
      The reference distribution pumps are at constant speed and are enslaved at the stop of the heat during periods of maintenance of the reduced temperature, as defined in the TH-C-E ex calculation method.

      3. Programming of intermittences

      The heat distribution is programmed by an automatic device that does not have an optimization function and takes into account the internal temperature, directly or by a change of the control points of terminal regulation.
      The latter is, however, not required in the continuing occupation premises for which the same programming device orders more than 400 m2.

      4. Emission and regulation

      The torque formed by the transmitter and its regulation has a spatial variation of Class B and a temporal variation of 1.2 K within the meaning of the TH-C-E ex calculation method.
      The emitters are supplied with medium temperature water within the meaning of TH-C-E ex.
      The back losses of the emitters are zero.
      For category CE1, transmitters are not equipped with fans. For category CE2 premises, the transmitters are equipped with reference fans whose power is 2 W/m2.

      Rule 32 Learn more about this article...


      In the case of a heating system using different types of emissions, distribution or generation, the references specific to each system are applied.

    • CHAPTER VII: SANITARY CHAUDE Rule 33 Learn more about this article...

      1. Production by a system using electricity.
      Production is ensured by Joule effect.
      The storage losses of the reference system are calculated by taking a cooling constant Cr of water heaters, expressed in (W.h)/(litre.K.jour), related to their capacity V, expressed in litres, equal to:
      Cr = 1.25.V- 0.33 if V is less than or equal to 500;
      Cr = 2.V- 0.4 if V exceeds 500.
      2. Production by another system.
      For sanitary hot water systems other than those referred to in section 33 (1), the generation losses of the reference system are calculated by assuming that the production is provided by one or more generators identical to those described in section 31 (1).
      The reference storage losses are calculated by taking a sanitary hot water storage ball with a Cr cooling constant, expressed in (W.h)/(litre.K.jour), related to its storage volume V, expressed in litre, equal to Cr = 3.3.V- 0.45 .
      3. Healthy hot water system using different types of generators.
      In the case of a sanitary hot water production system using different types of generators, the references specific to each generator are applied.
      4. Distribution.
      The sanitary hot water distribution network corresponds to the position of the reference production system. If the production is collective, the network is closed in the sense of TH-C-E ex.
      5. Position of storage balloons.
      The reference position of the storage balls is that of the project.

      Rule 34 Learn more about this article...


      For collective dwellings heated by Joule effect, consumption related to the production of sanitary hot water is reduced by 10%.
      The calculation of the reduction is done at the input of the generation system within the meaning of the TH-C-E ex calculation method.

    • CHAPTER VIII: REFROIDMENT Rule 35 Learn more about this article...


      For category CE1, cooling reference consumption and associated auxiliaries are zero.
      For EC2 class premises, cooling reference consumption and associated auxiliaries are calculated according to the characteristics of Article 36.

      Rule 36 Learn more about this article...


      1. Generation.
      For electric thermodynamic type generators, their efficiency corrected within the meaning of the TH-C-E ex calculation method, EERcorrigé, is 2.45. The other characteristics are those defined by default in the TH-C-E ex calculation method.
      For gas-cold production devices, the corrected efficiency within the meaning of the TH-C-E ex calculation method is 0.95 kW/kWep.
      2. Exchange.
      In the case of a cooling system linked to an urban cooling network, the components of the reference substation are characteristic of the project.
      3. Distribution.
      The reference distribution system is bitube type within the meaning of the TH-C-E ex calculation method. Its insulation is Class 3 within the meaning of the TH-C-E ex calculation method. The network length is the default value as defined in the TH-C-E ex calculation method.
      The temperature of the distributed fluid is low within the meaning of the TH-C-E ex calculation method.
      The reference distribution pumps are at constant speed and are served at the cooling stop.
      4. Programming of intermittences.
      For non-continuous occupancy premises and for networks serving a surface greater than 400 m2, the reference cold distribution is programmed by an automatic device controlled by a clock and taking into account the internal temperature directly or by a change of the control points of terminal regulations.
      5. Emission and regulation.
      The torque formed by the transmitter and its regulation has a spatial variation of Class B and a temporal variation of 1.8 K within the meaning of the TH-C-E ex calculation method.
      The transmitters are supplied with low temperature water within the meaning of TH-C-E ex.
      The back losses of the emitters are zero.
      The transmitters are equipped with enslaved fans with power of 2 W/m2.

    • CHAPTER IX: LOCAL CLAIMS Rule 37 Learn more about this article...


      This chapter applies to buildings covered byarticle R. 131-26 of the housing and construction code excluding buildings quotedarticle R. 111-1.

      Rule 38 Learn more about this article...


      The reference lighting power, known as Pecl ref, depends on the destination of the area or local area. It is given in the following tables in watt per square metre of useful area of the premises or in watts per square metre of useful area for 100 lux of maintained illumination.


      DESTINATION OF THE ZONE
      Pecl ref

      Trade and offices
      Sanitary establishment with accommodation
      Hotel and catering
      Education
      Sanitary establishment without accommodation
      Salles de spectacle, de conférence
      Industry
      Premises not mentioned in another category

      12 W/m2

      Sports establishment
      Storage
      Transport

      10 W/m2

      Local asking for an illumination
      to maintain more than 600 lux

      2.5 W/m2 per 100 lux
      with an upper limit of 25 W/m2

      Rule 39 Learn more about this article...


      Access to natural lighting taken in reference is:
      - effective, within the meaning of the TH-C-E ex calculation method, in parts of the building having actual or zero access to natural lighting within the meaning of the TH-C-E ex calculation method;
      ― impossible within the meaning of the TH-C-E ex calculation method, in parts of the building not having access to natural lighting.

      Rule 40 Learn more about this article...


      The lighting reference control is provided by manually controlled devices.

    • CHAPTER X: PRIMARY ENERGY TRANSFORMATION FOR CEP CALCUL Rule 41 Learn more about this article...


