4620.4510 MEASUREMENT OF AIR QUALITY CONDITIONS.
§
Subpart 1.
Measuring air quality.
Owners or operators of indoor ice arenas must measure carbon monoxide and nitrogen dioxide air concentrations in each arena when internal combustion engine-powered ice maintenance equipment is used.
§
Subp. 2.
Persons who can take measurements.
Measurements must be made by an individual who has received training as specified in part 4620.4450.
§
Subp. 3.
Measurements for ice resurfacing.
Owners or operators must measure air concentrations at least twice per week after using an internal combustion engine-powered ice resurfacer. Measurements must be taken:
§
A.
at board height, inside the boards, and at the centerline of the ice;
§
B.
20 minutes after completing resurfacing unless the commissioner has granted the operator approval to measure under an alternative schedule;
§
C.
at times of maximum use of the resurfacing machine; and
§
D.
at least once on Saturday or Sunday of each week that the arena is open to the public.
§
Subp. 4.
Measurements for ice edging.
§
A.
Owners or operators must measure air concentrations at least once per week after using an internal combustion engine-powered ice edger. Measurements must be taken following a time of maximum ice edger use at board height, inside the boards, and at the centerline of the ice:
§
(1)
20 minutes after completing edging if the arena building is open to the public when edging occurs; or
§
(2)
before the public reoccupies the arena, if the arena is not open to the public when edging occurs.
§
B.
Owners or operators may measure under an alternative schedule if the commissioner has approved one.
§
Subp. 5.
Measurement records.
Owners or operators must keep a record of measurement findings and make them available to the commissioner upon request.
§
Subp. 6.
Additional measurements.
Owners or operators must make additional measurements as determined by the commissioner.