Xinjiang Uyghur Autonomous Region, Cotton Fire Safety Management

Original Language Title: 新疆维吾尔自治区棉花消防安全管理办法

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$40 per month.
(November 28, 2007 offi 47th Executive session on November 30, 2007, people's Government of Xinjiang Uygur Autonomous Region announced the 150th since as of January 1, 2008) first in order to strengthening cotton fire safety management, protection and personal property security, promote economic development, according to the People's Republic of China fire protection law, the Xinjiang Uyghur autonomous region, the Fire Services Ordinance and the relevant laws and regulations, combined with State practice,
    These measures are formulated.
    Second autonomous region within the administrative area of cotton purchasing stations, factories, warehouses, open-air storage yard, transfer station and stacked cotton of cotton spinning enterprises sites (hereinafter referred to as cotton purchasing, processing, and storage units), these measures shall apply.
    Temporary storage of cotton collection, storage, and other places, in accordance with the measures implemented.
    Third Governments at all levels of public security organs and the public security fire control institutions responsible for the administration of cotton fire safety supervision and management of the work. Fourth cotton fire safety work carry out the policy of putting prevention first and combining prevention and fire protection safety responsibility system.
    Cotton purchasing, processing, and storage units of the legal representative or principal responsible are the fire safety unit responsible. Article cotton fire safety work in Governments at all levels should strengthen leadership.
    Cotton production and processing season, local people's Governments should urge the departments concerned to carry out fire safety education, organizations conduct fire control safety inspection. Sixth new construction, renovation or expansion of cotton, processing units, storage location, and fire-fighting equipment and the acquisition, processing and storage of settings, should comply with national fire protection technical specification requirements.
    Fire safety design for the examination shall be approved by public security fire control institutions, before construction; fire control acceptance after completion shall be approved by public security fire control institutions, may be put into use.
    Article building, rebuilding, expansion of cotton cotton stacking arrangement, processing, storage units and fire-fighting water supply system shall comply with the annex to this way of the cotton stacking arrangement and provision of fire water supply system of fire safety norms.
    Prior to the introduction of these measures build cotton processing, cotton stacking storage units arrangements and of fire water supply system does not meet the provisions of the preceding paragraph shall transform; difficult to reform, the public security organs and the public security fire control institutions shall guide the appropriate protective measures can be taken.
    Article eighth cotton purchase, processing, storage units should strengthen the construction of fire-fighting facilities, establish and improve the system of fire safety, implementation of the fire safety system, clear post fire safety responsibilities, determining fire safety responsibilities of each post, and fire safety improvement environment. Nineth cotton purchase, processing, storage unit, composed of workers needed to establish volunteer fire brigade, fire skill drills on a regular basis, improve the ability of extinguishing themselves.
    Provisions of laws and administrative regulations shall establish a full-time fire department, from its provisions. Article tenth cotton purchase, processing, storage units shall formulate fire control safety education program, fire safety training for staff.
    New staff (including permanent, temporary and seasonal workers and other staff) should be subject to internal fire safety training, examinations before they can post.
    11th cotton purchase, processing, storage units should be in accordance with the relevant regulations of the State fire motor pump, fire hydrants, fire facilities, equipment, and other fire fighting tools and designate a management, regular inspections, maintenance, winter anti-freezing measures to ensure normal use.
    12th cotton purchase, processing, storage units production plant, warehouse, distribution and other key sites prohibit the use of open fire; other parts requires the use of fire, this unit with fire management system shall be in accordance with the procedures, and to take effective preventive measures.
    Cotton purchasing, processing and storage areas outside of maintenance warehouse, loading and unloading installation and use of fire in the staff lounge, shall comply with the fire safety requirements, and approved by the fire safety of the unit responsible, rigorous management. 13th cotton purchase, processing, storage units should be strictly enforced doormen and night patrol system.
    Yard, warehouses for cotton processing factory should set clear and fire safety signs and warning signs prohibiting smoking. Prohibited to carry kindling into cotton yard area, warehouse and factory area.
    Motor vehicle into yard of cotton area, warehouse and processing zone, should be checked, prevent into kindling.
    14th article handling cotton of motor vehicle car should comply with following provides: (a) distribution loaded meet national standards of exhaust sparks out device, row tracheal side shall not near cotton Duo; (ii) in fixed locations parking, shall not in library district within refueling or repair vehicles; (three) into cotton yard district, and warehouse district and factory district job of battery, and forklift, and forklift and the Shang duo with of crane, should take prevent played sparks of security.
    15th cotton production should be the use of advanced technology and equipment, drive, moving parts of machinery and equipment should be set up security, security cover or take other protective measures, prevent friction in the machine burst into flames. 16th cotton factory, workshop should be cleaned on a regular basis, keep the environment clean to prevent cotton, dust winding equipment.
    Pipelines and trenches occlusion and containment measures should be taken to prevent cotton, dust from entering.
    17th open, half open seed cotton stacking and near-field (library) area of the wall, lint stack next to the railway, you must use a flame-resistant tarpaulin thatch.
    Article 18th cotton purchase, processing, storage and fire power unit electrical wiring should be the secondary power supply, electricity lines underground cables should be used, internal laying of distribution lines must wear a metal tube or flame-resistant tube.
    Stacked unginned cotton electrical machinery protection switch should be used, mobile cable should take measures to prevent rolling, designated personnel for on-site childcare, and regularly conduct insulation inspection.
    Cotton processing plant should be explosion-proof and dust-proof type lighting lamps and switches used for yard outdoor light fixtures, protective lighting should be used. 19th wires and electrical equipment should be undertaken by the special operator's license of electrical installation, inspection, repair and maintenance.
    Electrician should strictly comply with the electrical operation, insulation electrical equipment should be conducted regularly every year.
    Article 20th cotton processing, storage units should be in accordance with the national lightning protection design specifications, equipment lightning protection, testing on a regular basis, to ensure effective use.
    Article 21st Meteorological Department forecast wind of up to level 5, cotton processing, storage units should strengthen fire prevention, fire warning and, if necessary, should stop purchasing and processing activities.
    Weather forecasters in winds of 7 or above, local people's Governments of cotton processing, storage units and issuing a fire of adjacent factories, residential areas, and organized public security organs and the public security fire control institutions, safety, and other departments to supervise and inspect cotton purchase, processing, storage units should be organized 24-hour inspection by specialized personnel.
    22nd levels of people's Governments and relevant departments to cotton have made outstanding achievements in fire safety management units and individuals that recognize and reward.
    23rd violates these rules, should be given administrative punishments according to law, in accordance with the People's Republic of China fire protection law, the Xinjiang Uyghur autonomous region, the Fire Services Ordinance the relevant provisions of the penalties constitutes a crime, criminal responsibility shall be investigated according to law.
    24th public security organs and abuse their powers, neglect their duties, engages in public security fire control institutions, the units or the relevant competent authorities shall be given administrative sanctions constitutes a crime, criminal responsibility shall be investigated according to law. 25th article this way come into force on January 1, 2008.