      Primary energy transformation coefficients are taken by agreement equal to:
      2.58 for electricity consumption and production;
      0.6 for wood consumption;
      1 for other consumption.

    • CHAPTER XI: OTHER CARACTERISTICS Rule 42 Learn more about this article...


      When a characteristic required for the calculation of Cepref or Ticréf is not defined in the preceding articles, it agreed that its value is equal to that used respectively in the calculation of Cepproject or Tic of the project.

  • PART III: MINIMUM EXIGENCE
    • CHAPTER IER: THERMICAL ISOLATION Rule 43 Learn more about this article...


      The provisions of this Article shall apply to each wall of a heated or considered space, whose surface is greater than or equal to 0.5 m2, giving on the outside, on a non-heated volume or in contact with the ground, provided that the renovation work referred to in Article 4 leads to thermally isolate the wall. The new built walls must also meet the following requirements.
      For windows, windows, windows, curtain facades and roller shutters, the provisions of this section apply when they are installed or replaced.
      In these cases, each wall shall have a thermal transmission coefficient U, expressed in W/(m2.K), less than or equal to the maximum value given in the following table.
      These requirements are excluded:
      – the stained glass;
      ― unheated verandas and loggias;
      – the windows;
      – showcases and windows with a special function (anti-explosion, anti-effraction, defumage);
      ― the fully glazed entrance doors and access to public premises;
      ― lanterns, smoke exutories and fire openings;
      – the translucent walls in glass paved;
      – the roofs for vehicle traffic.


      PAROIS
      COEFFICIENT U MAXIMAL

      Walls in contact with the outside or with the floor

      0.45

      Walls in contact with unheated volume

      0.45/b (*)

      Low flooring overlooking the outside or on a collective parking

      0.36

      Low planchers overlooking a sanitary vacuum or unheated volume

      0.40

      Flooring in concrete or masonry, and roofings in stained metal plates

      0.34

      High metal sheeting

      0.41

      Other high floors

      0.28

      Windows and doors bare sockets overlooking the outside

      2.60

      Façades-rideaux

      2.60

      Wheel shutters boxes

      3.0


      (*) b being the deferral coefficient to unheated volumes, defined in the TH-C-E ex calculation method.
      The maximum U coefficient taken into account for windows and windows is that corresponding to the vertical position.
      The new floor-to-ceiling floors of heated or considered premises shall be insulated at least on their periphery by a thermal insulation greater than or equal to 1.7 m2.K/W:
      - for surface areas greater than or equal to 500 m2 and dallages of industrial buildings, if the insulation is placed on the periphery, it can be vertically on a minimum height of 0.5 m;
      ― for other dallages, if the insulation is horizontal or vertical, its minimum width or height is 1.20 m.

      Rule 44 Learn more about this article...

      The depletion coefficient by the walls and bays of the building in project, noted Ubât, cannot exceed the maximum depletion coefficient by the walls and bays of the building, noted Ubât-max" and determined according to the use of the building, the base depletion coefficient by the walls and bays of the building, noted Ubât-base, and the Ctd coefficient defined as follows:
      ― housing buildings: Ubât-max = Ubât-base × 1.25 × Ctd;
      Other buildings: Ubât-max = Ubât-base × 1.5.
      The Ubât-base coefficient is calculated as follows:

      Ubâte = a1.A1 + a2.A2 + a3.A3 + a4.A4 + a5.A5
      + a6.A6 + a7.A7 + a8.L 8 + a9.L 9 + a10.L 10
      A1 + A2 + A3 + A4 + A5 + A6 + A7

      The coefficients a1 to a10 are defined in Article 21.
      The A1 to A7 surfaces of opaque walls and bays and linear L8 to L10 are those of the project, as defined in Article 21.
      The Ctd coefficient is equal to the ratio of the total envelope surface of the building (including the surfaces separating the building into a project of the adjacent buildings if any) by the depletional surface of the building (equal to the sum of the coefficients A1 to A7).

      Rule 45 Learn more about this article...


      The insulation works of the opaque walls should not result in modifications of the aspect of the construction in contradiction with the protections provided for the saved sectors, the areas of protection of the architectural, urban and landscape heritage, the surroundings of the historical monuments, the sites listed and classified, the sites listed on the UNESCO World Heritage List or any other preservation decreed by the local authorities, as well as for the buildingsArticle L. 123-1 of the urban planning code.

    • CHAPTER II: EET CONFORT Rule 46 Learn more about this article...


      In any room intended for sleep and category CE1, the solar factor of berries must be less than or equal to the reference solar factor defined in the table to Article 23.

      Rule 47 Learn more about this article...


      Unless the rules of hygiene or safety prohibit it, the new bays of the same room other than for temporary occupation and category CE1 must be able to open on at least 30% of their total surface.
      This limit is reduced to 10% in the case of premises for which the altitude difference between the lower point of its lowest opening and the top point of its highest opening is equal to or greater than 4 m.

    • CHAPTER III: VENTILATION Rule 48 Learn more about this article...


      Renovation work must maintain a general and permanent ventilation system if it already existed prior to the renovation work.
      Otherwise, renovation work must be accompanied by the maintenance or installation of a system to ensure a minimum air renewal:
      - either a ventilation by service piece, mechanical or aeration grid in the parts facing the outside. In both cases the living rooms are equipped with minimum module air inputs 45 for rooms and 90 for stays;
      - a system ensuring a general and permanent ventilation.

      Rule 49 Learn more about this article...


      The provisions of sections 50 to 56 apply in the event of installation or replacement of the ventilation system.

      Rule 50 Learn more about this article...


      When in heating times an insuffed air humidification is provided, an automatic device must be able to adjust humidification to a level that corresponds to an absolute humidity of the insufficiated air less than or equal to 5 grams per kilogram of dry air.

      Rule 51 Learn more about this article...


      In the case of a non-residential building, the ventilation of premises or groups of premises with clearly different occupations, uses or emissions of pollutants shall be provided by independent systems.

