223. Regulation of the Federal Minister for Economic Affairs, Family and Youth, with which the Electrical Engineering Ordinance 2002 is amended (Electrotechnic Ordinance 2002/A2-ETV 2002/A2)

Pursuant to Sections 2, 3 (3), 3 (3), 3 (11), 4 (2), 5 (2) and 7 (2), (5) and (6) of the Electrical Engineering Act 1992-ETG 1992, Federal Law Gazette (BGBl). No. 106/1993, in the version of the Federal Law BGBl. I n ° 136/2001, as well as Section 181 (2) of the MinroG MinroG Act, BGBl. I n ° 38/1999, as last amended by the Federal Law BGBl. I n ° 115/2009, respectively, in conjunction with the Federal Ministries of the Federal Republic of Germany, 2009, BGBl. I No 3/2009, shall be ordered:

The regulation of the Federal Minister for Economic Affairs and Labour on the safety, normalization and typing of electrical equipment and equipment as well as other installations in the hazard and disturbance range of electrical installations (electrical engineering regulation) 2002-ETV 2002), BGBl. II No 222/2002, as amended by the BGBl Regulation. II No 33/2006, shall be amended as follows:

1. § 2 para. 2 reads:

" (2) The BGBl 2002 Annex I of the ETV. II No 222/2002, as amended by BGBl. II No 33/2006, binding and in the annexes to ETV 1993, BGBl. No 47/1994, on ETV 1996, BGBl. No 105/1996, as amended by BGBl. No 575/1996, and ETV 2002, BGBl. II No 222/2002, as amended by the BGBl Regulation. II No 33/2006, printed SNT rules remain binding, with the exception of those in the Annex II , the liability of which shall be repealed. "

2. In accordance with § 7, the following § 7a is inserted:

" § 7a. For the rental of an apartment according to § 2 paragraph 1 MRG, BGBl. No 520/1981 igF, it must be ensured that the electrical installation of the dwelling corresponds to the provisions of the ETG 1992; in the case of installations which do not have any additional protection in accordance with ÖVE/ÖNORM E 8001-1:2000-03-01, as amended by ÖVE/ÖNORM E 8001-1/A1:2002-04-01, ÖVE/ÖNORM E 8001-1/A2:2003-11-01, ÖVE/ÖNORM E 8001-1/A3:2007-10-01 and ÖVE/ÖNORM E 8001-1/A4: 2009-04-01, is, without prejudice to the existing plant condition, the protection of persons in the electrical system by the Installation of at least one fault current circuit breaker with a nominal fault current of not more than 30 mA, immediately in front of the line protection equipment located in the home. If there is no appropriate documentation available, the tenants can the tenant of the apartment does not assume that the electrical installation meets these requirements. "

3. § 9 reads:

" § 9. (1) It is the SNT regulations ÖVE/ÖNORM EN 60335-1 and their amendments (no. 69 of Annex I) only for joint application with the SNT regulation ÖVE/ÖNORM EN 60335-2-76.

(2) Electrical installations within the scope of the SNT rules listed in Annex III (1) to (10) shall, from the date of entry into force of this Regulation, be planned in accordance with these SNT rules and, at the latest as from 1 January 2011, under these SNT rules. "

4. § 10 reads:

" § 10. (1) Insofar as § 9 is not determined otherwise,

1.

the application of the Annex II of this Regulation, with the exception of Z 1, 22, 23, 28, 30, 31, 32, 57 and 58 specified therein, or five years from the date of entry into force of this Regulation, and

2.

the application of the Annex II of the SNT provisions listed in this Regulation: Z 1, 22, 23, 28, 30, 31, 32, 57 and 58, until 31 December 2010; and

3.

the application of the provisions of Annex II of the ETV 2002, BGBl. II No 222/2002, as amended by the BGBl Regulation. II No 33/2006, listed SNT rules, except for those indicated in Z 23, 27, 28, 39, 40 and 41, and until 29. January 2011 allowed; the application of Z 23, 27, 28, 39, 40 and 41 is not allowed. "

(5) The following paragraph 3 is added to § 12 (2):

