4620.4510 Measurement Of Air Quality Conditions


Published: 2015

Subscribe to a Global-Regulation Premium Membership Today!

Key Benefits:

Subscribe Now for only USD$20 per month, or Get a Day Pass for only USD$4.99.
4620.4510 MEASUREMENT OF AIR QUALITY CONDITIONS.


§
Subpart 1.

Measuring air quality.

Owners or operators of indoor ice arenas must measure carbon monoxide and nitrogen dioxide air concentrations in each arena when internal combustion engine-powered ice maintenance equipment is used.


§
Subp. 2.

Persons who can take measurements.

Measurements must be made by an individual who has received training as specified in part 4620.4450.


§
Subp. 3.

Measurements for ice resurfacing.

Owners or operators must measure air concentrations at least twice per week after using an internal combustion engine-powered ice resurfacer. Measurements must be taken:

§
A.

at board height, inside the boards, and at the centerline of the ice;


§
B.

20 minutes after completing resurfacing unless the commissioner has granted the operator approval to measure under an alternative schedule;


§
C.

at times of maximum use of the resurfacing machine; and


§
D.

at least once on Saturday or Sunday of each week that the arena is open to the public.



§
Subp. 4.

Measurements for ice edging.


§
A.

Owners or operators must measure air concentrations at least once per week after using an internal combustion engine-powered ice edger. Measurements must be taken following a time of maximum ice edger use at board height, inside the boards, and at the centerline of the ice:

§
(1)

20 minutes after completing edging if the arena building is open to the public when edging occurs; or


§
(2)

before the public reoccupies the arena, if the arena is not open to the public when edging occurs.



§
B.

Owners or operators may measure under an alternative schedule if the commissioner has approved one.



§
Subp. 5.

Measurement records.

Owners or operators must keep a record of measurement findings and make them available to the commissioner upon request.


§
Subp. 6.

Additional measurements.

Owners or operators must make additional measurements as determined by the commissioner.