      Rule 52 Learn more about this article...


      In the case of a non-residential area, specific mechanized ventilation systems shall be equipped with devices allowing, during heating and cooling periods, to limit the flow to the minimum values resulting from hygiene regulations for periods where the area is unoccupied.

      Rule 53 Learn more about this article...


      In the case of a non-residential building equipped with specific mechanized ventilation systems, any manual alteration of the airflows of a local must be timed.

      Rule 54 Learn more about this article...


      The cooling systems of the premises by increasing the flow rates beyond those required for hygiene needs must be equipped with devices that condemn this increase when the heating works.

      Rule 55 Learn more about this article...


      Ventilation networks are isolated in the following cases:
      - for heated or cooled air networks, in the parts between the heating or cooling device and the limit of the place where the blowing occurs, with the exception of the part between the local and the setting organ for cold air networks. For heated air networks only heated, insulation is imposed only if the blown air is warmed at a temperature above the temperature of delivery;
      ― for blown or resumed air networks with retrieval or recycling device, in areas outside the heated volume and between the retrieval or recycling device and the limit of the heated areas of the building.
      For parts of ducts located inside heated and to be isolated, the thermal resistance is greater than or equal to 0.6 m2K/W.
      For parts of ducts located outside heated and to be isolated, the thermal resistance is greater than or equal to the following two values: 1.2 m2K/W and the Acondext/(0.025.Ap) ratio where:
      Acondext is the surface in square meters of the outer ducts to be isolated;
      ― Ap is the sum of the surfaces of the outer walls taken into account for the calculation of Ubât-ref.

      Rule 56 Learn more about this article...


      New air preheating equipment shall be equipped with a device stopping operation outside the heating period.

    • CHAPTER IV: CHAUFFAGE Rule 57 Learn more about this article...


      The new gaseous fuel generators providing heating shall not have a permanent watchmaker.

      Rule 58 Learn more about this article...


      1. General case.
      Subject to the provisions of Article 60, a new heating system shall be operated by local serving one or more manual shut-off devices and automatic adjustment according to the internal temperature of that room.
      However, when heating is provided by a hot water heating floor operating at low temperature, this device can be common to premises with a maximum surface area of 150 m2.
      2. Additional provisions for Joule-effect transmitters.
      The regulation of the new Joule-effect heating transmitters shall lead to a maximum regulation amplitude of 0.5 K and a maximum load drift of 1.5 K. These values are ranged to 1 K and 2.5 K for integrated wall transmitters, accumulation heating appliances and "two-wire ventilo-convectors".
      Unless the new transmitter, together with the heating system, provides a cooling function, its control device must also allow the reception of remote controls to ensure the operation in comfort, reduced, excluding freezing and stopping.

      Rule 59 Learn more about this article...


      The provisions of this section apply where the work provides for the replacement or installation of Joule-effect transmitters, or the replacement or installation of the heat generator for other heating systems.
      1. Case of emitters with Joule effect.
      Subject to the provisions of Article 60, if the heating is provided by independent electrical appliances and if the heated surface from a single point of delivery of the heating energy of the installation exceeds 400 m2 and includes several premises, the power supply of these appliances must be adjusted automatically according to the outside temperature.
      A single device can serve a maximum of 5,000 m2. However, such a device is not required if the heating is automatically stopped in case of opening of one of the openings.
      2. Cases of other systems.
      Subject to the provisions of Article 60, if the heating is provided by transmitters connected to a central generation of the heat serving a surface of more than 400 m2 comprising several premises, it shall include, in addition to the devices provided above, one or more central automatic adjustment devices of the heat supply, which is at least function of the outside temperature. A single device can serve a maximum of 5,000 m2.
      This requirement does not apply to residential buildings if the distribution network is used both for heating and the production of decentralised sanitary hot water.

      Rule 60 Learn more about this article...


      For new mixed heating facilities, sections 58 and 59 do not apply to basic heating, which shall include, regardless of the surface served, one or more automatic adjustment devices according to at least the outside temperature.
      In the event that, from a central generation, equipment is supplied for heating and hot water, the obligation described in section 59-2 applies only if the surface of the equipment is serviced above 400 m2 and has several premises.

      Rule 61 Learn more about this article...


      Any new heating system serving staggered-occupancy premises shall include a manual control and automatic programming device at least by a clock allowing:
      – a supply of heat according to the following four lines: comfort, reduced, excluding gel and stopping;
      – an automatic switching between these lines.
      When switching between two strokes the heating power shall be zero or maximum in order to minimize the duration of the transition phases.
      Such a device can only be common to premises with similar occupancy times. A single device can serve a maximum of 5,000 m2.

      Rule 62 Learn more about this article...


      Heating water distribution networks located outside or in unheated premises are provided with insulation that corresponds to a coefficient of loss, expressed in W/(m.K), less than or equal to 2.6.d + 0.2 where d is the outer diameter of the tube without insulating, expressed in meters.
      Water distribution networks must be equipped with a flow-through balancing organ in each column.
      Water distribution networks of collective heating systems must be balanced according to the new thermal characteristics of the areas served.

      Rule 63 Learn more about this article...


      The pumps of the new heating facilities shall be equipped with a device to stop them outside the heating season.

    • CHAPTER V: SANITARY CHAUDE Rule 64 Learn more about this article...


      For new accumulation electric water heaters, the maximum Qpr losses expressed in kilowatt hours per 24 hours within the meaning of NF EN 60 335-1 and NF EN 60 335-2-21 are as follows:
      ― V water heater less than 75 litres: 0.1474 + 0.0719 V2/3;
      • horizontal water heater of V greater than or equal to 75 litres: 0.939 + 0.0104 V;
      - vertical water heater of V greater than or equal to 75 litres: 0.224 + 0.00663 V2/3;
      where V is the storage capacity of the balloon in litres.

      Rule 65 Learn more about this article...