" (3) The BGBl Regulation. II No 223/2010 has been complied with in accordance with the provisions of Directive 98 /34/EC, OJ L 327, 28.12.1998 No. OJ L 204, 21.07.1998 p. 37, as amended by Directive 98 /48/EC, OJ L 201, 31.7.1998, p. No. OJ L 217, 05.08.1998 p. 18, notified (notifying number 2010 /139/A). "

6. Annexes I, II and III are:

" Annex I

Summary list of mandatory electrotechnical safety regulations and rules on normalization and typing (SNT regulations)

Note: SNT provisions of this section, which are not printed in Annex III, are given in Annex III to one of the following Regulations:

-Electrical Engineering Ordinance 1993, BGBl. No 47/1994;

-Electrical Engineering Ordinance 1996, BGBl. No 105/1996;

-Electrical Engineering Ordinance 2002, BGBl. (II) No 222/2002;

-Regulation amending the Electrotechnical Ordinance 2002, BGBl. II No 33/2006.

I. Austrian regulations for electrical engineering

No.

Label

Title

1

ÖVE-E 36/1970

Construction and operation of electrical fishing facilities (excluding § 10.5)

2

ÖVE/ÖNORM E 1100-2: 2005-05-01

Standard Voltages-Part 2: Rated Voltages for Low Volts Power Distribution Systems

3

ÖVE/ÖNORM E 8001-1:2000-03-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 1: Terms and protection against electric shock (protective measures)

4

ÖVE/ÖNORM E 8001-1/A1:2002-04-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 1: Terms and protection against electric shock (protective measures) (amendment)

5

ÖVE/ÖNORM E 8001-1/A2:2003-11-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 1: Terms and protection against electric shock (protective measures) (amendment)

6

ÖVE/ÖNORM E 8001-1/A3:2007-10-01

Erection of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: Terms and protection against electric shock (protective measures) (amendment)

7

ÖVE/ÖNORM E 8001-1/A4:2009-04-01

Erection of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: Terms and protection against electric shock (protective measures) (Amendment + corrigendum 1)

(excluding section 10.2.2.4)

8

ÖVE/ÖNORM E 8001-1-23:2000-12-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 1-23: protective measures-protection against thermal influences

9

ÖVE/ÖNORM E 8001-1-24:2006-01-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 1-24: protective measures-protection against undervoltage

10

ÖVE/ÖNORM E 8001-2-30:2008-12-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 2-30: switchgear and distributors

11

ÖVE/ÖNORM E 8001-2-31:2003-01-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 2-31: activation, disconnection and switching-requirements, selection and use of equipment

12

ÖVE/ÖNORM E 8001-2-31/AC1:2004-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 2-31: activation, disconnection and switching-requirements, selection and use of equipment (Corrigendum)

13

ÖVE/ÖNORM E 8001-2-39:2008-08-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 2-39: busbar systems

14

ÖVE/ÖNORM E 8001-3-41/A1:2002-07-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 3-41: Nature, dimensioning and laying of lines and cables-Design of cables and cables in mechanical and electrical respects-Overcurrent protection (Change)

15

ÖVE/ÖNORM E 8001-3-41/A2:2004-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 3-41: Nature, dimensioning and laying of lines and cables-Design of cables and cables in mechanical and electrical respects-Overcurrent protection (Change)

16

ÖVE/ÖNORM E 8001-4-44:2001-02-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-44: Completed electrical facilities

17

ÖVE/ÖNORM E 8001-4-45:2000-12-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-part 4-45: humidity and wet areas and spaces and facilities in the open air

18

ÖVE/ÖNORM E 8001-4-50:2001-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-50: Fire-prone spaces

19

ÖVE/ÖNORM E 8001-4-51:2004-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-51: Current circuits with rated voltages up to ~ 1000 V in switching fields with nominal voltages above 1 kV (low-voltage circuits in high-voltage switching fields)

20

ÖVE/ÖNORM E 8001-4-56:2003-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-56: Electrical installations in agricultural and hortic-building facilities

21

ÖVE/ÖNORM E 8001-4-58:2001-05-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-58: Construction constructions from or with combustible building materials as well as hollow walls