    December 5, 1997 the municipality 75th cotton fire safety in Xinjiang Uygur Autonomous Region promulgated and implemented the regulations repealed simultaneously. Accessories: cotton stacking arrangement and fire water supply system of fire safety norms 1. open yard more than 5000 tons of cotton total acquisition, processing, storage units, should be divided into the yard, yard between fire separation, of not less than 15m.
    Cotton stacking separately in between yard adjacent to the thatch with a tarpaulin.
    2. open, half open cotton cotton within the yard duo with spacing between field fence not less than 10m.
    Stacking open, half open seed cotton and lint fire separation between the stacks, not less than 35m.
    3. stack layout 3.1. open seed cotton stacking each mound covers an area of not more than 340m2, Duo high above 6m, Duo duo between fire separation, and not less than 8M.
    3.2. open lint stacking each mound covers an area of not more than 240m2, Duo high above 8M, Duo duo between fire separation, and not less than 4m.
    3.3. the lint between the stacks in the warehouse should set aside the necessary channels, main channel width not less than 2m, other channel of a width of not less than 1.5M stacker and wall distance not less than 0.5M, and column distance not less than 0.2m, and the beam at a distance not less than 1M.
    4. the water supply system 4.1. cotton purchasing, processing and storage unit of fire water supply system of high pressure and temporary high pressure water supply system should be used, maximum water supply pressure should ensure total water use pipes, water gun in the most unfavourable location, its full water not less than 10m.
    Outdoor fire water supply pipe diameter not less than DN100.
    Pumps for high pressure and temporary high pressure water supply system, you should set up a standby power supply.
    4.2. fire hydrant in an outdoor setting, should be used in underground fire hydrant fire hydrant or a drainage function of the ground.
    Underground fire hydrant fire hydrant selected for their 2 DN65, 2 Pan, 2 multifunctional water gun.
    Outdoor fire hydrant should set the logo.
                          4.3. water tank Setup should meet the requirements of national fire protection technical specification and set for fire engine water intake or take the wellhead.