      The new gas accumulators and bath heaters must have thermal performance at least equal to European standards EN 89 for gas accumulators and EN 26 for instantaneous production heaters.

      Rule 66 Learn more about this article...


      The new prefabricated solar water heaters must have a coefficient of UA thermal losses expressed in W/K below 0.16 V1/2, where V is the nominal storage volume of the water heater expressed in litres.

      Rule 67 Learn more about this article...


      The parts maintained in temperature of the distribution of sanitary hot water are heated by insulation, the coefficient of loss, expressed in W/m.K, is at most equal to 3,3.d + 0.22, where d is the outer diameter of the tube without insulating, expressed in meters.

    • CHAPTER VI: LOCAL CLAIMS Rule 68 Learn more about this article...


      This chapter applies to premises of buildings covered byArticle R. 131-26 of the Construction and Housing Code to the exclusion of those quotedarticle R. 111-1where the general lighting system is undergoing renovation or replacement work.

      Rule 69 Learn more about this article...


      Any premises in which the occupant(s) may act on the control of the lighting shall include at least one of the following:
      – a device allowing the extinction at each exit of the local;
      – a device, possibly timed, proceeding to the automatic extinction of the lighting when the space is empty;
      – a manual device allowing the extinction from each workstation.

      Rule 70 Learn more about this article...


      Any local whose lighting control is within the purview of its management staff, even during periods of occupancy, must include a device for lighting and lighting ignition. If this device is not located in the local area, it will then have to allow to visualize the state of the lighting in this space from the place of order.

      Rule 71 Learn more about this article...


      In premises with several uses requiring very different levels of illumination for at least two uses, such as sports premises and multi-purpose rooms, a device will have to reserve to persons authorized the start-up of higher lighting at the basic level.

      Rule 72 Learn more about this article...


      In the same room, artificially illuminated points, which are placed less than 5 metres from a bay, must be ordered separately from other lighting points as soon as the total power installed in each of these positions is greater than 200 W.

      Rule 73 Learn more about this article...


      When natural lighting is sufficient, artificial lighting should not be automatically started, including a clock or presence detection device.

    • CHAPTER VII: Rule 74 Learn more about this article...


      In the case of non-residential buildings, cooled premises with a cooling system being installed or replaced as part of the work referred to in Article 4 shall be provided with specific ventilation devices.

      Rule 75 Learn more about this article...


      Access doors to a cooled area for non-residential use must be equipped with a device ensuring their closure after crossing.

      Rule 76 Learn more about this article...


      The pumps of the new cooling installations shall be equipped with a means of stopping them.

      Rule 77 Learn more about this article...


      In the case of installation or replacement of the cooling system, the new installation shall consist of one or more manual shut-off devices and automatic adjustment of the cold supply according to the inside temperature.
      However:
      ― when the cold is provided by a variable airflow system, this device can be common to premises with a maximum total surface area of 100 m2 provided that the total airflow regulation is carried out without increasing load loss;
      - when the cold is provided by a refreshing floor, this device can be common to premises with a maximum surface area of 150 m2;
      ― for the systems of "brailo-convectors two cold tubes alone", the obligation of the first paragraph is considered satisfied when each fan is served at the inside temperature and that the production and distribution of cold water are equipped with a device allowing their programming;
      ― for residential buildings and accommodation cooled by refurbishment of new air without increasing the treated flows beyond the double of the hygiene requirements, the obligation of the first paragraph is considered satisfied if the supply of cold is, on the one hand, regulated at least according to the air recovery temperature and the outside temperature and, on the other, prohibited in heating period.

      Rule 78 Learn more about this article...


      In the event of installation or replacement of the cooling system, the new system shall not heat and cool, or cool, and then heat the air, before final emission in the local area, with energy-using devices designed for heating or cooling air. This provision does not apply in case the heating is obtained by recovery on cold production.

    • CHAPTER VIII: FOLLOW-UP Rule 79 Learn more about this article...


      For buildings for use in dwellings, equipped with a heating system or the production of collective sanitary hot water serving the dwellings in horizontal distribution, one or more devices shall allow to follow the consumption of heating and sanitary hot water, possibly confused, of each dwelling.

      Rule 80 Learn more about this article...


      For non-residential buildings, if the heated surface exceeds 400 m2, one or more devices shall allow to monitor the operating time of each ventilation unit of the facility.

      Rule 81 Learn more about this article...


      For non-residential buildings, if the heated surface exceeds 400 m2, one or more devices shall allow to monitor the heating consumption, possibly confused with those of sanitary hot water, if the generator is common, and to measure the internal temperature of at least one local per part of the hot distribution network.

      Rule 82 Learn more about this article...


      If a building has premises or a set of premises to receive more than 40 beds or to serve more than 200 meals a day, one or more devices shall be used to monitor the volumic or calorific consumption of sanitary hot water of centralized equipment.

      Rule 83 Learn more about this article...


      For non-residential buildings, if the illuminated surface exceeds 1000 m2, one or more devices shall allow to monitor lighting consumption, except in the case where the electrical network is not modified and does not allow the counting to be installed.

      Rule 84 Learn more about this article...


      For non-residential buildings, if the cooled surface exceeds 400 m2, one or more devices shall allow to monitor the cooling consumption, possibly confused with those of heating if the generator is common, and to measure the inside temperature of at least one room per part of the cold distribution network.

  • PART IV: APPROVAL OF TECHNICAL SOLUTIONS Rule 85 Learn more about this article...


    A technical solution is a combination of renovation work attached to a family of buildings defined by their destination and their constructive and architectural principles, approved by the Minister responsible for construction, and deemed to ensure compliance with the provisions of headings I to III of this Order for all buildings of that family.
    The use of a technical solution can only be done using the solution in its integral form.
    Technical solutions can focus on the calculation of energy consumption, either on summer comfort or on both areas.

    Rule 86 Learn more about this article...


    The request for approval of a technical solution is addressed to the Minister responsible for construction and housing, accompanied by a study package, as set out in Appendix IV.
    An application for approval using all or part of an existing solution will require the prior agreement of the first applicant.