22

ÖVE/ÖNORM E 8001-4-95:2008-12-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-part 4-95: lifts

23

ÖVE/ÖNORM E 8001-4-714:2003-10-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4-714: Requirements for premises, rooms and installations of special kind-lighting systems outdoors

24

ÖVE/ÖNORM E 8001-4-753:2009-04-01

Erection of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 4-753: Electrical heating systems with heating lines and surface heating elements

25

ÖVE/ÖNORM E 8001-6-61:2001-07-01

Erection of electrical installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 6-61: Tests-Initial tests

26

ÖVE/ÖNORM E 8002-1:2007-10-01

High-power plants and safety power supply in construction sites for human gatherings-Part 1: General

27

ÖVE/ÖNORM E 8002-2:2007-10-01

High-power plants and safety power supply in building facilities for human gatherings-Part 2: Event venues

28

ÖVE/ÖNORM E 8002-3:2002-11-01

High-power plants and safety power supply in construction sites for human gatherings-Part 3: sales outlets and exhibition venues

29

ÖVE/ÖNORM E 8002-4:2002-11-01

High-power plants and safety power supply in construction sites for human gatherings-Part 4: high-rise buildings

30

ÖVE/ÖNORM E 8002-5:2002-11-01

High-power plants and safety power supply in construction sites for human gatherings-Part 5: Pubs

31

ÖVE/ÖNORM E 8002-6:2002-11-01

High-power plants and safety power supply in construction sites for human gatherings-Part 6: Large-scale garages

32

ÖVE/ÖNORM E 8002-8:2007-10-01

High-power plants and safety power supply in construction facilities for human gatherings-Part 8: Flying buildings as venues, sales outlets, exhibition venues or shanks and dining economies

33

ÖVE/ÖNORM E 8002-9:2002-11-01

High-power plants and safety power supply in building facilities for human gatherings-Part 9: Schools

34

ÖVE/ÖNORM E 8007 :2007-12-01

High-power plants in hospitals and medical-use rooms outside hospitals

35

ÖVE/ÖNORM E 8014-1:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: General requirements and terms

36

ÖVE/ÖNORM E 8014-2:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 2: Fundamenterder

37

ÖVE/ÖNORM E 8014-3:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 3: Special features of grounding systems in buildings with special EMC requirements of information technology facilities

38

ÖVE/ÖNORM E 8065 :2008-08-01

Erection of electrical installations in potentially explosive atmospheres

39

ÖVE/ÖNORM E 8383 :2000-03-01

High-current systems with rated AC voltage above 1 kV

40

ÖVE/ÖNORM E 8384 :2007-05-01

Endings in alternating current systems with rated voltages above 1 kV

41

ÖVE/ÖNORM E 8385 :2006-05-01

Operation of electrical installations-Special specifications for agricultural and hortic-building facilities

42

ÖVE/ÖNORM E 8555 :2000-08-01

Operation of electric trains and trolleybuses

43

ÖVE/ÖNORM E 8701-1:2003-01-01

Inspection after repair and re-installation of electrical equipment-Part 1: General requirements

44

ÖVE/ÖNORM E 8701-2-2:2003-11-01

Inspection after repair and reconversion and re-examination of electrical equipment-Part 2-2: Special requirements for power tools

45

ÖVE-EN 1, part 2:1993-04

Erection of heavy-current installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 2: Electrical operating equipment (excluding § 28, this is not applicable)

46

ÖVE-EN 1, part 2a: 1996-03

Night rag a to Part 2: 1993-04

Erection of heavy-current installations with nominal voltages up to 1000 V and = 1500 V-Part 2: Electrical operating equipment (excluding § 28, this is not applicable)

47

ÖVE-EN 1, part 3 (§ 40): 1998-11

Construction of heavy-power plants up to 1000 V and = 1500 V-Part 3: Nature, dimensioning and laying of cables and cables-§ 40 Nature and use of cables and cables