    Rule 87 Learn more about this article...


    The Minister responsible for construction and housing agrees the technical solution for a specified period of time after the advice of a commission of experts constituted for this purpose.
    The Commission shall issue a notice in a report after consideration of the proposed technical solution, including the following:
    ― definition of the intended family;
    ― definition and relevance of the sample on which the performance of the technical solution is verified;
    - definition of the technical solution;
    ― mode of dissemination of the technical solution to all professionals;
    • respect for the characteristics set out in title III;
    ∙ variation in the value of the relationship between Cepinitial, Cepproject, Cepref and Cepmax on the representative sample of the building family;
    ―from the value of the difference between Tic and Tic ref, on the representative sample of the building family.

  • PART V: CAS PARTICULIERS Rule 88 Learn more about this article...


    In the event that the TH-C-E ex calculation method is not applicable to an existing building, system or renovation project, a request for approval of the project or system justification method must be addressed to the Minister responsible for construction and housing. It is accompanied by a study file composed as set out in Appendix V which establishes in particular how the TH-C-E ex calculation method is not applicable to the system or construction project.

    Rule 89 Learn more about this article...


    The Minister for Construction and Housing approves the proposal after notice of a commission of experts constituted for this purpose.
    The commission shall issue a notice in a report after a review of the energy consumption of the building in the project, of the guarantees it provides in terms of summer comfort and of the consideration of the minimum characteristics defined in 1-5° of Article 12.

  • PART VI: OTHER PROVISIONS Rule 90 Learn more about this article...


    Buildings with a surface area of less than 2% of the floor surface created do not meet the requirement of 1-6° of section 12, as well as the provisions of Chapter II of Title III.

    Rule 91 Learn more about this article...


    The application of the provisions of this Order shall not jeopardize the legislative and regulatory measures taken in respect of health, safety, hygiene and security in force.

    Rule 92 Learn more about this article...


    The Director General of Urban Planning, Habitat and Construction and the Director General of Energy and raw materials are responsible, each with respect to it, for the execution of this Order, which will be published in the Official Journal of the French Republic.

  • Annex



    A N N E X E I



    DEPARTMENT

    01. Ain.

    H1c

    02. Aisne.

    H1a

    03. Allier.

    H1c

    04. Alpes-de-Haute-Provence.

    H2d

    05. Hautes-Alpes.

    H1c

    06. Alps-Maritimes.

    H3

    07. Ardèche.

    H2d

    08. Ardennes.

    H1b

    09. Ariège.

    H2c

    10. Dawn.

    H1b

    11. Aude.

    H3

    12. Aveyron.

    H2c

    13. Bouches-du-Rhône.

    H3

    14. Calvados.

    H1a

    15. Cantal.

    H1c

    16. Charente.

    H2b

    17. Charente-Maritime.

    H2b

    18. Dear.

    H2b

    19. Corrèze.

    H1c

    2A. South Corsica.

    H3

    2B. Haute-Corse.

    H3

    21. Gold Coast.

    H1c

    22. Côtes-d'Armor.

    H2a

    23. Dig.

    H1c

    24. Dordogne.

    H2c

    25. Doubs.

    H1c

    26. Drôme.

    H2d

    27. Eure.

    H1a

    28. Eure-et-Loir.

    H1a

    29. Finistère.

    H2a

    30. Gard.

    H3

    31. High-Garonne.

    H2c

    32. Gers.

    H2c

    33. Gironde.

    H2c

    34. Hérault.

    H3

    35. Ille-et-Vilaine.

    H2a

    36. Indre.

    H2b

    37. Indre-et-Loire.

    H2b

    38. Isère.

    H1c

    39. Jura.

    H1c

    40. Landes.

    H2c

    41. Far-and-Cher.

    H2b

    42. Loire.

    H1c

    43. High-Loire.

    H1c

    44. Loire-Atlantique.

    H2b

    45. Loiret.

    H1b

    46. Lot.

    H2c

    47. Lot-et-Garonne.

    H2c

    48. Lozère.

    H2d

    49. Hande-et-Loire.

    H2b

    50. Channel.

    H2a

    51. Marne.

    H1b

    52. High-Marne.

    H1b

    53. Mayenne.

    H2b

    54. Meurthe-and-Moselle.

    H1b

    55. Meuse.

    H1b

    56. Morbihan.

    H2a

    57. Moselle.

    H1b

    58. Nièvre.

    H1b

    59. North.

    H1a

    60. Oise.

    H1a

    61. Orne.

    H1a

    62. Not Calais.

    H1a

    63. Puy-de-Dôme.

    H1c

    64. Pyrenees-Atlantiques.

    H2c

    65. High Pyrenees.

    H2c

    66. Pyrenees-Orientales.

    H3

    67. Bas-Rhin.

    H1b

    68. Upper Rhine.

    H1b

    69. Rhone.

    H1c

    70. Haute-Saône.

    H1b

    71. Saône-et-Loire.

    H1c

    72. Sarthe.

    H2b

    73. Savoie.

    H1c

    74. Haute-Savoie.

    H1c

    75. Paris.

    H1a

    76. Seine-Maritime.

    H1a

    77. Seine-et-Marne.

    H1a

    78. Yvelines.

    H1a

    79. Two-Sèvres.

    H2b

    80. Sum.

    H1a

    81. Tarn.

    H2c

    82. Tarn-et-Garonne.

    H2c

    83. Var.

    H3

    84. Vaucluse.

    H2d

    85. Vendée.

    H2b

    86. Vienna.

    H2b

    87. Upper Vienna.

    H1c

    88. Vosges.

    H1b

    89. Yonne.

    H1b

    90. territory of Belfort.

    H1b

    91. Essonne.

    H1a

    92. Hauts-de-Seine.

    H1a

    93. Seine-Saint-Denis.

    H1a

    94. Val-de-Marne.

    H1a

    95. Val-d'Oise.

    H1a


    A N N E X E I
    DEFINITION AND DETERMINATION OF EXHIBITIONS
    OF BAIES IN THE BRUIT OF TRANSPORT INFRASTRUCTURES


    The class of exposure of a bay to noise from an infrastructure depends on:
    ―from the classification of the ground transportation infrastructure in the vicinity of the construction, given by a prefectural order taken under the Decree No. 95-21 of 9 January 1995 relating to the classification of land transport infrastructure and amending the urban planning code and the code of construction and order dated 30 May 1996 relating to the classification of land transport infrastructure and the acoustic isolation of residential buildings in the areas affected by noise;
    the situation of the bay in relation to these infrastructures;
    ―the situation of the building in relation to areas A, B, C or D of the noise exposure plan (PEB) of the airport approved by a prefectural order taken under articles R. 147-5 to R. 147-11 of the urban planning code,
    in the following manner and conventions:


    Definition of an obstacle to exposure


    An obstacle to exposure is a mask to the spread of the noise (building, screen, earth butt...) having an altitude greater than or equal to that of the exposed floor.
    When the obstacle is more than 250 metres from the bay under review and to take into account the curvature effect of the propagation of noise (nightly thermal reversal), 10 metres are added to the minimum altitude required to take into account the obstacle for residential premises.


    Definition of an infrastructure view from a bay


    The view of the infrastructure from a bay is defined as follows:
    A direct view is defined for an infrastructure plan view of more than 30° after deduction of barriers to exposure. This is the case of side faces of a building without a mask.
    A partial view is defined for a horizontal view of the infrastructure below 30°, after deduction of obstacles to exposure.
    There is a masked view of the infrastructure when the infrastructure cannot be seen, taking into account obstacles to exposure, from the bay. When the obstacles to this view are of insufficient height within the meaning of the definition of an "hazard to exposure" to form a "shown view", but that they allow to remove any direct vision of the infrastructure, the view is then considered partial.
    A rear view is defined for the rear façade of the building.
    A protected rear view is defined for a bay located in a remote rear façade of the building and any vis-à-vis façade that would be directly exposed to the noise of the infrastructure.
    A view of a closed courtyard can be reached for a closed courtyard on its four sides, without porch or open passage exposed to noise.


    Determination of exposure class
    at the sound of a bay of a building


    1. Depending on the category of infrastructure near which the building or part of the building is built, and to the extent that this building is located at a distance greater than the maximum distance taken into account the transport infrastructure indicated below, all of its bays are then in the BR1 class of noise exposure.




    SITUATION OF BUSINESS
    leading to a classification
    of these bays in BR1

    Infrastructure Category

    1

    Distance greater than 700 m.

    of Land Transport:

    2

    Distance over 500 m.


    3

    Distance greater than 250 m.


    4

    Distance over 100 m.


    5

    Distance greater than 30 m.

    Aerodrome


    Out of the noise exposure plan.


    2. In other cases, the bay's exposure class is determined in the tables given below from one part of the areas defined in the aerodrome noise exposure plan for air transport noises, and on the other hand from the infrastructure category, the distance from the infrastructure to the façade and the angle under which it is seen by the bay for ground transportation infrastructure.
    In the case of several infrastructure, the most unfavourable noise exposure class will be retained.
    3. In the absence of a detailed determination, the BR class of a façade bay is the highest class of the bays of this façade.

    CATEGORY
    infrastructure
    DISTANCE OF THE BAIE
    to Land Transport Infrastructure

    Category 1

    15-50 m

    50-160 m

    160-300 m

    300-460 m

    460-700 m

    1,700 m

    Category 2

    0-25 m

    25-80 m

    80-250 m

    250-370 m

    370-500 m

    1 500 m

    Category 3


    0-30 m

    30-100 m

    100-160 m

    160-250 m

    1 250 m

    Category 4


    0-10 m

    10-30 m

    30-60 m

    60-100 m

    1 100 m

    Category 5



    0-10 m

    10-20 m

    20-30 m

    1 30 m

    View of the infrastructure from the bay:







    direct view

    BR3

    BR3

    BR3

    BR2

    BR2

    BR1

    partial view

    BR3

    BR3

    BR2

    BR2

    BR1

    BR1

    masked view or rear view

    BR3

    BR2

    BR2

    BR1

    BR1

    BR1

    protected rear view

    BR2

    BR2

    BR1

    BR1

    BR1

    BR1

    view on closed courtyard

    BR2

    BR1

    BR1

    BR1

    BR1

    BR1






    Location of the building in the airfield noise exposure plan
    Area A
    Area B
    Area C
    Area D
    Outside area

    All views

    BR3

    BR3

    BR3

    BR2

    BR1



    A N N E X E I I
    DEFINITIONS
    Altitude


    The altitude of a building is that of its main access door.


    Bay


    A bay is a measured opening in an exterior wall used for lighting, passage or ventilation. A transparent or translucent wall is considered a bay.


    Categories CE1 and CE2


    A room is of category CE2 if it is equipped with a cooling system and if one of the following conditions is met:
    - simultaneously, the space is located in a residential or accommodation area, its bays are exposed to noise BR2 or BR3, and the building is built in climate zone H2d or H3 at an altitude below 400 metres;
    - simultaneously, the space is located in a teaching area, its bays are exposed to noise BR2 or BR3, and the building is built in climate zone H2d or H3 at an altitude below 400 metres;
    - the local is located in an office area, and its bays are exposed to noise BR2 or BR3 or are not working under other regulations;
    - the premises is located in an area for office use, and the building is constructed either in H1c or H2c climate zone at an altitude below 400 metres, or in H2d or H3 climate zone at an altitude below 800 metres;
    the local is located in a commercial area;
    ― the local is located in a multi-purpose entertainment or conference or room area;
    ― the local is located in a health facility area.
    Other premises are category CE1.
    An area or part of the area is of category CE2 if all non-passive occupation premises are of category CE2. It is category CE1 in other cases.