48

ÖVE-EN 1, part 3 (§ 41): 1995-03

Construction of heavy-current systems with nominal voltages up to ~ 1000 V and = 1500 V-Part 3: Nature, dimensioning and laying of lines and cables-§ 41 Measurement of cables and cables in mechanical and electrical respects, overcurrent protection

49

ÖVE-EN 1, part 3 (§ 42): 1998-03

Construction of heavy-current installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 3: Nature, dimensioning and laying of cables and cables-§ 42 laying of cables and cables

50

ÖVE-EN 1, part 4 (§ 49): 1996-03

Erection of high-voltage power plants with nominal voltages up to 1000 V and = 1500 V-Part 4: Special installations-§ 49 Baderrooms, Shower corners, swimming pool and sauna facilities

51

ÖVE-EN 1, part 4 (§ 53 )/1988

Construction of heavy-current systems with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-§ 53 Replacement power supply systems and other power supply systems for temporary operation

52

ÖVE-EN 1, part 4 (§ 54 )/1989

Construction of high-voltage power plants with nominal voltages up to ~ 1000 V and = 1500V-Part 4: Special installations-§ 54 classrooms with experimental stands

53

ÖVE-EN 1, part 4 (§ 55): 1997-11

Erection of Starkstromanlagen up to 1000 V and = 1500 V-Part 4: Special Appendices-§ 55 Construction sites and Provisories

54

ÖVE-EN 1, part 4 (§ 57 )/1989

Construction of heavy-current installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-§ 57 Electrical installations for security purposes

55

ÖVE-EN 1, part 4 (§ 58 bis § 59 )/1983

Construction of heavy-current installations with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-§ 58 to § 59 (excluding § 58, this is not applicable)

56

ÖVE-EN 1, part 4 (§ 60 )/1983

Construction of heavy-current systems with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-60 auxiliary circuits

57

ÖVE-EN 1, part 4 (§ 65 )/1985

Construction of high-voltage power plants with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-§ 65 Limited, conductive spaces

58

ÖVE-EN 1, part 4 (§ 90 )/1983

Construction of high-voltage power plants with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special installations-§ 90 Garages, working pits and subfloor systems for motor vehicles

59

ÖVE-EN 1, part 4 (§ 92): 1997-11

Construction of heavy-power plants up to 1000 V and = 1500 V-Part 4: Special installations-§ 92 Electrical plants on campsites and in caravans

60

ÖVE-EN 1, part 4 (§ 93): 1997-11

Erection of Starkstromanlagen up to 1000 V and = 1500 V-Part 4: Special installations-§ 93 Electrical systems for marinas (berths) and water sports vehicles

61

ÖVE-EN 1, part 4 (§ 97 )/1990

Construction of high-voltage power plants with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special facilities. -§ 97 Flying buildings and wagons according to the type of Schaustellerart as well as their power supply

62

ÖVE-EN 31/1981

Construction of electric fence systems

63

ÖVE/ÖNORM EN 50107-1:2003-10-01

Luminous tube devices and luminescent tube systems with an idling voltage above 1 kV but not above 10 kV-Part 1: General requirements

64

ÖVE/ÖNORM EN 50110-1:2008-09-01

Operation of electrical installations Part 1: European Standard; Part 2-100: National additions

65

ÖVE EN 50110-2-700:1998-11

Operation of electrical installations-Part 2-700: Operation of electrical installations in mining

66

ÖVE/ÖNORM EN 50341: 2002-09-01

Free lines over ~ 45 kV

-Part 1: General requirements-Joint provisions

-Part 2: Index of National Normative Provisions (NNA)

-Part 3: National Normative stipulations (NNA) for Austria

67

ÖVE/ÖNORM EN 50341/AC1:2007-01-01

Free lines via AC 45 kV, Corrigendum

68

ÖVE/ÖNORM EN 50423 :2005-09-01

Power lines via AC 1 kV up to and including AC 45 kV

69

ÖVE/ÖNORM EN 60335-1:2007-11-01

(Only for joint application with ÖVE/ÖNORM EN 60335-2-76:2008-10-01)

Safety of electrical appliances for domestic use and similar purposes-Part 1: General requirements