    General lighting


    General lighting is a uniform lighting of a space without taking into account the special needs in certain locations.


    Curtain facade


    Light facade consisting of an assembly of frame and carpentry profiles and opaque, transparent or translucent filling elements. It can have one or more walls and is entirely located in front of a floor nose.


    Closure


    With the exclusion of devices that do not reduce deferrals such as grids, bars, store curtains, any mobile device, commonly known as shutter, persian or jealousy, used to close the access to a window, a window window, a window holder or a door, is a closure.


    Daily inertia


    Daily inertia is the inertia used to calculate the damping of internal temperatures over a period of twenty-four hours.


    Sequential inertia


    The sequential inertia is the inertia used in summer comfort to calculate the amortization of internal temperatures over a twelve-day period.


    Local


    A local is a completely separate volume from the outside or other volumes by horizontal and vertical, fixed or mobile walls.


    Heated area


    A local is said to be heated when its normal temperature during occupancy is greater than 12 °C.


    Premises for intermittent gathering of persons


    A local is defined as being used to gather people intermittently, if the terms of use of the local are random in terms of occupation or non-occupation and in terms of number of occupants. The office building meeting rooms, the public meeting rooms are considered to be part of this category. The showrooms, landscape offices, restaurant rooms are not considered to belong to them.


    Close Mask


    A nearby mask is an architectural barrier to solar radiation, linked to the building studied, such as berry paintings, overhangs or lateral overflows.


    Discontinuous occupation, continued occupation


    A building, or part of a building, is said to be in discontinuous occupation if it meets the following two conditions:
    ―it is not intended for hosting people;
    ― each day, normal occupancy temperature may not be maintained for a continuous period of at least ten hours.
    Building parts or buildings that do not meet these two conditions are said to be in continuous occupation.


    Household occupation of a local


    A passenger occupancy room is a space that per destination does not involve a stay for an occupant greater than half an hour.
    This is the case, for example, of traffic and maiming practices. On the other hand, a kitchen or a hall with a workstation is not considered to be a temporary occupation.


    Guidance


    The north orientation is any orientation between the north-east and north-west, including the north-east and north-west directions.
    The orientation is any orientation between the north-east and the south-east through the east, not including the north-east and south-east directions.
    The south orientation is any orientation between the south-east and the south-west, including the south-east and south-west directions.
    The west orientation is any orientation between the south-west and the north-west through the west, not including the south-west and north-west directions.


    Vertical or horizontal


    A wall is said vertical when the angle of this wall with the horizontal plane is equal to or greater than 60 degrees, it is said horizontal when this angle is less than 60 degrees.


    Thermally isolated opaque light


    An opaque wall is said to be thermally insulated if its thermal transmission coefficient U is not greater than 0.50 W/m2.K.


    Transparent or translucent weight


    A wall is said to be transparent or translucent if its luminous transmission factor (without possible mobile protection) is equal to or greater than 0.05. Otherwise, it is said opaque.


    Plancher bas


    A low floor is a horizontal wall with only the upper face on a heated space.


    High floor


    A high floor is a horizontal wall with only the lower face on a heated space.
    An unappointed floor or a terrace roof are, for example, high floors.


    Intermediate


    An intermediate floor is a horizontal wall whose lower and upper sides overlook a heated space.


    Cooling system


    A cooling system is a cold production equipment by thermodynamic machine associated with cold transmitters intended for people's comfort.


    Internal temperature


    The internal temperature for the calculation of the coefficient C is the indoor air temperature considered uniform in the area studied.
    The mean radiating temperature is the average, weighted by the wall surfaces, from the inner surface temperatures of the walls in contact with the air of the area studied.


    Operational temperature


    The temperature within the meaning of section R. 111-6 of the construction and housing code is the operating temperature, defined as the mean between the mean radiating temperature and the air temperature of the area considered uniform.
    The mean radiating temperature is the average, weighted by the walls, from the inner surface temperatures of the walls in contact with the air of the area studied.


    Vitrine


    A showcase is a glass wall reserved only for the exhibition of objects, products or services intended for sale.


    Heated volume


    The heated volume is the volume delimited by the surfaces of the walls taken into account in calculating the Ubât coefficient.


    A N N E X E I V
    SCHOOL FOR THE PROPOSAL
    TECHNICAL SOLUTIONS
    1. Subject


    This annex describes the content of the study file to be prepared in support of a technical solution proposal submitted to the Minister for Construction and Housing.


    2. Elements to be provided by the applicant


    The applicant provides:
    – the description of technical solutions in the form provided for its dissemination. This document includes the input data definition format to be used to justify a given project;
    ― the area of application covered by the technical solution: in particular can be specified the use of buildings, the limits of their massing, the ratios of glass parts, the winter and summer climate zones, the conditions of exposure to noise and the energy systems for heating, ventilation and hot water sanitary;
    ― the elements to ensure that the user of a technical solution can easily and safely apply this technical solution;
    ― the elements to ensure that the application of each technical solution is consistent with the minimum thermal characteristics described in heading III;
    – a calculation file justifying the claimed performance levels for the technical solution in terms of either energy consumption, or summer comfort, or both areas, according to the intended scope.


    3. Variant compared to an already approved solution


    In the event that a technical solution would be a variant of an already approved technical solution, the applicant would refer to the technical solution and would be able to provide only the complementary elements to those given during the previous application for approval.
    The shape of the variant (page, typography...) and its structure will have to be consistent with those of the already approved technical solution so as to avoid any potential confusion when using the variant.
    In case the author of the variant is different from that of the original technical solution, the written agreement of the latter will be attached.