70

ÖVE/ÖNORM EN 60335-2-76:2008-10-01

Safety of electrical appliances for domestic use and similar purposes-Part 2-76: Special requirements for electric fence aisles

71

ÖVE/ÖNORM EN 62305-3:2008-01-01

Lightning protection-Part 3: Protection of construction plants and persons (except for table 1 last line and section 4.1 last paragraph)

72

ÖVE/ÖNORM IEC 60884-1:2005-09-01

Plugs and sockets for domestic use and similar purposes-Part 1: General requirements

73

ÖVE-IG/EN 50075/1990

Flat, non-reconnectable, two-pole plug, 2.5 A 250 V, with line for connection of Class II devices for household and similar purposes

74

ÖVE-L 1/1981

Erection of high-power supply lines up to 1000 V

75

ÖVE-L 1a/1986

Supplement a to the provisions relating to the construction of power lines up to 1000 V, ÖVE-L1/1981

II. ÖNORMEN

No.

Label

Title

Output Date

1

ÖNORM E 6610

Triple-pole sockets with N-and with protective contact; Main dimensions 16 A, ~ 220/380 V, 16 A, ~ 230/400 V

Jänner 1991

2

ÖNORM E 6611

Three-pole plug with N-and with protective contact;

Main dimensions 16 A, ~ 220/380 V, 16 A, ~ 230/400 V

Jänner 1991

3

ÖNORM E 6612

Triple-pole sockets with N-and with protective contact; Main dimensions 25 A, ~ 220/380 V, 25 A, ~ 230/400 V

Jänner 1991

4

ÖNORM E 6613

Triple-pole plug with N-and with protective contact; Main dimensions 25 A, ~ 220/380 V, 25 A, ~ 230/400 V

Jänner 1991

5

ÖNORM E 6620

Two-pole plug for class II devices, 2.5 A, 250 V

May 1994

6

ÖNORM E 6622-1

Double-pole socket with protection contacts of type A; 10/16 A, 250 V

1 April 1996

7

ÖNORM E 6622-2

Two-pole socket with protection contacts of type B, 10/16 A, 250 V

1 November 1996

8

ÖNORM E 6622-6

Plug-in devices for home installations and similar purposes-Two-pole plug for Class II devices, splash-proof, for = 10 A/ ~ 16 A, 250 V or ~ 16 A, 250 V

1 April 1996

9

ÖNORM E 6622-7

Plug-in devices for domestic installations and similar purposes; two-pole plug with protective contacts, splash-proof, 10/16 A, 250 V

1 April 1996

10

ÖNORM E 6622-8

Plug-in devices for domestic installations and similar purposes; two-pole coupling sockets with protective contacts, splash-proof, 10/16 A, 250 V

1 April 1996

11

ÖNORM E 6622-9

Plug-in devices for domestic installations and similar purposes; two-pole safety sockets with protection contact 10/16 A, 250 V with shutter; Teaching L2

1 April 1996

12

ÖNORM E 6622-10

Plug-in devices for domestic installations and similar purposes; basic design of sockets; built-in sockets; Teaching L1

November 1986

13

ÖNORM E 6622-11

Plug-in devices for domestic installations and similar purposes; Two-pole mounting socket and non-lockable coupling sockets 2.5 A, 250 V and teachings

1 April 1996

14

ÖNORM E 6623

Two-pole plug with protection contacts 10/16 A, 250 V

1 April 1996

15

ÖNORM E 6624

Plug-in devices for home installations and similar purposes-Two-pole plug for Class II devices for

= 10 A/ ~ 16 A, 250 V or ~ 16 A, 250 V

1 April 1996

Annex II

List of electrotechnical safety regulations and regulations on normalization and typing (SNT regulations) according to the state of the Electrical Engineering Ordinance 2002, BGBl. (II) No 222/2002, the liability of which is repealed in accordance with Article 2 (2)

Note: The numbers correspond to those set out in Annex I to ETV 2002, as amended by the BGBl Regulation. II No 33/2006.

I. Austrian regulations for electrical engineering

No.

Label

Title

1

ÖVE-E 5, part 9/1982

Operation of Starkstromanlagen -Part 9: Special provisions for the operation of electrical installations in explosion-hazard facilities

2

ÖVE-E 15/1985

Operation of Starkstromanlagen in Agricultural Estate

22

ÖVE/ÖNORM E 8002-1:2002-11-01

High-power plants and safety power supply in construction sites for human gatherings-Part 1: General

23

ÖVE/ÖNORM E 8002-2:2002-11-01

High-power plants and safety power supply in building facilities for human gatherings-Part 2: Event venues

28

ÖVE/ÖNORM E 8002-8:2002-11-01

High-power plants and safety power supply in construction facilities for human gatherings-Part 8: Flying buildings as venues, sales outlets, exhibition venues or shanks and dining economies

30

ÖVE/ÖNORM E 8007/A1:2001-02-01

High-current installations in hospitals and medical-use rooms outside hospitals-change A1 to ÖVE-EN 7/1991

31

ÖVE/ÖNORM E 8007/A2:2002-11-01

High-current installations in hospitals and medical-use rooms outside hospitals-Amendment A2 to ÖVE-EN 7/1991

32

ÖVE/ÖNORM E 8007/AC1:2004-04-01

High-current installations in hospitals and medical facilities outside hospitals (rectification)

33

ÖVE/ÖNORM E 8049-1:2001-07-01

Lightning protection of constructional installations-Part 1: General principles (only protection classes I to III permitted)

34

ÖVE/ÖNORM E 8065 :2005-08-01

Erection of electrical installations in potentially explosive atmospheres

35

ÖVE/ÖNORM E 8111 :2002-09-01

Erection of high-power supply lines over ~ 1 kV up to ~ 45 kV

40

ÖVE-EH 41/1987 identical to

ÖVE-EH 41/1975 +

ÖVE-EH 41a/1980 +

ÖVE-EH 41b/1986

Endings in alternating current systems with rated voltages above 1 kV (§ § 19 and 20 only)

57

ÖVE-EN 1, part 4 (§ 95 )/1991

Construction of high-voltage power plants with nominal voltages up to ~ 1000 V and = 1500 V-Part 4: Special facilities. -§ 95 lifts

58

ÖVE-EN 1, part 4 (§ 95a): 1997-11

Supplement a to Part 4 (§ 95) 1991

Erection of Starkstromanlagen up to 1000 V and = 1500 V-Part 4: Special Appendixes-§ 95 lifts

60

ÖVE-EN 7/1991

High-power plants in hospitals and medical-use rooms outside hospitals

61

ÖVE-EN 7a: 1994-06

Night rag a to ÖVE-EN 7/1991 Starkstromanlagen in hospitals and medically used rooms outside of hospitals

64

ÖVE EN 50110-1:1997-06

(EN 50110-2-100 incorporated)

Operation of electrical installations

Part 1: European Standard

Part 2-100: National additions

67

ÖVE/ÖNORM EN 60335-1 + A1 + A2 + A11 + A12 + A13 + A14 + A15 + A16: 2001-10-01

(Only for joint application with ÖVE/ÖNORM EN 60335-2-76 + A1:2002-11-01 mandatory)

Safety of electrical appliances for domestic use and similar purposes-Part 1: General requirements

68

ÖVE/ÖNORM EN 60335-2-76 + A1:2002-11-01

Safety of electrical appliances for domestic use and similar purposes-Part 2-76: Special requirements for electric fence aisles

69

ÖVE/ÖNORM IEC 60884-1:2000-03-01

Plugs and sockets for domestic use and similar purposes-Part 1: General requirements

II. ÖNORMEN

No.

Label

Title

Output Date

1

ÖNORM E 2790

Electrical installations, grounding facilities, fundamenteres

July 1991

9

ÖNORM E 6622-3

Plug-in devices for domestic installations and similar purposes; Mobile multiple-table sockets; sockets for 2.5 A, socket outlets for 10/16 A with protective contacts, 250 V

1 April 1996

10

ÖNORM E 6622-4

Plug-in devices for domestic installations and similar purposes; Two-pole coupling sockets with protective contact 10/16 A, 250 V

1 April 1996

11

ÖNORM E 6622-5

Plug-in devices for home installations and similar purposes; adapter with 2 sockets 2.5 A, 250 V

1 April 1996

Annex III

Electro-technical safety regulations and regulations on normalization and typing (SNT regulations), which are declared binding in accordance with § 2 para. 1

CONTENT OVERVIEW

I. Austrian regulations for electrical engineering

No.