    4. Composition of the calculation file
    concerning energy consumption


    The energy performance calculation package includes for each proposed technical solution:
    I. - The thermal characteristics claimed for the various components of the technical solution as described. In point 6, an indicative list of the parameters for which the applicant must indicate the characteristic claimed, if any, according to the scope of the technical solution.
    II. - The default values used for calculations.
    III. - The calculation of Cepinitial, Cepproject and Cepref coefficients for a series of buildings representative of the application areas covered by the technical solution.
    IV. - The calculation for each building of this series of energy performance, Perfréf and Perfmax, given by the following formulae:


    Perfréf = 100*(Cepréf ― Cep projet)/Cepref
    Perfmax = 100*(Cepmax-Cepheating, cooling, hot water production)/Cepmax


    V. - The minimum and maximum average values of envelope and energy performance.
    VI. - A histogram with the absorption of enveloped and energetic performances and the number of typical buildings with this level of performance.


    5. Composition of the calculation file
    concerning summer comfort


    The energy performance calculation package includes for each proposed technical solution:
    I. - The thermal characteristics claimed for the various components of the technical solution as described. In point 6, an indicative list of the parameters for which the applicant must indicate the characteristic claimed, if any, according to the scope of the technical solution.
    II. - The default values used for calculations.
    III. - Calculation of Tic internal temperatures and Ticréf internal temperatures for a series of premises or buildings representative of the areas of application covered by the technical solution.
    IV. ∙ A histogram with Tic deviations ― Ticréf and ordering the number of representative premises or buildings with this level of performance.


    6. Claimed features


    The applicant must provide the value(s) used for each input data from the calculation of Cepinitial, Cepproject and Cepref for energy consumption, and Tic and Tic ref for summer comfort.


    A N N E X E V
    SCHOOL FOR SPECIFIC
    1. Subject


    This annex describes the content of the study file for construction systems or projects for which the methods of calculation Th-C ex or Th-E ex are not applicable, provided in support of the application for approval with the Minister for Construction and Housing.


    2. Elements to be provided by the applicant


    The request can be made either for a particular building project or for the inclusion of a particular system in several building projects.


    2.1. Application for a specific building project


    After indicating the calculation method that is not applicable, the applicant must provide:
    - the design of the construction project concerned;
    - the list of input data for parts of the calculation method that are applicable;
    a detailed description of the reasons that make the calculation method unapplicable to other parties;
    an explicit argument in which the project respects the principles at the basis of this regulation.
    This argument must be used to justify the alleged level of performance of the operation, therefore the compliance with all the requirements of the regulations, both in respect of land guards, the limitation of summer discomfort and the limitation of conventional energy consumption.


    2.2. Application for a particular system
    usable in several building projects


    After indicating the calculation method that is not applicable, the applicant must provide:
    ― a description of the system considered accompanied by elements to assess its thermal performance (test reports, measurement campaigns...) in particular with a view to justifying the adaptation proposal for the calculation;
    a description of the scope of this system;
    - the list of input data for parts of the calculation method that are applicable;
    a detailed description of the reasons that make the calculation method unapplicable to other parties;
    – an adaptation proposal to make the calculation for non-applicable parties. The proposed adaptation may relate either to the proposal of rules of entry by equivalence of input data of the TH-C-E ex calculation method, or to the proposal for processing of the output data of the calculation, together with an example of digital application.
    In addition, the applicant may propose an adaptation of the algorithms of the TH-C-E ex calculation method.


    A N N E X E VI
    THERMICAL STANDARDIZED SYSTEM


    1. For each building that is justified under the terms of the second paragraph of Article 16, the thermal study synthesis shall include:
    – the values of the initial Cep, if its calculation has been made, and the values of Cep project, Cepref and Cepmax of the building in kWh of primary energy per square meter of SHON;
    - the value of the building SHON used in the calculation;
    - the value of the useful surface of the building within the meaning of the TH-C-E ex method;
    ― the values in kWh of final energy and kWh of primary energy of conventional energy consumption of the building corresponding to heating, cooling, production of sanitary hot water, lighting, ventilation auxiliaries, heating auxiliaries, sanitary hot water supply auxiliaries and cooling auxiliaries, and for each of them the type of energy used, as well as the possible inputs
    - annual average occupancy and occupancy rates for:
    – leakage failure;
    ― air intakes;
    - opening of windows;
    - ventilation system;
    - if the calculation has been performed, the values of Tic and Ticréf of each zone of type CE1;
    – the values of Ubât and Ubâtréf of the building in W/m2.K and the total W/K losses of the building and reference;
    ― the decomposition of the Ubât calculation showing for each wall and linear category, the coefficient has taken into reference for the calculation of Ubâtréf according to articles 18 and 21, the total surface or linear and the average value of the surf or linear transmission;
    ― for each building area and group project, all characteristic data as defined in the TH-C-E ex calculation rule;
    The thermal study synthesis must also be able to present the sensitivity of the Cepproject coefficient of the building to typical variations of the following parameters:
    – Ubât diminished by 10%;
    - air permeability reduced by 0.5 m3/(h.m2) (Q4Pa within the meaning of TH-C-E ex) if the initial value is greater than 0.5 m3/(h.m2);
    ― solar and luminous intakes by berries reduced by 20%;
    – installed lighting power decreased by 10%;
    – total power of fans decreased by 20%;
    • 1 K upgraded hot transmitter time variable class;
    • 1 K upgraded temperature change class of cold emitters.
    2. For each building subject to justification by technical solution in accordance with the terms of the second paragraph of Article 12, the synthesis of thermal study shall specify all the data used and the results obtained to justify compliance with the technical solution from both the scope and the technical and architectural provisions to be implemented.


Done in Paris, June 13, 2008.


Minister of State, Minister of Ecology,

of energy, sustainable development

for the Minister and by delegation:The Director General

of energy

and raw materials,

P.-F. Chevet

Director General

urban planning,

habitat and construction,

E. Crepon

Minister of Housing and City,

For the Minister and by delegation:

Director General

urban planning,

habitat and construction,

E. Crepon


Download the document in RTF (weight < 1MB) Extrait du Journal officiel électronique authentifié (format: pdf, weight : 1.56 MB) Download the document in RDF (format: rdf, weight < 1 MB)