Label

Title

1

ÖVE/ÖNORM E 8001-1/A3:2007-10-01

Erection of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: Terms and protection against electric shock (protective measures) (amendment)

2

ÖVE/ÖNORM E 8001-1/A4:2009-04-01

Construction of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: Concepts and protection against electrical shock (protective measures) (Amendment + corrigendum 1) (excluding section 10.2.2.4)

3

ÖVE/ÖNORM E 8001-1-24:2006-01-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 1-24: protective measures-protection against undervoltage

4

ÖVE/ÖNORM E 8001-2-30:2008-12-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 2-30: switchgear and distributors

5

ÖVE/ÖNORM E 8001-2-39:2008-08-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-Part 2-39: busbar systems

6

ÖVE/ÖNORM E 8001-4-753:2009-04-01

Erection of electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 4-753: Electrical heating systems with heating lines and surface heating elements

7

ÖVE/ÖNORM E 8001-4-95:2008-12-01

Erection of electrical systems with rated voltages up to AC 1000 V and DC 1500 V-part 4-95: lifts

8

ÖVE/ÖNORM E 8002-1:2007-10-01

High-power plants and safety power supply in construction sites for human gatherings-Part 1: General

9

ÖVE/ÖNORM E 8002-2:2007-10-01

High-power plants and safety power supply in building facilities for human gatherings-Part 2: Event venues

10

ÖVE/ÖNORM E 8002-8:2007-10-01

High-power plants and safety power supply in construction facilities for human gatherings-Part 8: Flying buildings as venues, sales outlets, exhibition venues or shanks and dining economies

11

ÖVE/ÖNORM E 8007 :2007-12-01

High-power plants in hospitals and medical-use rooms outside hospitals

12

ÖVE/ÖNORM E 8014-1:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 1: General requirements and terms

13

ÖVE/ÖNORM E 8014-2:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 2: Fundamenterder

14

ÖVE/ÖNORM E 8014-3:2006-08-01

Construction of grounding systems for electrical installations with rated voltages up to AC 1000 V and DC 1500 V-Part 3: Special features of grounding systems in buildings with special EMC requirements of information technology facilities

15

ÖVE/ÖNORM E 8065 :2008-08-01

Erection of electrical installations in potentially explosive atmospheres

16

ÖVE/ÖNORM E 8384 :2007-05-01

Endings in alternating current systems with rated voltages above 1 kV

17

ÖVE/ÖNORM E 8385 :2006-05-01

Operation of electrical installations-Special specifications for agricultural and hortic-building facilities

18

ÖVE/ÖNORM EN 50110-1:2008-09-01

Operation of electrical installations Part 1: European Standard Part 2-100: National additions

19

ÖVE/ÖNORM EN 50341/AC1:2007-01-01

Free lines via AC 45 kV, Corrigendum

20

ÖVE/ÖNORM EN 50423 :2005-09-01

Power lines via AC 1 kV up to and including AC 45 kV

21

ÖVE/ÖNORM EN 60335-1:2007-11-01

(Only for common use with

ÖVE/ÖNORM EN 60335-2-76:2008-10-01)

Safety of electrical appliances for domestic use and similar purposes-Part 1: General requirements

22

ÖVE/ÖNORM EN 60335-2-76:2008-10-01

Safety of electrical appliances for domestic use and similar purposes-Part 2-76: Special requirements for electric fence aisles

23

ÖVE/ÖNORM IEC 60884-1:2005-09-01

Plugs and sockets for domestic use and similar purposes-Part 1: General requirements

24

ÖVE/ÖNORM EN 62305-3:2008-01-01

Lightning protection-Part 3: Protection of construction plants and persons (except for table 1 last line and section 4.1 last paragraph)

(Text of the SNT provisions see Annex) "